Installation and operating manual for Alarm-control.plus page
6 (10)
Setup and configuration
The configuration and setting of the Alarm-control.plus device can be done via the screen of the
PC-45 exclusiv, from the computer or smartphone.
Configuration from the PC-45 exclusiv
After the two controls have been connected, an additional
symbol appears in the main menu of the PC-45 exclusiv.
Clicking this button takes you to the configuration menu.
Alarm-control.plus menu
The screen shows the current status of the sensors
connected to the Alarm-control.plus.
Attention! The connected sensors are configured on the
Alarm-control.plus website
Set alarm limits
for air temperature and humidity
Alarm settings for water sensors
On this screen you can individually set the reaction of the
Alarm-control.plus-unit when a water sensor is triggered.
There are 5 ways to respond to a leak:
Audible alarm.
Potential-free contact of the alarm relay. The relay
closes for the duration of the leak.
230V relay for valve control. The relay closes for
the duration of the leak.
Stopping the PC-45 exclusive and all devices
contained in its network cluster.
Send alarm by email. The email address is set via the
Alarm-control.plus website.
□
Deactivating the response to the leakage sensor.
Alarm settings for climate sensor
On this screen you can set the reaction of the Alarm-
control.plus individually for each parameter that exceeds
the set limit values. There are three ways to react to an
alarming event:
Audible alarm.
Potential-free contact of the alarm relay.
Send alarm by email.
□
Disabling the response to the event.