background image

16

5.2.3  Adjusting the feet

The product is equipped with three factory fitted 

feet (F), adjustable from 0-40 mm. Unscrew the 

feet a minimum of 15 mm from the bottom of the 

product. Then adjust the feet individually until the 

product is standing firmly and level vertically and 

horizontally.

5.3 Intermittent discharge from tundish

 

1.  Turn off the electrical supply to the immer-

sion heater.

2.  Turn off cold water supply valve.

3.  Open a hot tap.

4.  Turn the knob (K) on the Temperature and 

Pressure Relief Valve clockwise and hold in 

this position for 30 seconds (see below).

5.  Check pre-charge on vessel and  adjust 

pressure if necessary.

6.  Open cold water supply valve.

7.  When water flows through open tap, close 

tap. Turn on electrical supply to the immer-

sion heaters. 

5.4 Continous very hot water discharge from 

tundish

This indicates a malfunction of a thermal cut-out, 

operating thermostat or the combined tempera-

ture and pressure relief valve. Turn off the electri-

cal supply to the immersion heater and also iso-

late any indirect unit connected to the vessel or 

coil. Contact the installer or competent engineer.

5.5 Expansion vessel maintenance

The expansion vessels require annual mainte-

nance by a competent person and the precharge 

pressure must be restored to the original value. 

An annual visual inspection is recommended. 

Important: to check the precharge the expansion 

vessel must be completely empty of water. if the 

pressure is different from the value shown on the 

F

F

K

F

label it must be restored to the original value.

Do not remove expansion vessel without depres-

surising the cylinder and draining 10 litres of water 

from the drain valve at the base of the cylinder

5.6 Warranty

 

Cylinder should be serviced annually (as below) 

and logbook should be updated in order to vali-

date warranty. Logbook and service records act 

as warranty document. For terms of warranty see 

Service logbook at rear of manual.

5.7 Service procedure

 

The following maintenance work has to be carried 

out annually by a competent person:

1.  Inspection of pressure/temperature relief 

valve and expansion relief valve.

2.  Manually operate each valve by twisting the 

operating cap, and check if water flows un-

obstructed via the tundish to the discharge 

point.

3.  Ensure that both valves re-seat satisfactorily.

4.  Turn off mains water supply and open near-

est hot water tap to depressurise the DHW 

system.

5.  Check the expansion vessel.

6.  If the pressure is below 3 bar, top up with 

a suitable air pressure pump to pressure 

shown on vessel label. 

7.  Complete the service section of Benchmark/

Cylinder Commissioning Checklist included 

in the inside back pages of these instructions.

8.  Remove , clean and replace line strainer.

9.  The immersion heater element must be 

removed for inspection on service after 5 

years. The threads must be checked for cor-

rosion. If signs of corrosion are evident, the 

element must be replaced. Subsequently 

the element must be removed and exam-

ined every 3 years. Failure to do so in ar-

eas of aggressive water may result in the 

element separating from the cylinder with 

consequential escape of water.

10.  Visual inspection of all valves, external fit-

tings, immersion heaters and electrical con-

nections.

5.8 Discharge

 

Discharge pipes must be metal or suitably tem-

perature rated as defined by G3 building Regula-

tions. The pipe should have a continuous fall and 

should terminate in a safe and visible place. 

Downward discharges at low level, i.e. up to 100 

mm above external surfaces such as car parks, 

hard standings, grassed areas etc. are accept-

able providing that where children may play or 

Summary of Contents for 80800277

Page 1: ...146249 00 01 2022 Optima Geocoil OGC 300 l EN SAFETY INFORMATION O M INFORMATION INSTALLATION MANUAL TDS TECHNICAL DATA SHEET ...

Page 2: ... 5 Requirements for installation location 8 3 6 Pipe installation 8 3 7 Electrical installation 11 4 Commissioning 13 4 1 Commissioning and filling 13 4 2 Turning on the power 13 4 3 Temperature adjustment of tap water 13 4 4 Control points 13 4 5 Draining 13 4 6 System flushing 14 4 7 Handover to end user 14 5 User guide safety and servicing 15 5 1 Safety cut out 15 5 2 Settings 15 5 3 Intermitte...

