Caution Wire
Routing

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 1000’ (300 m)
unshielded).

Wires should be run in pairs with a neutral or common paired with a hot or
signal line.
If wiring is to be exposed to lightning or surges, use appropriate surge
suppression devices.
Keep AC, high energy, and rapidly switching DC wiring separate from
signal wires.
Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground. This
provides a path for static and high frequency dissipation. Typical values to use are 1MOhm and
4700pF.

Connection

 

To make a connection, strip about 3/8” of insulation off the end of the wire, turn the connector

screw counterclockwise until the gap is wide open, insert the wire all the way in, and turn the
screw clockwise until it’s tight.

Connect positive DC line to the ‘+24V’ terminal and the DC ground to the
‘0V‘ terminal.

2.2.2 Grounding Requirements

Chassis ground must be used. DC ground is not directly coupled to Earth ground internally. It is
preferable not to ground DC negative return to chassis ground as poor site earths can introduce
noise into a system, but if necessary an earth connection should be made, from the power supply
return point to the central star earth point. Ground conductors should be as short and as large in
size as possible. The conductors must always be large enough to carry the maximum short circuit
current of the path being considered. Ground conductors should be connected to a tree from a
central star earth ground point. This ensures that no ground conductor carries current from any
other branch.

2.2.3 CE Requirements

To make an MMI8000 comply with EMC directives, and to reduce susceptibility to electrical
interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the
power connector. This ground connection should be run directly to the central star earth connection
point (as recommended in most Installation Instructions).

2.2.4 Safety Guidelines

This section presents recommended installation practices, and procedures. Since no two
applications are identical, these recommendations should be considered as guidelines.

Hardware
Considerations

WARNING!

The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface, such as
an MMI8000, can lead to equipment start-up, which could result in property damage and/or
physical injury to the equipment operator.

If you, or your company, use any programmable control systems that require an operator or
attendant, you should be aware that this potential safety hazard exists and take appropriate
precautions. Although the specific design steps depend on your particular application, the
following precautions generally apply to installation of solid-state programmable control devices.
In addition, these precautions conform to the guidelines for installation of Controllers as
recommended in the NEMA ICS 3-304 Control Standards.

Programming
Considerations

To conform with ICS Safety Recommendations, checks should be placed in the controller to
ensure that all writable registers that control critical parts of plant or machinery have limit checks
built into the program, with an out-of-limit safe shut down procedure to ensure safety of
personnel.

Summary of Contents for MMI8056

Page 1: ...s has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Prop...

Page 2: ...humidity are present This causes condensation of water in the device Do not install these terminals in environments where inflammable gases are present 2 2 Power Connections Make sure that all local...

Page 3: ...from any other branch 2 2 3 CE Requirements To make an MMI8000 comply with EMC directives and to reduce susceptibility to electrical interference a separate 14 AWG ground wire should be taken to the...

Page 4: ...permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you look at the back of the case are the ports for connecting to a PLC o...

Page 5: ...a Rx 3 Tx Tx 4 Tx Tx 5 GND Signal Ground Signal Ground Signal Ground Signal Ground 6 Data Data 7 TxD Transmit 8 RxD Receive 9 Data Data 2 3 3 USB Host port Supports various devices with USB interface...

Page 6: ...ctManager or EasyBuilder8000 to change modes ON OFF OFF OFF Force to Touch Adjust mode Used for touchscreen calibration Reset project memory and settings to default OFF OFF ON OFF Force to Boot ROM Lo...

Page 7: ...e reset again by inputting YES Click OK The default password 111111 is restored However other passwords including download and upload password must be reset Note When the reset action is taken saved p...

Page 8: ...re IP65 front panel O ring seal Operating Temperature 0 45 C Operation humidity 10 90 RH non condensing Enclosure Plastic Dimensions WxHxD 323 x 243 x 51mm 286x212x50mm 240x179x50mm 204x150x48mm Panel...

Page 9: ...9 Dimensions Drawings are not to scale and are for visual purposes only MMI8121 MMI8100 8104 MMI8080...

Page 10: ...10 MMI8056 MMI8070 Kessler Ellis Products 10 Industrial Way East Eatontown NJ 07724 Phone 732 935 1320 Fax 732 935 9344 www kep com 9900132REV07FEB11...