14
Table 3: Airflow tables U
NIQUE
Advantage ECM ½ HP motor
AC / HP SIZE
Adjustment
BLUE wire position
A/C size
(TONS)
CFM ²
AC/HP CFM
ADJUST
BLACK wire
position = (NOM)
CFM ²
AC/HP CFM
ADJUST
BLACK wire position
= (LO)
CFM ²
AC/HP CFM
ADJUST
BLACK wire position
= (HI)
36
3.0
1200
1080
1320
30
2.5
1000
900
1100
24
2.0
800
720
880
18
1.5
600
540
660
AC / HP SIZE
Selection
BLUE wire position
A/C size
(TONS)
CFM ¹
CONTINUOUS
FAN
YELLOW wire
position = (LO)
CFM ¹
CONTINUOUS FAN
YELLOW wire
position = (MED)
CFM ¹
CONTINUOUS FAN
YELLOW wire
position = (HI)
36
3.0
600
960
1200
30
2.5
500
800
1000
24
2.0
400
640
800
18
1.5
300
480
600
HEAT KW/CFM
adjustment
RED wire position
POWER
(Kw)
CFM
First stage
24 VAC on W1 ¹
CFM
Second stage
24 VAC on W1
and/or W2 ¹
25
25
715
1359
23/20
23
620
1178
23/20
20
620
1178
18/15
18
450
855
18/15
15
450
855
10
10
238
452
ON / OFF DELAY
Adjustment
WHITE wire position
ON-Delay
Time
OFF-Delay
% CFM - Time
0 / 90
0 sec.
100% - 90 sec.
30 / 90
30 sec.
100% - 90 sec.
0 / 0
0 sec.
0 sec.
ENH
30 sec.
70 % - 150 sec.
No adjustment
required
ON-Delay
Time
OFF-Delay
% CFM - Time
-
0 sec.
50% - 60 sec.
¹ Remove the Jumper
J2
when a 2 stages thermostat is used
ON & OFF DELAY FOR COOLING AND HEAT PUMP HEATING
DELAY PROFILE FOR ELECTRIC HEATING MODE
COOLING OR HEAT PUMP HEATING MODE (WITH HP-EFF SELECTED ¹)
¹ "SYSTEM TYPE"
² In Cooling - Dehumidification mode (with Jumper
J1
remove), with no 24 VAC input to DH, the CFMs are
reduced by 15%.
The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 only (Y/Y2 not powered)
CONTINUOUS FAN
¹ CFM's when AC/HP CFM ADJUST at NOM position. CFM's 10% lower or higher if AC/HP CFM ADJUST at
LO or HI position.
ELECTRIC HEATING MODE