INSTALLATION GUIDE
7.5.2021
I
max Al
I
max Cu
U
max
VC05-0387
220 A
245 A
1000 A
-
-
-
VC05-0390
220 A
245 A
1000 A
-
-
-
VC05-0391
220 A
245 A
1000 A
-
-
-
Type
Screw size
Screw 1
M14
Tightening torque
M
Stripping length
L
20 mm
SW 1
6
6-25 mm²
12 Nm
35-95 mm²
22 Nm
Busbar Cu 3x1x24
8 Nm
Max. wire cross section
95 mm²
1,5 mm
2
2,5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
35 mm
2
50 mm
2
-
-
3
3
3 (1)
3 (1)
2 (1)
1 (1)
70 mm
2
95 mm
2
120 mm
2
150 mm
2
185 mm
2
240 mm
2
300 mm
2
400 mm
2
1 (1)
1 (1)
-
-
-
-
-
-
Ouneva Oy
Teollisuustie 21
Tel. +358 400 179 750
www.ounevagroup.fi
FI-82730 Tuupovaara, Finland
www.ounevaproducts.fi
Mounting
Product information
Product code
Product name
I
n Al
I
n Cu
U
n
USA specific
OTL branching connector 2xAl/Cu 6-95mm² FBB (Grey)
OTL branching connector 2xAl/Cu 6-95mm² FBB (Blue)
OTL branching connector 2xAl/Cu 6-95mm² FBB (Yellow/Green)
DIN-rail and screw (M5) mounting
Connection
Copper conductors
Aluminium conductors
Supported IEC 60228 -conductors
Sector shaped cable
Conductor installation
Input
Cross section and max. number of Cu- conductors / space (Al- conductors in parenthesis)
Marking
5 mm width
(Eg. Partex TX)
Removal
Release the slider and lift
connector
DIN rail mounting
Set connector on DIN rail. Push
until connector locks down.
Screw mounting
max. Ø5 mm screw
L
SW
Max. Busbar (3x1x24)
Class 5 & 6 (fine stranded) Using
ferrule is recommended
Class 1 & 2 (solid and
stranded)
Max. 3 X CU /
Conductor space
1 X AL / Conductor
space
Anti-corrosion paste:
e.g. Penetrox
Pre-round the cable
≤ 95 mm² total
Max. 95 mm² Al / Cu
Support connector during
tightening the screws
The specified max. amount of
conductors refers only to industrially
installed terminals.