OUMAN M-LINK Manual Download Page 12

12

Setting

Factory 

setting

Description (see figure, page 5)

Gateway port 1
(First port of device 
that is connected to 
C-Serial)

503

 A M-Link-compatible device can be connected to M-Link’s C connector as a master device. The 

M-Link-compatible device may have one or more RTU buses. The port setting of Modbus master 
1 bus is specified here. The Port 1 setting determines the TCP/IP port serving as the gateway to 
the Modbus RTU bus of the M-Link- compatible device. 

Gateway port

 2

(Second port of device 
that is connected to 
C-Serial)

504

 The M-Link-compatible device may have several RTU buses. The port setting of Modbus master 
2 bus is specified here. The Port 2 setting determines the TCP/IP port serving as the gateway 
to the Modbus RTU bus of the M-Link- compatible device (for example, an Ouflex M device may 

have two RTU buses in use (A1, B1 and A2, B2)

Gateway port 

(Internal registers of 

M-LINK)

505

M-Link’s internal register details are read via this port. 

Port 4 (Internal re-

gisters of device 

that is connected to 

C-Serial)

502

Port 4 is reserved for the internal communication of a M-Link-compatible device connected to 
M-Link. Information from the Modbus register of a M-Link-compatible device connected to M-
Link is read/written via this port.

Port 5 (Port for de-

vices that has con-

nected to modbus 

RTU)

506

M-Link’s own port to the RTU bus (strip terminals 5 (A) and 4 (B). If the port value is 0, port con-

nection is not open.

Slave address for in-

ternal registers

1

When a M-Link-compatible device (Ouflex M, Ouflex M BA, S203, C203, H23) is connected to M-
Link via the C connector as a slave device, the address of the device is set here. 

Maximum number of 

connections

20

The server load can be changed by changing this setting. The setting determines the maximum 
number of allowed simultaneous connections from different IP addresses to the server.

Size of requests 

buffer

50

Buffer for TCP requests.

Idle timeout before 

connections close

300

This determines the time after which inactive connections are disconnected from the server. 
Value 0 means that idle timeout is not in use.

Allowed client add-

ress

0.0.0.0

 The data security of the system can be improved by activating the allowed client address func-
tion. If the value is 0.0.0.0, connections from any IP address to the server are enabled. When you 
specify a certain connection address, only contacts from the specified IP address are allowed.
Refresh view.

1. LAN is routed via Internet

The Access service operates on the Internet so the Access service is not available if the device is not connected to the Internet. The 

Access device examines the availability of Internet connection by sending a Ping packet to the Internet server at 3-minute intervals.

The network must allow the ICMP outwards from any port and the receipt of the reply message to the same port.

2. The VPN protocol used by Access service outwards is not blocked

The Access service is based on the VPN connection which the Access device creates to the Access server.

The network must allow the UDP outwards from any port to the port 1194 and the receipt of the reply message to this port.

3. Time service protocol outwards is not blocked

The Access service works only when the clock in the Access device shows the correct time. The clock is set to the correct time from 

the network using the NTP protocol.

The network must allow the UDP outwards from any port to the port 123 and the receipt of the reply message to this port.

Access service requirements

Modbus TCP

Modbus TCP/IP settings are used to change the Modbus TCP server settings.   The Modbus TCP/IP in-

terface can be used for communication with Modbus/RTU slave devices connected to the device. 

Summary of Contents for M-LINK

Page 1: ...nk s terminal strips 2 5 8 3 6 1 4 7 2x0 8 2x 2 1 x0 24 RX B TX A External power supply for M Link An external power supply is used if no M Link compatible device is connected to M Link s C connector Modbus RTU bus Connectors 7 and 8 are not used 2 2 3 1 M LINK is a media converter for converting Ouman s Modbus RTU TCP based devices or those of other manufacturers to the Ouman system The device ca...

Page 2: ...e power supply of an M Link device comes from an Ouman device con nected in the C connector Supported Ouman devices C203 v 1 5 1 the older versions must be updated to obtain M Link support Ouflex C Platform v 4 0 0 Ouflex M Platform v 1 2 0 Ouflex M BA Platform v 1 0 0 S203 v 1 2 0 Ouflex M or Ouflex M BA RJ45 connector S203 or H23 RJ45 I connector Modbus RTU bus Older Ouman devices such as EH 203...

Page 3: ...blic network If the device is in an internal network you can establish a browser con nection to the device by reading the QR code or by entering the www address in the label The address is in the format https and enter then the web address on the label so that the ouman net is replaced by text ouman local For example https m00000735 40rxr ouman local If you do not know the www address of the M Lin...

Page 4: ...in the C connector M LINK Enter the URL as the IP address do not enter https or www Url address can be found on the sticker on the side of M Link The default port is 502 If you want to activate the transfer of SNMP alarms give the Device address Add the template from the file or Ounet or download it from the device When connecting an Ouman device to a C connector check in the device s network sett...

Page 5: ... connected device An external operating voltage source is not requi red The firmware version of the device connected via the C bus can be updated remotely where necessary The application of the device connected via the C bus can be uploaded remotely Ouflex M BA and Ouflex M if the Ouflex M device has a memory card in place Through the device connected to the C bus you can read Modbus devices that ...

Page 6: ...RTU settings TE PE Datajamak 2 x 2 1 x 0 24 The protective shield extends from one device to the next without a break Terminal resisstor 120 ohm Master device M Link A B C203 A1 B1 H23 A B S203 A B Ouflex M BA A1 B1 Ouflex M A1 B1 or WL Base A B C203 slave all versions S203 or H23 slave all versions Modbus device WL BASE Ouflex M or Ouflex M BA slave 23 B1 6 B B B 7 B1 6 BG 22 A1 21 BG 3 A A A 8 A...

Page 7: ...ect Devices 3 Select Modbus master SerialPort2 4 Select Add device 5 If the device you want to add is on the list select the device 6 Just select points from the list of points you want to read 7 If the device cannot be found from the list select New device name the device and enter a unique device address 8 8 Add the new device s points to the points list Create the points for the device by right...

Page 8: ...oint transfer between devices connect devices to the bus of the M Link Add a device you want to write or read through the bus Enter the IP address You can read the device points of another device Make a point transfer C203 Master Master Ouflex M or Ouflex M BA Ouflex master The switch device Modbus TCP Modbus TCP Modbus TCP Internet Master S203 tai H23 connector I Point transfer from device to ano...

Page 9: ...s point where you want to read the source field point Drag and drop the point to the Tar get field If you select synchronize you can both read and alter the device point you can alter the value of the point from either device Select the Point bindings tab Select Bus points Select the device whose point data is to be read Select the point you want to read Drag and drop the point to the Source field...

Page 10: ...alendar details of the controller connected to M Link via a C connector will also be updated from the server Time zone UTC offset The current time zone Finland s time zone is 2 00 DST in use If you select DST in use the device will automatically switch between winter time and daylight saving time according to the calendar Controller Ouman device connected to an Ouman device via a C connector Contr...

Page 11: ...tory setting Description SNMP server IP 10 1 1 23 The IP address of the destination server where the message is sent Ounet s IP address 10 1 1 23 is the default Retry delay 5 min If the alarm is not acknowledged from the server the alarm message will be resent after the delay that is set SNMP in use This selection enables disables the entire SNMP function The SNMP function can be used for alarm tr...

Page 12: ...determines the maximum number of allowed simultaneous connections from different IP addresses to the server Size of requests buffer 50 Buffer for TCP requests Idle timeout before connections close 300 This determines the time after which inactive connections are disconnected from the server Value 0 means that idle timeout is not in use Allowed client add ress 0 0 0 0 The data security of the syste...

Page 13: ... registers 1 Serial port A1 B1 settings Port baudrate 9600 Speed of traffic in the bus The devices connected to the same bus must have the same traffic speed baud rate The default rate is 9600 bauds but it can be changed Data bits 8 Number of data bits in the bus The devices connected to the same bus must have the same Data bits value Parity None Parity of the bus None parity is not taken into acc...

Page 14: ...es or are factory settings restored Clear set values You can also cancel the update Cancel updat ing Change password You can change the password of the M Link device Username service and the password pwd is shown in the label at the end of the M Link device Current password Enter the current password in the Current password field New password Enter the new password in the New password field Confir...

Page 15: ... the Ounet Allows connecting Modbus RTU devices over a Modbus TCP IP network and vice versa Different bus point transfers can be made from one device to the next for example reading the outdoor temperature to the EH 203 and the EH 105 via the RTU bus Use of I O cards over a TCP IP network Update of C and M based devices and remote downloading of software ...

Page 16: ... RS 232 RS 485 Modbus RTU Operating voltage 16 30 VDC 1 4 W or 24 VAC 20 25 3 6 VA Ethernet protocols Modbus TCP HTTP SNMP and FTP Approvals EMC Interference tolerance EMC Interference emissions EN 61000 6 1 EN 61000 6 3 System dependency Can be connected to Ounet Modbus TCP IP support Warranty 2 years Manufacturer Ouman Oy XM1368_M Link_User manual_v 2 5 0_ENG_20180918 91 mm 71 mm 4M 59 mm We res...

Reviews: