Zone Wiring
Power down the alarm controller and complete all zone
wiring. Zones can be wired to supervise normally open de-
vices (e. g., smoke detectors) or normally closed devices
(e.g., door contacts). The Control Panel can be programmed
as normally open or for SEOL/DEOL.
Observe the following guidelines when wiring zones:
•
SEOL/DEOL installations recommended.
•
Minimum 22 AWG wire, maximum 18 AWG.
•
Do not use shielded wire.
•
Do not exceed 100Ω wire resistance. Refer to the
chart below:
Table 5: Burglary Zone Wiring Chart
Wire Gauge Maximum Length to EOL Resistor (meters)
22
910
20
1490
19
1880
18
2370
Figures are based on maximum wiring resistance of 100Ω
12F Power Wiring
This terminal provide 11.3-12.5V
DC
/350mA of current
(shared with PM outputs).
Connect the positive side of any device to the 12F termi-
nal, the negative side to GND.
The 12F output is protected; if too much current is drawn
from these terminals (wiring short) the output is temporar-
ily shut off until the problem is corrected.
PM Wiring
PMs switch to ground when activated
from the Control Panel. Connect the
positive side of the device to the 12F
terminal and the negative side to a PM
terminal.
PM output sink up to 200mA current.
A relay is required for current levels
greater than 50mA or 300mA. PM can
also be used for 2-wire smoke detec-
tors.
Single End-of-Line (SEOL) Resistor
When SEOL resistors are installed at the end of a zone
loop, the Control Panel detects if the circuit is secure, open,
or shorted.
Double End of Line (DEOL) Resistors for Fire Detectors
When double end-of—line (DEOL) resistors are installed
at the end of a zone loop, the second resistor enables the
panel to determine if the zone is in alarm, tampered or
faulted.
Note:
* – The additional resistor value should be
820 Ohm to recognize the second detector in the loop.
Bell Wiring
These terminals supply 150mA
of current at 10.4-12.5V
DC
for in-
stallations.
Note:
Steady and pulsed alarms
are also supported.
The BEL output is supervised
and power limited by 450mA PTC.
Connecting AC Power
Primary: 100-240VAC/50-60Hz/0.25A
Secondary: 15VDC/0.67A
The Control Panel have built-in AC/DC power source.
The 3-wired 22AWG cable should be used.
Ground Wiring
Using an insulated green
wire (minimum 22AWG),
connect the power cable to
Control Panel’s PCB via hole
marked as “PEg.
NOTE:
Wire and installa-
tion hardware not included.
Battery
A sealed, rechargeable, lead acid or gel type 12V 2.3Ah
battery is required for power standby.
Lun-25. Installer Guide
Revision
6