Table 4 : Floor Protection
FLOOR PROTECTION
Canada
USA
B
14
18" (457 mm)
16" (406 mm)
M
8" (203 mm)
N/A
N
N/A
8" (203 mm)
N
M
B
DOOR
Figure 14: Floor Protection
To determine the need to add floor protection
(D)
beyond the hearth extension
(A)
, the following
calculation must be done using the data in
«Table 5 : Data for Floor Protection Calculation»
of
this section: D = B - G, where G = A-C.
HEARTH SLAB:
NON-COMBUSTIBLE MATERIAL
FLOOR PROTECTOR:
NON-COMBUSTIBLE MATERIAL
B
C
D
E
F
A
G
HEARTH SLAB:
NON-COMBUSTIBLE MATERIAL
FLOOR PROTECTOR:
NON-COMBUSTIBLE MATERIAL
B
C
D
E
F
A
G
Figure 15: Additional Floor Protection - Raised Installation
Figure 16: Additional Floor Protection - Not Raised Installation
Table 5 : Data for Floor Protection Calculation
A
B
C
D
E
Air Jacket
Maximum
Extended
Dimension
of the hearth
extension
See raised
installation
2" (51 mm)
4" (102 mm)
G = (A-C)
D=B-G
10" (254 mm)
12" (305 mm)
2" or 4"
back from
fireplace
facing
If the value
(D)
is negative or zero, additional floor protection in front of the unit is not needed
because the masonry fireplace hearth extension is long enough. If the value
(D)
is positive, an
additional floor protection in front of the hearth extension at least equivalent to the result
(D)
must be added.
14
From door opening. The depth of the hearth extension in front of the insert is included in the calculation of the floor protector’s dimensions.
Summary of Contents for MATRIX 2700 INSERT
Page 2: ......
Page 6: ...Page 6 Installation and Operation Manual Matrix 2700 Insert ENGLISH CERTIFICATION PLATE ...
Page 50: ...Page 50 Installation and Operation Manual Matrix 2700 Insert ENGLISH 5 Remove the blower ...
Page 57: ...Page 57 Installation and Operation Manual Matrix 2700 Insert ENGLISH NOTES ...
Page 58: ...NOTES ...
Page 59: ......