PC-250 Filter control unit operating manual   Page: 12 (24 

Dosing system connection 

PC-250

20 21

Dosiertechnik

(potentialfrei)

max. 230V / 8A

 

There  is  a  floating  relay  contact  between  terminals  20 
and  21.  This  can,  for  example,  be  used  for  activation  of 
the  dosing  system  (the  contact  remains  closed  during 
filter operation). 

This contact can be loaded with a maximum of 230 V/8A.

 

Temperature sensor connection 

Schwimmbad

Temperaturfühler

30 31

Fühler

Solar-

32 33

Filtersteuerung PC-250

 

 -Tauchhülse

 

The  swimming  pool  temperature  sensor  is  connected  to  terminals  30  and  31.  The 
temperature  sensor  is  supplied  with  a  cable  length  of  1.5  m  as  standard.  If  required,  this 
can  be  lengthened  to  maximum  20  m  (cross-section  minimum  0.5  mm²)  with  a  2-core 
cable.  You  should  avoid  routing  the  sensor  cable  near  power  cables  to  prevent  possible 
interference. 

Since  precise  temperature  control  can  only  be  achieved  with  good  heat  transfer  between 
temperature  sensor  and  swimming  pool  water,  an 

  immersed  sleeve  R  ½"  (Art.  No. 

3200200003) should be built into the piping system. The sensor polarity is as required. 

A  solar  temperature  sensor  (Art.  No.  3100000030)    can  be  additionally  connected  to 
terminals  32  and  33.  The  temperature  sensor  is  supplied  with  a  cable  length  of  20  m  as 
standard.  If  required,  this  can  be  lengthened  to  maximum  50  m  (cross-section  minimum 
0.5mm²) with a 2-core cable. You should avoid routing the sensor cable near power cables 
to prevent possible interference. The solar temperature sensor should be connected at the 
solar  collector  output  and  must  have  good  heat  contact  to  the  returning  water  flow.  The 
temperature at the temperature sensor installation site may not exceed 80 °C. 

Setting motor protection 

Please see the Info key information in menu command 10. 

Starting the backflushing process 

If  the  backflushing  key    is  pressed  for  3  seconds  without  interruption,  the  backflushing 
process  will  start.  Backflushing  will  not  start  unless  a  backflushing  duration  has  been 
entered.  

Submerged sleeve 

Summary of Contents for POOL-Control-250

Page 1: ...pecifications Dimensions 220mm x 220mm x 100mm Operational voltage 400V 50Hz Control system power consumption ca 10VA Switching capacity Pump max 3 0 kW AC3 Heater max 2A Dosing system max 8A Protecti...

Page 2: ...ng switching times 8 Start backflushing process manually 8 Info key 8 Installation 9 Electrical power supply 9 Mains connection when using 400V 3 phase pump 10 Mains connection when using 230 V AC pum...

Page 3: ...n on time 17 Heater priority circuit 18 Solar heater priority circuit 18 Frost protection 19 Pump time 19 heater time 19 Solar time 19 Motor defect 19 Phase fields 19 Int backflushing intern 19 Ext Ba...

Page 4: ...y This controller is not usable for other types of solar collector Terminals for electronic level regulation NR 12 TRS 2 Art No 3030075020 enable convenient automatic regulation of the swimming pool w...

Page 5: ...R ck sp len The filter pump is switched on because backflushing is taking place using the bar valve connected Klar sp len The filter pump is switched on because rinsing is taking place using the bar v...

Page 6: ...he control system this indicator lamp is used to show the current operating status of the solar heater Backflushing process indicator lamp This indicator lamp always illuminates if backflushing or rin...

Page 7: ...y shows 0 00 0 00 1 the minute display of the top time switch on time blinks Note if you press the key the current time will be taken over 3 You can now use the and keys to set the required switch on...

Page 8: ...et the minutes If you press the key the current time is taken over 4 Press the key again the hours in the switch on time blink You can now use the and keys to set the hours 5 Press the key again the s...

Page 9: ...display automatically Installation The controller must be protected against moisture in accordance with its protection class and the fixed to a plain fireproof support with suitable loading capacity...

Page 10: ...L1 N WSK schutz 230V max 8A Filterpumpe max B16A Vorsicherung FI Schalter Netz 1 N 230V 50Hz 25A 0 03A N kontakt The bridge fitted in the works between the terminals labelled WSK must be removed if a...

Page 11: ...N A 230 V bar valve for rinsing can be connected to terminals U4 and N Both valves will be controlled by the internal backflushing controller Heater and dosing systems are blocked during the backflus...

Page 12: ...h good heat transfer between temperature sensor and swimming pool water an immersed sleeve R Art No 3200200003 should be built into the piping system The sensor polarity is as required A solar tempera...

Page 13: ...e right Fuses The electronic control system is protected by a 0 25A fine wire fuse on the PCB in the inside of the device The short circuit protection for the filter pump must be provided by a backup...

Page 14: ...tched off temporarily by the EUROTRONIK 10 or the NR 12 TRS 2 level regulation system Backflushing The filter pump is switched on because backflushing is taking place using the bar valve Rinsing The f...

Page 15: ...defective Caution If both temperature sensors are at the same temperature the solar sensor must never display a higher value than the water temperature sensor otherwise the solar heater will not swit...

Page 16: ...e value is 0 the largest 15 3 If you press the key again the normal diagnosis display appears and the filter unit continues to operate The adjusted value will be saved automatically A temperature diff...

Page 17: ...d the filter unit is switched off and the display shows the following Min Solar s Minimale Einschaltzeit der Solarheizung 120 2 Use the and keys to change the minimum time in stages of 10s The smalles...

Page 18: ...3 If you press the key again the normal diagnosis display appears and the filter unit continues to operate The additional heater priority is switched off at the works Solar heater priority circuit Thi...

Page 19: ...ump time This line displays the total operating hours for the filter pump heater time This line displays the total operating hours for the additional heater Solar time This line displays the total ope...

Page 20: ...he filter pump operating status is displayed in the top line of the service terminal the pump can be switched on or off manually 1 Once the key has been pressed the filter unit is switched off and the...

Page 21: ...tinues to operate Dosing unit When the dosing unit operating status is displayed in the top line of the service terminal it can be switched on or off manually 1 Once the key has been pressed the filte...

Page 22: ...ormal diagnosis display appears and the filter unit continues to operate Diagnosis This menu is only accessible for trained osf service technicians Language When the language is shown in the top line...

Page 23: ...ungsschutz Filterpumpe Temperaturf hler Heizungspumpe W Netz 400V Dosiertechnik Dosier pumpe N Netz 230V 1 N PE Ausgang Pumpe Druckschalter Netz 230V 1 N PE Stellantrieb Ge ffnet bei R cksp len und Kl...

Page 24: ...PC 250 Filter control unit operating manual Page 24 24...

Reviews: