background image

Outdoor Lifestyles by Hearth & Home Technologies  •  Installation Manual TWILIGHT-II-MOD  •  2290-970 Rev. H  •  5/14  

6

J.  Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in 
whole or in part for residential purposes, including those 
owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) 
feet above 

fi

 nished grade in the area of the venting, in-

cluding but not limited to decks and porches, the following 
requirements shall be satis

fi

 ed:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas 

fi

 tter 

shall observe that a hard wired carbon monoxide detector 
with an alarm and battery back-up is installed on the 

fl

 oor 

level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas 

fi

 tter shall observe that 

a battery operated or hard wired carbon monoxide detec-
tor with an alarm is installed on each additional level of 
the dwelling, building or structure served by the side wall 
horizontal vented gas fueled equipment. It shall be the 
responsibility of the property owner to secure the services 
of quali

fi

 ed licensed professionals for the installation of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic, 
the hard wired carbon monoxide detector with alarm and 
battery back-up may be installed on the next adjacent 

fl

 oor level.

In the event that the requirements of this subdivision can 
not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply 
with the above requirements; provided, however, that dur-
ing said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA 
720 and be ANSI/UL 2034 listed and IAS certi

fi

 ed. 

Signage

A metal or plastic identi

fi

 cation plate shall be permanent-

ly mounted to the exterior of the building at a minimum 
height of eight (8) feet above grade directly in line with the 
exhaust vent terminal for the horizontally vented gas fu-
eled heating appliance or equipment. The sign shall read, 
in print size no less than one-half (1/2) in. in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-
STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon-
tally vented gas fueled equipment shall not approve the 
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 
through 4. 

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4: 
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 
of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure separate 
from the dwelling, building or structure used in whole or 
in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 
horizontally vented gas equipment provides a venting 
system design or venting system components with the 
equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system 
shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the 

fl

 ue gases, but identi

fi

 es 

“special venting systems”, the following requirements 
shall be satis

fi

 ed by the manufacturer:

• The referenced “special venting system” instructions 

shall be included with the appliance or equipment in-
stallation instructions; and 

• The “special venting systems” shall be Product Ap-

proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation 
instructions. 

A copy of all installation instructions for all Product Ap-
proved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting 
instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion 
of the installation. 

See Gas Connection section for additional Common-
wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 
document.

Summary of Contents for TWILIGHT-II-MOD

Page 1: ...ble for use and operation OWNER Retain this manual for future reference NOTICE DO NOT discard this manual In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter SeeTable of Contents for location of additional Commonwealth of Massachusetts requirements TWILIGHT II MOD WARNING A barrier designed to reduce the risk of burns from the hot viewing glass i...

Page 2: ...uirements for the Commonwealth of Massachusetts 6 2 Getting Started A Design and Installation Considerations 7 B Tools and Supplies Needed 7 C Inspect Appliance and Components 7 3 Framing and Clearances A Appliance Dimension Diagram 8 B Clearances to Combustibles 9 4 Termination Location and Vent Information A Chimney Diagram 11 5 Appliance Preparation A Removing Non combustible Facing Material As...

Page 3: ...tting for installation type ___________________________ Finishing Section 8 Pg 22 24 Combustible materials not installed in non combustible areas ___________________________ Verified all clearances meet installation manual requirements ___________________________ Mantels and wall projections comply with installation manual requirements ___________________________ Appliance Setup Section 9 Pg 25 27...

Page 4: ...on NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in residential heating calculations NOTICE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code ANSI Z223 1 latest edition in the U S A...

Page 5: ... glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered non combustible materials H Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame...

Page 6: ...rizontally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors a...

Page 7: ...de paying particular attention to flashing and sealing in structions 2 In the cold northern climates pay attention to expo sures and prevailing wind conditions when locating the appliance the same as you would for locating exterior windows and doors The TWILIGHT II MOD has the thermal characteristics of a high quality window system Temperatures near the appli ance will be cooler than what is reali...

