OSAKA OPERATING INSTRUCTIONS –COC 30- Page
9
10
HS2
Regulator differential 2
(FLOOR)
1 ÷ 999
2
“
]
CL” Group
(clock parameters)
Par.
Description
Range
Def.
11
ct
Cooking time
0.01÷ 23.59
hrs. - min.
1.00
12
On
Automatic switch on time
0.00÷ 23.59
hrs. - min.
0.00
13
bt
Buzzer activation time
1 ÷ 999 seg.
30
14
cEF
Automatic switch off at
end of cooking
On – OFF
OFF
“
]
In” Group
(measurement inputs parameters)
Par.
Description
Range
Def.
15
EFP
(com)
Floor probe presence
(FLOOR)
On – OFF
On
16
ESP
(com)
OFF Steamer probe
presence (STEAM
On – OFF
On
17
EAP
(com)
Auxiliary probe presence
(AUX)
On – OFF
On
18
OSt
(com)
Top probe calibration
(TOP)
-99 ÷ 999
0
19
OSF
(com)
Floor probe calibration
(FLOOR)
-99 ÷ 999
0
20
OSS
(com)
Steam Probe calibration
(STEAM)
)
-99 ÷ 999
0
21
OSA
(com)
Auxiliary probe
calibration (AUX)
-99 ÷ 999
0
22
Uni
(com)
Unit of measurement
°C / °F
°C
23
SEn
(com)
Type of probe in input
J / CrA
J
24
i1F
(com)
Function digital input 1
0-1-2-3-4-5
0
25
i1L
(com)
Logic function digital
input 1
On – OFF
On
26
i1d
(com)
Delay digital input 1
0 ÷ 999 seg.
0
27
i2F
(com)
Function digital input 2
0-1-2-3-4-5
0
28
i2L
(com)
Logic function digital
input 2
On – OFF
On
29
i2d
(com)
Delay digital input 2
0 ÷ 999 seg.
0
30
i3F
(com)
Function digital input 3
0-1-2-3-4-5
0
31
i3L
(com)
Logic function digital
input 3
On - OFF
On
32
i3d
(com)
Delay digital input 3
0 ÷ 999 seg.
0
Group “ ] AL”
(alarm parameters)
Par.
Description
Range
Def.
33
A1t
(com)
Alarm type AL1
Ab / dE
Ab
34
A1L
(com)
Lower threshold alarm
-99 ÷ 999
-99
35
A1H
(com)
Upper threshold alarm
-99 ÷ 999
999
36
HA1
(com)
Hysteresis alarm 1
1 ÷ 999
1
37
A1d
(com)
Delay activation of alarm
1
0 ÷ 999
seg.
0
38
A2t
(com)
Alarm type AL2
Ab / dE
Ab
39
A2L
(com)
Lower threshold alarm 2
-99 ÷ 999
-99
40
A2H
(com)
Upper threshold alarm 2
-99 ÷ 999
999
41
HA2
(com)
Hysteresis alarm 2
1 ÷ 999
1
42
A2d
(com)
Delay activation of alarm
2
0 ÷ 999
sec.
0
43
Pod
(com)
Disabling alarms on
switching on
0 ÷ 999
min.
0
“
]
St” Group
(steam control parameters)
Par.
Description
Range
Def.
44
SPS
Steamer regulator Set
Point
-99 ÷ 999
130
45
HSS
(com)
Steamer regulador
hysteresis
1 ÷ 999
2
46
SEt
(com)
Steam injection block
temperature
-99 ÷ 999
110
47
SIF
(com)
Permanent steam
injection command
function
On - OFF
OFF
48
SIt
Steam injection duration
1 ÷ 999
sec.
10
49
Sid
(com)
Time of block of steam
injection between two
subsequent steam
injections.
1 ÷ 999
seg.
30
50
SIi
Interval between
automatic steam
injections
0 ÷ 999
min.
0
51
SIc
Duration of automatic
steam injection cycles
0 ÷ 999
min.
0
]
ES” Group
(extractor control parameters)
Par.
Description
Range
Def.
52
ESd
Disabling of extractor
during steam injection
On - OFF
OFF
53
Edt
Extractor disabling time
after end of steam
injection
1 ÷ 999
seg.
1
54
EAS
Automatic switching on of
extractor at the end of
cooking
On - OFF
OFF
55
Ecn
(com)
Function of the
monostable extractor
output command
On - OFF
OFF
“
]
AO” Group
(AUX output parameters)
Par.
Description
Range
Def.
56
AOF
(com)
AUX output function
0-1-2-3-4-5-6
0
57
AOt
AUX output time
0 ÷ 999
min.
0
58
Auxiliary regulator Set
Point
-99 ÷ 999
0
59
HSA
(com)
Auxiliary regulator
differential
1 ÷ 999
2
60
ArF
(com)
Auxiliary regulator
function mode
H - C
H
“
]
SE” Group
(serial communication parameters)
Par.
Description
Range
Def.
61
Add
(com)
Address of the station for
serial communication
1 … 255
1
62
bau
(com)
Serial port baud rate
bau
1-2-3-4-5
3
63
PAC
(com)
Programming access
through serial port rs485
LoC / Lor
Lor