Page 3: ... the safety valves must NOT be sealed or plugged Discharge must comply with current building regulations The electrical supply to the heater shall be done in accordance with current local regula tions and best practice by a qualified electrician The product is intended for permanent supply The mains power supply cable shall withstand 90 C A strain reliever must be fitted supplied The product shall...

Page 4: ...12897 2016 Safety standard EN 60335 2 21 Welding standard EN ISO 3834 2 The manufacturer is certified for Quality ISO 9001 Environment ISO 14001 Work environment ISO 45001 2 2 Intended use Optima OGC is designed to deliver hot water and hydronic heat from an electrical and or external energy source The OGC 300 can be used with a heat pump fitted with a three way valve The lower part of the cylinde...

Page 5: ...ylinder rated pressure MPa Bar 1 10 Maximum design pressure of lower cylinder rated pressure MPa Bar 0 20 2 5 Operating pressure of cylinder upper MPa Bar 3 Max operating temperature of cylinder C 70 Expansion vessel capacity L 18 Hydraulic connections Buffer connections Inch BSP female 1 Cold water Inch BSP female 3 4 Hot water Inch BSP female 3 4 Immersion heater Inch BSP female 1 1 4 Safety val...

Page 6: ... 2 1 8 5 2 1 9 10 4 4 3 6 7 3 2 1 G3 Inlet Group kit The product is supplied with a G3 Inlet Group kit The kit contains the components shown in table below and illustration right No Description Dim A Cold water supply ø22 mm B Balanced cold supply optional ø22 mm C Expansion vessel 1 2 D Multibloc valve 3 4 E Discharge pipework 15 22 mm F Drain cock not supplied N A G Cold water inlet 3 4 int H Tu...

Page 7: ...3 4 int thread Coil connection lower F 3 4 int thread Coil connection upper G 1 2 Safety valve lower cylinder H 3 4 int thread Cold water inlet upper cylinder I ø15 mm T P relief valve upper cylinder J ø6 ø8 mm Sensor slot K 3 4 int thread Hot water outlet L 3 4 int thread Anode A E B D C F I J K L J H G ø 30 45 15 3 4 1 Delivery The product should be transported carefully as shown with packaging ...

Page 8: ...e installation The product is designed to be permanently connected to the mains water supply Ap proved pipes of the correct size should be used for installation The relevant standards and regulations must be followed 3 6 1 Incoming water pressure The efficiency of the product depends on the incoming cold water pressure The water pressure should be min 2 bar and max 6 bar throughout the day Excessi...

Page 9: ...volume A Approved pipes of a suitable dimension can be fitted to coil connections 3 and 4 B Approved pipes of a suitable dimension can be fitted to buffer volume connections 5 Unused connections must be properly plugged Use a suitable thread sealant with all connec tions to avoid leaks HW outlet CW inlet Space heating High output heat source 3 6 4 Pipe fitting schematics Suggested pipe fitting lay...

Page 10: ...sel shall be filled first Discharge must comply with current building regulations 3 6 6 Temperature sensor installation The product is equipped with two temperature sensor brackets which allows installation of 6 or 8 mm temperature sensors To install the temperature sensor follow the instructions below 1 Remove temperature sensor bracket A from tank body by gripping it and pulling straight out 2 I...

Page 11: ...s connected to the terminal on the heating ele ment hexagonal brass D Internal wires from the element to the ther mostat are factory fitted and connected to point 4 on the safety thermostat and point 2 on the work thermostat See illustration right 3 7 1 Electrical components Component Note Safety cut out upper lower 85 C thermal cut out Safety thermostat upper box 40 70 C adjustable Work thermosta...

Page 12: ...stalled by an authorised electrician Components for disconnection must be included in the fixed electrical installation in accordance with applicable standards and regulations Mains cable should withstand 90 C continuously A strain reliever must be fitted supplied CAUTION The product shall have a clearance for servicing of 400 mm in front of the electric junction box covers 100 mm over the highest...

Page 13: ...ower can be switched on Turn on power switch circuit breaker 4 3 Temperature adjustment of tap water The outgoing hot water temperature from the product to the taps will be the same as the set temperature of the thermostat For tempera ture adjustment see section 5 1 1 Since the water temperature in the product can be up to 70 C it is strongly recommended to include a mixer valve in the system to a...

