INSTALLATION GUIDE
Product code
I
n Al
I
n Cu
U
n
I
max Al
I
max Cu
U
max
VG03-0007
380 A
425 A
1000 V
-
-
-
VG03-0035
380 A
425 A
1000 V
-
-
-
VG03-0036
380 A
425 A
1000 V
-
-
-
Type
Screw size
Screw
S
M16
Tightening torque
M
S
95-240 mm²
25 Nm
30 mm
SW
S
8
M
H1
2,5-35 mm²
6 Nm
(output)
L
2
16 mm
Screw
H1
M8
M
H2
6-50 mm²
10 Nm
SW
H1
4
-
-
Screw
H2
M10
Max. Input cable
240 mm²
SW
H2
5
Max. Output cable
50 mm²
1,5 mm
2
2,5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
35 mm
2
50 mm
2
-
0/3/0
0/3/3
0/3/3
0/2/3
0/1/2
0/1/1
0/0/1
70 mm
2
95 mm
2
120 mm
2
150 mm
2
185 mm
2
240 mm
2
300 mm
2
400 mm
2
-
2/0/0
2/0/0
1/0/0
1/0/0
1/0/0
-
-
Ouneva Oy
Teollisuustie 21
Tel. +358 400 179 750
FI-82730 Tuupovaara, Finland
17.1.2018
Product data
Product name
OJL-connector 400 C
Installation
OJL-connector 400 C Blue
OJL-connector 400 C Green
DIN-rail and screw mounting
Cross-section of conductors and max. number of conductors/ space (for Cu-conductors). ( S / H1 / H2 )
Connection
Stripping length (input)
L
1
Note! The specified amount of
conductors refers only to industrially
installed terminals.
DIN-rail mounting
Set the connector on a DIN-rail.
Push until connector locks
down.
Mounting with a screw
Max. Ø 5
Removing from DIN-rail
Release the slider part with a
screwdriver. Lift the
connector.
SW
Sc
rew
Connect the
input
conductor when the cover is open. Both the copper- or aluminium conductors
can be used in the input. Note! When using the aluminium conductor, it is only allowed to use
one conductor/one space.
With the Al-conductors, it's recommended to use anti-corrosion paste. (e.g. Penetrox)
We recommend a ferrule when using a fine-stranded conductor.
The branching conductors
H1
and
H2
can be connected also when
the cover is closed. Note! It's only allowed to use Cu-conductors for
branching.
Output
H
2
Output
H
1
Input
S
Screw
S
Sw
S
Screw
H2
Sw
H2
Screw
H1
Sw
H1
M
S
M
H2
M
H1
L
1,2