Operating instructions PC-30-Vario filter control unit Page: 22
Frost protection temperature (air temperature)
Display text: Frost prot.
This line displays the temperature at which the frost protection function automatically
starts up. To adjust this value to suit the requirements of the particular swimming pool
installation, make sure it is displayed in the
top
line of the Service Terminal:
1.
After pressing the button on the terminal, the filter system is switched off and the
display shows:
Frost prot. °
Temperature of
the freeze
protection
0.0
2. You can now use the
and
buttons on the terminal to change the frost protection
temperature. The lowest value you can set is -3°C, the highest value is 5°C.
3. If you press the
button again, the standard diagnostics display reappears and the
filter system resumes operation. The set value is saved automatically.
The factory setting for the frost protection temperature is 0°C.
Frost protection temperature (water temperature)
Display text: water frost.:
This line displays the temperature to which the water is heated during frost protection
mode. To adjust this value to suit the requirements of the particular swimming pool
installation, make sure it is displayed in the
top
line of the Service Terminal:
1.
After pressing the button on the terminal, the filter system is switched off and the
display shows:
water frost.: °
Water temperature
with freze
protection
3.0
2. You can now use the
and
buttons on the terminal to change the frost protection
water temperature. The lowest value you can set is 1°C, the highest value is 5°C.
3. If you press the
button again, the standard diagnostics display reappears and the
filter system resumes operation. The set value is saved automatically.
The factory setting for the frost protection temperature is 3°C.
Switch off pump during backwashing
Display text: Valve pause:
This line displays the length of time that the filter pump is switched off, if at all, during
operation of the sliding valve. To adjust this value to suit the requirements of the particular
swimming pool installation, make sure it is displayed in the
top
line of the Service
Terminal:
1.
After pressing the button on the terminal, the filter system is switched off and the
display shows:
Valve pause
actuating time
hydraulic valves
10
2. You can now use the
and
buttons to change the period of time (in seconds) that
the pump is off. The smallest value you can set is 0, the largest value is 120.
3. If you press the
button again, the standard diagnostics display reappears and the
filter system resumes operation. The set value is saved automatically.
The factory setting for the off period is 0.