11
Step 6: External battery connection
Connect one end of external battery cable to UPS unit and the other end to battery box. Use
the chart below for detailed connection.
CAUTION:
Connection to External Battery shall be installed by SERVICE PERSONNEL only.
ATTENTION:
La connexion à la batterie externe doit être installée uniquement par le
PERSONNEL DE SERVICE.
NOTE:
If connecting more one external battery box, it’s requested to connect load at 80% of
UPS capacity.
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note
: The battery charges fully during the first five hours of normal operation. Do not expect
full battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. Please follow steps below to download and install monitoring software:
1. Go to the website:
https://www.orionpowersystems.com/software-downloads.html
2. Click ViewPower software icon and then choose your required OS to download the
software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
2-5 Battery Replacement
NOTICE:
This UPS is equipped with internal batteries and only service person can replace
the batteries.
AVIS:
Cet onduleur est équipé de batteries internes et seul un technicien peut remplacer les
batteries.
CAUTION!!
Consider all warnings, cautions, and notes before replacing batteries.
Note:
Upon battery disconnection, equipment is not protected from power outages.
UPS
Battery Box
Battery Box
It’
s in closed status for UPS
normal operation as default.
To activate EPO
function, remove
these two screws.