Page 8: ...C D C G H I J K L M N E ELECTRICAL ACCESS GAS LINE ACCESS Q VENT OPENING R P O F S S MEASURE TO BOTTOM OF LIP AS SHOWN IN T T OUTDOOR OUTDOOR OUTDOOR INDOOR VIEW OUTDOOR VIEW Location Inches Millimeter Location Inches Millimeter A 2 1 4 57 K 32 5 8 829 B 4 3 4 121 L 36 1 4 921 C 1 2 13 M 41 7 8 1064 D 43 1092 N 21 1 2 546 E 24 610 O 38 5 8 981 F 46 7 8 1191 P 42 1 8 1070 G 40 3 4 1035 Q 21 1 2 546...

Page 9: ...vary due to individual design preference WARNING Risk of Fire The exterior side of the TWILIGHT II MOD CANNOT be recessed into the framing GLASS EXTERIOR INSULATED ENVELOPE GLASS A B B D C 24 INCH MAX B GLASS FLUSH TO EXTERIOR INSULATED ENVELOPE GLASS E C NOTE Appliance may be installed flush on exterior interior or anywhere in between Any projection of the appliance interior or exterior must have...

Page 10: ... Do not install appliance against vapor barriers or exposed insulation Prevent contact with sagging or loose insulation Locate and install appliance to all clearance specifications in manual The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace Failure to maintain airspace may cause overheating and a fire Reference Figu...

Page 11: ...located between two single family dwellings and serves both dwellings Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft Covered Alcove Applications Spaces open only on one side and with an overhang CAUTION Risk of Burns Terminations are HOT consider proximity to doors traf...

Page 12: ...PLY HIGH TEMPERATURE SEALANT 300 F 149 C min BOTH SIDES APPLIANCE EXTERIOR A Removing Non combustible Facing Ma terial Assembly The non combustible assembly is located on right hand side of appliance when looking from outdoor side of appliance Hold non combustible pieces in place Remove and save two screws from upper bracket Remove non combustible pieces Remove and save three screws from lower bra...

Page 13: ...se wood shims Keep nailing tabs flush with the framing Secure the appliance to the framing by using nails or screws through the nailing tabs Placing Flashing and Sheathing Apply high temperature silicone sealant to corner edges of fireplace flange see Figure 5 3 Figure 5 3 Application of High Temperature Sealant Figure 5 4 Header Flashing Installation Install outdoor flashing header sheet metal pi...

Page 14: ...n combustible sheath ing and MAY extend over the flashing behind non com bustible sheathing a maximum of 1 inch Use high temp silicone or sealant recommended by the manufacturer of the housewrap to seal between combustible sheathing house wrap and non combustible sheathing The sealant material used within 6 inches of the top and 1 inch on the sides of the fireplace surround must be approved to a m...

Page 15: ...tallation of Non combustible Facing Material Outdoor Side Fire Risk Follow these instructions exactly Facing materials must be installed properly to prevent fire No materials may be substituted without authorization by Hearth Home Technologies Center and attach two top boards the two shorter pieces to the framing members See Figure 5 8 Attach the left and right side pieces to the framing mem bers ...

Page 16: ...nformation NOTICE Waterproof insulated wire should be used when wiring the junction box GREEN WIRE INSIDE BOX 14 2WG COPPER GROUND ATTACHED TO GRN SCREW WITH GRN WIRE BLK WHT WHT BLK HEAT SHIELD Junction Box Installation If the box is being wired from the OUTSIDE of the appliance Install the Romex connector not included with appliance in the side wrap Loosen two screws on the Romex connector feed ...

Page 17: ...ure 6 2 Fan Installation Fan should be positioned on the left side as viewed from appliance interior side See Figure 6 3 NOTE For ease of installation it is recommended that the fan be installed prior to gas line installation Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the appliance ...

Page 18: ...sformer Remove batteries before using the transformer and unplug the transformer before installing the batteries Battery polarity must be correct or module damage will occur Figure 6 4 Intellifire Pilot Ignition IPI Wiring Diagram NOTE 1 Ignition module valve pilot and wall switch operate on 3 volts Uninterrupted 120 VAC is required at junction box unless equipped with battery back up IGNITION MOD...

Page 19: ...x connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 in insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch connector 1 4 in male as shown Red Switch Switch Bo...

Page 20: ...ere are no ignition sources such as sparks or open flames Light the appliance It will take a short time for air to purge from lines When purging is complete the appliance will light and operate normally WARNING Risk of Fire Explosion or Asphyxiation Check all fittings and connections with a non corrosive commercially available leak check solution DO NOT use open flame Fittings and connections coul...

Page 21: ...e 2000 feet elevation In the USA Reduce burner orifice 4 for each 1000 feet above 2000 feet In CANADA Reduce burner orifice 10 for elevations between 2000 feet and 4500 feet Above 4500 feet consult local gas utility E Air Shutter Setting Air shutter settings should be adjusted by a qualified ser vice technician at the time of installation The air shutter is set at the factory NOTICE If sooting occ...

Page 22: ...nces Fire Risk Finish all edges and fronts to clearances and specifications listed in manual Black metal columns may be covered with non combustible material only Do NOT overlap combustible materials onto appliance front Install combustible materials only up to specified clearances on top front and side edges Seal joints between the finished wall and appliance top and sides using only a 300ºF mini...

Page 23: ...the appliance This non combustible finishing material can be up to a maximum of 6 inches thick 6 inches maximum horizontal overhang to allow for brick and stone alcoves See Figure 8 5 NOTE Combustible housewrap or building paper MUST NOT extend over the outside of non combustible sheathing and MAY extend over the flashing header behind non combustible sheathing Use high temp caulk to seal between ...

Page 24: ... OPENING MEASURED FROM CORNER TOP VIEW FIREPLACE HOOD 1 2 IN Note Measurements are in inches Figure 8 6 Clearances to a Combustible and or Non combustible Indoor Mantel Figure 8 7 Clearances to a Combustible and or Non combustible Indoor Mantel or Mantel Leg APPLIANCE HOOD TOP OF APPLIANCE SOFFIT SIDING HOUSEWRAP BUILDING PAPER AND SHEATHING 35 5 16 in MINIMUM CLEARANCE TO NON VINYL 64 5 16 in CLE...

Page 25: ...sembly Interior Side GLASS RETAINER BRACKET GLASS RETAINER BRACKET WING NUT ON THREADED STUD WING NUT ON THREADED STUD Removing Fixed Glass Assembly Interior Loosen two wing nuts on bottom glass retainer bracket Loosen and remove two wing nuts on top glass retainer bracket Remove glass retainer bracket See Figure 9 1 Lift glass assembly off of glass retainer bracket Replacing Fixed Glass Assembly ...

Page 26: ... that the smooth re flective side is facing the inside or viewing area of the fireplace USE SLOTS TO SLIDE REFRACTORY INTO POSITION Figure 9 3 Install Refractory GLASS LATCH GLASS LATCH Removing Fixed Glass Assembly Exterior Remove vanity panel from appliance to expose glass latches Pull glass latch out to release Grasp glass assembly on sides and pull bottom toward you Slide glass assembly down a...

Page 27: ... glass refractory This area must remain open for proper air flow See Figure 9 4 Figure 9 4 No Glass Rock Media in Gap NOTICE Care should be taken to avoid placing glass rock media between the left and right of the media tray and the firebox Blocking this gap may cause an undesirable flame appearance See Figure 9 4 NO MEDIA IN SHADED AREA BOTH LEFT AND RIGHT SIDE WARNING Risk of explosion DO NOT pl...

Page 28: ...accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and will void the warranty Decorative Doors and Fronts WARNING Risk of Fire Install ONLY doors or fronts approved by Hearth Home Technologies Unapproved doors or fronts may cause fireplace to overheat T...

Reviews: