Installation and Operating Instructions PC-230-smart Page
4 (10)
Electrical connection
The control unit must be mounted such that it is protected from moisture in accordance with its
degree of protection. The ambient temperature must lie between 0°C and + 40°C and should
vary as little as possible. The relative humidity at the installation position must not exceed 95%
and there must not be any condensation. Avoid exposing the unit to direct heat or sunlight.
The power supply for the unit must be provided via an all-pole disconnection switch
with a minimum contact gap of 3mm and via a residual-current circuit breaker with a
fault current I
FN
≤ 30mA.
Always disconnect the unit from the power supply before opening the case. All
electrical wiring and calibration and servicing work must be performed solely by
an approved electrician. The attached wiring diagrams and all applicable safety
regulations must be observed.
Extra Low Voltage lines
Low-voltage lines must not be laid along with three-phase or AC power cables in the same
cable conduit. In general, always avoid routing low-voltage lines close to three-phase or AC
power cables.
Wiring diagram
This control is not suitable for connecting a filter pump with speed control. We have other
controls in our range for this type of pump.
The factory-inserted link between the two terminals labelled
Th
must be removed when
connecting a safety thermal cutout. If no device is connected, then this link must remain
screwed in place.
The factory-inserted link between terminals
13
and
14
must be removed when connecting an
NR-12-TRS-2 water level controller. If there is no water level controller connected, the link
between these terminals must remain screwed in place. In this case, terminals
11
and
12
remain unused.
The factory-inserted link between terminals
3
and
5
must be removed when connecting a
EUROTRONIK-10. If there is no EUROTRONIK-10 connected, the link between these terminals
must remain screwed in place. In this case, terminals
2
and
4
remain unused.
Opening one of the contacts between terminals
13
and
14
or
3
and 5 immediately switches off
the filtration pump, dosing equipment and heating
Closing the contact between terminals
2
and
4
automatically switches on the filtration pump,
while heating and dosing equipment are switched off.
Closing the contact between terminals
11
and 12 automatically activates the filtration pump, the
temperature regulation and the dosing equipment.
On the terminals 21 and 22 there is a floating contact for dosing systems. The contact is closed,
if the PC-230-smart is in filtration.