MMI touch screens are calibrated before leaving the factory. Adjustment should not required.
If for some reason the touch screen needs recalibration. Use the following procedure.

Touchscreen calibration mode is entered by setting dip switches and resetting or cycling power to the unit.

1.

 Set dipswitch 1 in the UP (ON) position. Leave all other switches in the DOWN (OFF)

position.

2.

 Cycle power to the HMI or press the reset button located near the dipswitches. The MMI8000 powers up to the

Touch screen calibration mode.

3.

 Follow the instructions on the screen. Briefly touch the center of the cross hairs “+” as they appear in all 5

positions (4 corners and center). When all five “+” are done the “+” disappears. The touch information is
processed and calibration is completed.

4.

 After calibration, the Password Reset dialog appears. If you wish to reset the password, you may do so at this

time. Otherwise select "NO" to continue on to the Boot-up process. If no action is taken, after a short time, the unit
automatically moves on to the Boot-up process.

When “YES” is chosen, another pop-up dialog appears as below.

Users must confirmed the reset again by inputting “YES”.
Click OK. (The default password 111111 is restored. However, other passwords, including download and upload
password, must be reset.)

Note: 

When the reset action is taken, saved projects and data in the HMI are all cleared.

5.

 Be sure to put Dipswitch 1 in the DOWN (OFF) position when done. Otherwise, the unit always goes to the

Touchscreen calibration mode on power up.

2.4 CE Requirements

EU directives that apply to the MT-8000 Series:

 

EMC Directive (89/336/EEC, 92/31/EEC, 93/68/EEC) electromagnetic emissions and immunity

 

Machinery Directive (89/392/EEC, 91/368/EEC, 93/44/EEC, 93/ 68/EEC) machine safety

 

MMI8000 products are CE-marked to indicate compliance with the EMC Directive.

The MMI8000 Series has been designed to operate satisfactorily in electromagnetic noise (immunity) and without
emitting high levels of electrical noise into the environment (emission). The units are designed to meet European
Community standards when installed per the wiring instructions in this manual.

Compatibility
Standards

The MMI8000 has been designed to meet electromagnetic compatibility for industrial
environments.

 

CISPR (EN 55011) Group 1, Class A Radiated Emissions levels

 

EN50081-2 Generic emission standard, industrial environment (Also US FCC Class A)

 

EN50082-2 Generic immunity standard, industrial environment

Summary of Contents for MMI8056

Page 1: ...s has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Prop...

Page 2: ...humidity are present This causes condensation of water in the device Do not install these terminals in environments where inflammable gases are present 2 2 Power Connections Make sure that all local...

Page 3: ...from any other branch 2 2 3 CE Requirements To make an MMI8000 comply with EMC directives and to reduce susceptibility to electrical interference a separate 14 AWG ground wire should be taken to the...

Page 4: ...permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you look at the back of the case are the ports for connecting to a PLC o...

Page 5: ...a Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground Signal Ground Signal Ground Signal Ground 6 Data Data 7 TxD Transmit 8 RxD Receive 9 Data Data 2 3 3 USB Host port Supports various devices with USB interface...

Page 6: ...ctManager or EasyBuilder8000 to change modes ON OFF OFF OFF Force to Touch Adjust mode Used for touchscreen calibration Reset project memory and settings to default OFF OFF ON OFF Force to Boot ROM Lo...

Page 7: ...e reset again by inputting YES Click OK The default password 111111 is restored However other passwords including download and upload password must be reset Note When the reset action is taken saved p...

Page 8: ...re IP65 front panel O ring seal Operating Temperature 0 45 C Operation humidity 10 90 RH non condensing Enclosure Plastic Dimensions WxHxD 323 x 243 x 51mm 286x212x50mm 240x179x50mm 204x150x48mm Panel...

Page 9: ...9 Dimensions Drawings are not to scale and are for visual purposes only MMI8121 MMI8100 8104 MMI8080...

Page 10: ...10 MMI8056 MMI8070 Kessler Ellis Products 10 Industrial Way East Eatontown NJ 07724 Phone 732 935 1320 Fax 732 935 9344 www kep com 9900132REV07FEB11...

Reviews: