ROMANCE 28 STOVE
4
Burner
Natural Gas
Propane LP
Maximum Input, BTU/h (kW)
minimum :
maximum
:
19 000
(5,6)
28
500
(8,4)
20
000
(5,9)
26
000
(7,6)
Inlet Pressure Inch WC (kPa)
minimum :
maximum
:
5,0
(1,3)
7,0
(1,8)
11,0
(2,8)
14,0
(3,5)
Manifold Pressure Inch WC (kPa)
minimum :
maximum
:
1,6
(0,4)
3,5
(0,9)
6,3
(1,7)
10,0
(2,5)
Burner orifice,
∅
:
#36
DMS
#52
DMS
Gas Valve
Natural Gas
Propane LP
S.I.T. Controls USA
Model SIT 0.820.634 Nova mV
Model SIT 0.820.633 Nova mV
Honeywell VS8420E8001B
VS8420E8001B
Y
OUR STOVE IS EQUIPPED WITH A SOPHISTICATED GAS CONTROL VALVE FOR A SAFE USE
. T
HE GAS CONTROL VALVE
OPERATES WITHOUT ELECTRICITY DUE TO THE ENERGY GIVEN BY THE PILOT FLAME AND CAPTURED BY THE THERMO
-
GENERATOR
. (
ALSO CALLED THERMOPILE
). T
HE ADMISSION OF THE GAS FUEL TO THE BURNER IS DONE ONLY UNDER
SAFE CONDITIONS
.
Pressure Adjustments
For USA, above 2000 ft (610 m), see gas codes to adjust the valve operating pressure.
•
Adjustments to the valve assembly must be performed by a qualified service person.
•
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of ½ psi (3.5 kPa);
•
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less that ½
psi (3.5 kPa);
NATURAL GAS
The inlet supply or line pressure must be a minimum of 5" WC and a maximum of 7" WC. The orifice has a
#36 DMS hole.
ELEVATION
INPUT RATING
0-4500 ft (0-1400m)
28 500 BTU/h
(8.4 kW)
over 4500 ft (1400 m)
28 500 BTU/h
(8.4 kW) less 4% per 1000 ft (300 m)
or reduce manifold pressure by 0.25 INWC per 1000 ft (300 m)
PROPANE GAS
The inlet supply or line pressure must be a minimum of 11” WC and a maximum of 14” WC. The orifice has
a #52 DMS hole.
ELEVATION
INPUT RATING
0-2000 ft (0-610 m)
26 000 BTU/h
(7.6 kW) Manifold pressure 10 " WC
2000-4500 ft (0-1400 m)
24 200 BTU/h
(7.0 kW) Manifold pressure 8.5 " WC
over 4500 ft (1400 m)
24 200 BTU/h
(7.6 kW) less 4% per 1000 ft (300 m)
or reduce manifold pressure by 1" WC per 1000 ft
NOTE : The input rating should always be checked when running this appliance for the first time. To do this,
verify inlet valve pressure and manifold pressure. Adjust manifold pressure to meet the value range as
indicated in the burner characteristics table.
Available Options
Blower Kit AC02050
•
Ultra quiet crossflow blower;
•
Variable speed control.
Thermo Switch Kit AC05530
•
Thermo switch starting the blower at 110
O
F (43
O
C) and stopping it at 90
O
F (32
O
C)
Thermostat Kit
AC05558