2.1.2 Making a NEMA-4 Mounting

Panel Details

The unit can be mounted into panels with a depth of 4”(105mm). It is recommended that the unit be mounted on
the front panel of a steel enclosure, through an appropriate opening*.

 

Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware.

 

Allow clearance for cable connections to the back of the unit.

 

Unit depth may vary according to cable type used. Typically, plan a depth to accommodate at least

4”(105mm) behind the panel.

NEMA-4 Mounting

Put the unit through the panel cut out. Slide the clamps into the 6 holes provided around the case. Tighten the
clamping screws in an even pattern until the unit is secured in the panel.

Caution!

Do not over tighten mounting clamps!

Note: Specifications 

To seal to NEMA-4 specifications, all supplied mounting clamps must be used and panel

cannot flex more than 0.010”.

2.1.3 Environmental Considerations

The MMI8000 Series units are designed for indoors use as built in displays. Make sure that the displays
are installed correctly and that the operating limits are followed (See Specifications).

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, vapors

or dusts.

 

The unit should not be installed where fast temperature variations and/or high humidity are

present. This causes condensation of water in the device.

 

Do not install these terminals in environments where inflammable gases are present.

2.2 Power Connections

Make sure that all local and national electrical standards are met when the installing the unit.
Contact your local authorities to determine which codes apply.

2.2.1 Power Requirements

Power

MMI8000 units are powered by DC power only. The specified voltage range is 24±5% Volts DC.
This insures compatibility with most controller DC systems.
The power conditioning circuitry inside the unit is accomplished by a switching power supply.
The peak starting current can be as high as 700mA.

Fusing
Requirements

If the display does not come on within 2 seconds of power up, remove power. An internal fuse
prevents damage if the polarity of the DC power is incorrect. Check wiring to insure proper
connections and try to power up again.

High Voltage
Caution

An Internal fuse prevents damage for over voltage condition however it isn’t guaranteed.

DC voltage sources should provide proper isolation from main AC power and similar hazards.

Caution
Emergency
Stop

A Hard-wired EMERGENCY STOP should be fitted in any system using an MMI8000 to comply
with ICS Safety Recommendations.

Caution
Supply Voltage

Do not power the MMI8000 and inductive DC loads, or input circuitry to the controller, with the
same power supply.

Note: The 24 VDC output from 

 

some controllers may not have enough current to power the

MMI8000.

Summary of Contents for MMI8056

Page 1: ...s has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Prop...

Page 2: ...humidity are present This causes condensation of water in the device Do not install these terminals in environments where inflammable gases are present 2 2 Power Connections Make sure that all local...

Page 3: ...from any other branch 2 2 3 CE Requirements To make an MMI8000 comply with EMC directives and to reduce susceptibility to electrical interference a separate 14 AWG ground wire should be taken to the...

Page 4: ...permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you look at the back of the case are the ports for connecting to a PLC o...

Page 5: ...a Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground Signal Ground Signal Ground Signal Ground 6 Data Data 7 TxD Transmit 8 RxD Receive 9 Data Data 2 3 3 USB Host port Supports various devices with USB interface...

Page 6: ...ctManager or EasyBuilder8000 to change modes ON OFF OFF OFF Force to Touch Adjust mode Used for touchscreen calibration Reset project memory and settings to default OFF OFF ON OFF Force to Boot ROM Lo...

Page 7: ...e reset again by inputting YES Click OK The default password 111111 is restored However other passwords including download and upload password must be reset Note When the reset action is taken saved p...

Page 8: ...re IP65 front panel O ring seal Operating Temperature 0 45 C Operation humidity 10 90 RH non condensing Enclosure Plastic Dimensions WxHxD 323 x 243 x 51mm 286x212x50mm 240x179x50mm 204x150x48mm Panel...

Page 9: ...9 Dimensions Drawings are not to scale and are for visual purposes only MMI8121 MMI8100 8104 MMI8080...