Page 14: ...ord Log Book at the back of this manual Hand this installation manual over to the end user that the water in the vessel can be very hot take necessary precautions After draining close drain cock Close all open taps The vessel must be filled with water before pow er is turned on see pt 4 1 4 6 System flushing System flushing will not be necessary under normal circumstances as the line strainer will...

Page 15: ... the temperature of the water inside the vessel Increasing the temperature will result in a higher available hot water volume The outgoing hot water temperature from the product to the taps will be the same as the set temperature of the thermostat For temperature adjustment see pt 5 2 Since the water temperature in the product can be up to 70 C it is strongly recommended to in clude a mixer valve ...

Page 16: ...ylinder should be serviced annually as below and logbook should be updated in order to vali date warranty Logbook and service records act as warranty document For terms of warranty see Service logbook at rear of manual 5 7 Service procedure The following maintenance work has to be carried out annually by a competent person 1 Inspection of pressure temperature relief valve and expansion relief valv...

Page 17: ...withstanding high temperature discharges of water and 3 m from any plastics guttering system that would collect such discharges tundish visible Where a single common discharge pipe serves more than one system it should be at least one pipe size larger than the largest individual dis charge pipe D2 to be connected For further information contact your Building Control Office Valve Outlet size Minimu...

Page 18: ... installer No hot water Power supply interrupted Verify that the fuse is on the plug is plugged in to the wall contact the earth breaker has not tripped Thermostat has cut out Press the RESET button on the safety thermostat see User guide Heating element is defective Replace heating element Contact auth installer Leak in hot water pipe Verify as follows a close the mixer valve b wait 2 3 hours c f...

Page 19: ... The pressure in the heating sys tem is too high Check the system pressure Normal operating pressure is 1 2 bar Contact auth Installer when needed The valve is defective Replace the valve Contact auth installer The heating circuit has to be refilled frequently Leak in the heating system Check all pipe couplings Turn off the power sup ply remove the lid on the junction box in the lower cylinder and...

Page 20: ...the European Drinking Water Directive EN 98 83 EC or latest version The water should not be aggressive i e the water chemistry shall comply with the following Chloride 250 mg L Electric Conductivity EC 25 C 750 uS cm Saturation Index LSI 80 C 1 0 0 8 pH level 6 0 9 5 The immersion heater has not been exposed to hardness levels exceeding 5 dH 180 ppm CaCO3 A water softener is recommended in such ca...

Page 21: ...ith the appropriate Building Regulations 3 Failure to install and commission this appliance to the manufacturer s instructions may invalidate the guarantee The above does not affect your statutory rights For full details on the HWA charter please visit http www hotwater org uk HEATING AND HOTWATER INFORMATION COUNCIL IT IS THE RESPONSIBILITY OF THE INSTALLER TO COMPLETE THIS LOG BOOK AND PASS IT O...

Page 22: ...EER IF DIFFERENT NAME DATE ADDRESS TEL No REGISTERED OPERATIVE ID CARD No IF APPLICABLE REGISTRATION DETAILS IT IS THE RESPONSIBILITY OF THE INSTALLER TO COMPLETE THIS LOGBOOK AND PASS IT ON TO THE CUSTOMER FAILURE TO DO SO MAY INVALIDATE THE CYLINDER GUARANTEE APPLIANCE TIME CONTROL DETAILS MANUFACTURER MODEL CAPACITY TYPE TIME CONTROL UNVENTED PROGRAMMER litres MANUFACTURE date TIME SWITCH or ...

Page 23: ...WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED NO YES NO bar HAS THE EXPANSION VESSEL OR INTERNAL AIR SPACE BEEN CHECKED YES NO WHAT IS THE HOT WATER TEMPERATURE AT THE NEAREST OUTLET C bar ALL PRODUCTS YES DOES THE HOT WATER SYSTEM COMPLY WITH THE APPROPRIATE BUILDING REGULATIONS HAS THE SYSTEM BEEN INSTALLED AND COMMISSIONED IN ACCORDANC...

Page 24: ...AME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 9 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 2 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 4 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 6 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 8 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 10 ...

Reviews: