I N S T A L L A T I O N

11

•  The fan must be installed according to the air direc-

tion label on the fan.

•  The fan must be connected to duct or equipped with 

a safety grille.

•  The fan should be installed in a safe way and make 

sure that no foreign objects are left behind.

•  The fan should be installed in a way that makes ser-

vice and maintenance easy. N.B.! Consider the 
weight and size of the fan.

•  The fan should be installed in a way that vibrations 

not can be transfused to duct or building. To provi-
de this, use for example a flange.

•  Electrical installations must be made by an authori-

zed electrician.

•  See Wiring diagram at the lid of the junction box.
•  Electrical installation must be connected to a local-

ly situated isolator switch or by a lockable main 
switch.

•  Control that the fan is installed and connected elec-

trically in the right way, grounded and with motor 
protection.

•  For single phase fans a residual current device i used  

(type A).

•  For 3-phase fans a residual current circuit breaker is 

used  (type B). 

AC-MOTOR

•  For speed regulation of AC motor a transformer or 

thyristor can be connected.

•  The AC motor has a built-in thermal contact.
• The capacitor (only for AC motor) has finite life-

time and should be exchanged after 45.000 opera-
tion hours (about 5 years of operation) to secure 
maximum function. Defective capacitor can cause 
damage.

EC-MOTOR

• Speed regulating of EC 

motor can be done with 
the built-in potentio-
meter, 0-10 V. 
An external potentio-
meter can be connected 
to the terminal if neces-
sary. The internal poten-

tiometer should then 

be disconnected. 

•  IRB EC (does not apply for  125 B1/160B1/200 C1/

250 A1/250 B1/400x200 C1/500x250 A1/500x 
250 B1) has a potentional free alarm relay that 
breaks at max AC 250 V 2A, ”K1”

Fans eqipped with a tachometer, see page 15 Tech-
nical Data, for number of pulses per revolution.

•  Some EC motors has tachometer output one pulse 

per revolution.

• EMC-compatible installation of external control 

lines: The control cable must not be longer than 30 
m. Screened control cables must be used when the 
cable length is longer than 20 m. When using a shi-
elded cable connect the shielding to one side only, 
i.e. only to the device with the protective ground 
(keep cable short and with as little inductance as 
possible!). Pay attention to sufficient distance from 
power lines and motor wires to prevent interferen-
ces.  

Attention! 

Ensure correct polarity! Never 

apply line voltage to analog inputs!

•  The EC motor has electronically thermal-/over-

voltage protection.

MODBUS

. For Modbus, the fan types IRB 250 E1 EC,

IRB 500x 250 E1 EC, IRB 315 A1 EC and IRB
600x300 A1 EC applies:
• Baud rate: 19200
• Bits: 8
• Parity: None
• Stop bits: 1
• Handshake: None

E N G L I S H

Summary of Contents for IRB 1000x500 F3 EC

Page 1: ...SVENSK ENGLISH VERSION Bruksanvisning Directions for use IRB...

Page 2: ...svarig f r deras s kerhet Barn skall h llas under uppsikt f r att f rs kra att de inte leker med produkten Fl kten ska anv ndas f r transport av ren luft m a o den r ej avsedd f r transport av brand o...

Page 3: ...s efter 45 000 driftstim mar ca 5 rs kontinuerlig anv ndning f r bibeh l len fl ktfunktion Defekt kondensator kan orsaka skada EC MOTOR Varvtalsreglering av EC motor kan g ras med den inbyggda potenti...

Page 4: ...rts och dokumenterats Garantigivaren ansvarar enbart f r funktionen om godk nda tillbeh r anv nds Garantin omfattar inte fel p produkten som orsakats av tillbeh r utrustning av annat fabrikat S V E N...

Page 5: ...r ver Vid sjunkande temperatur Kontrollera 11 14 vakning f r att skydda den fr n skador stiger moduleringen propor kylning av sluten orsakade av alltf r h ga inre tempera tionellt igen regulatorn ture...

Page 6: ...ss lyckats D r det n dv ndigt att enkelt kunna terst lla eller st nga av str mmen 6 x Rel ej draget IGBT Fel EC enheten st ngs av anslutning Kortslutning mot jord eller kortslut nya f rs k till omstar...

Page 7: ...ektivet f r elektromagnetisk kompatibilitet EMC 2004 108 EG Harmoniserande standarder SS EN 61000 6 1 2007 Elektromagnetisk kompatibilitet EMC Generella fordringar Immunitet hos utrustning i bost der...

Page 8: ...sponsible for their safety Children should be supervised to ensure that they do not play with the appliance The fan is used for transportation of clean air mea ning not intended for fire dangerous sub...

Page 9: ...tion hours about 5 years of operation to secure maximum function Defective capacitor can cause damage EC MOTOR Speed regulating of EC motor can be done with the built in potentio meter 0 10 V An exte...

Page 10: ...off When cleaning and maintaining the fan always have to be secured when open so it can t fall down and cause injury The fan must be cleaned when needed at least once a year to maintain the capacity a...

Page 11: ...ls D1 24 V 10 V D1 24 V 10V bridged Digital In 1 not bridged 2 x Energized Active temperature monitoring terminals The device has an active temperature At sinking temperature the Check cooling 11 14 m...

Page 12: ...essary to have rotatable an enabling reset or to disconnect the power supply 6 x De energized IGBT Fault EC Controller switches off renewed terminals Shortcut earth or shortcut of motor attempt to sta...

Page 13: ...omagnetic Compatibility EMC 2004 108 EG Harmonised standards SS EN 61000 6 1 2007 Electromagnetic compatibility EMC Generic standards Immunity for residential commercial and light industrial environme...

Page 14: ...1270372 utg 1 AB C A STBERG Box 54 SE 774 22 Avesta Sweden Industrigatan 2 Avesta Tel 46 226 860 00 Fax 46 226 860 05 Email info ostberg com www ostberg com...

Reviews: