INSTALLATION GUIDE

7.5.2021

I

max Al

I

max Cu

U

max

VC05-0387

220 A

245 A

1000 A

-

-

-

VC05-0390

220 A

245 A

1000 A

-

-

-

VC05-0391

220 A

245 A

1000 A

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Screw size

Screw 1

M14

Tightening torque 

M

Stripping length 

L

20 mm

 

SW 1

6

6-25 mm²

12 Nm

35-95 mm²

22 Nm

Busbar Cu 3x1x24

8 Nm

Max. wire cross section

95 mm²

1,5 mm

2

2,5 mm

2

6 mm

2

10 mm

2

16 mm

2

25 mm

2

35 mm

2

50 mm

2

-

-

3

3

3 (1)

3 (1)

2 (1)

1 (1)

70 mm

2

95 mm

2

120 mm

2

150 mm

2

185 mm

2

240 mm

2

300 mm

2

400 mm

2

1 (1)

1 (1)

-

-

-

-

-

-

Ouneva Oy

Teollisuustie 21

Tel. +358 400 179 750

www.ounevagroup.fi

FI-82730 Tuupovaara, Finland

[email protected]

www.ounevaproducts.fi

Mounting

Product information

Product code

Product name

I

n Al

I

n Cu

U

n

USA specific

OTL branching connector 2xAl/Cu 6-95mm² FBB (Grey)
OTL branching connector 2xAl/Cu 6-95mm² FBB (Blue)
OTL branching connector 2xAl/Cu 6-95mm² FBB (Yellow/Green)

 
 

DIN-rail and screw (M5) mounting

Connection

Copper conductors

Aluminium conductors

Supported IEC 60228 -conductors

Sector shaped cable

 

Conductor installation

Input

Cross section and max. number of Cu- conductors / space (Al- conductors in parenthesis)

Marking

5 mm width 

(Eg. Partex TX)

Removal

Release the slider and lift 

connector

DIN rail mounting

Set connector on DIN rail. Push 

until connector locks down.

Screw mounting

max. Ø5 mm screw

L

SW

Max. Busbar (3x1x24)

Class 5 & 6 (fine stranded) Using 

ferrule is recommended

Class 1 & 2 (solid and 

stranded)

Max. 3 X CU / 

Conductor space

1 X AL / Conductor 

space

Anti-corrosion paste: 

e.g. Penetrox

Pre-round the cable

≤ 95 mm² total

Max. 95 mm² Al / Cu

Support connector during 

tightening the screws

The specified max. amount of 

conductors refers only to industrially 

installed terminals.