4
•
•
Unauthorized reproduction or copying of all or part of this manual is
prohibited.
•
•
Oriental Motor shall not be liable whatsoever for any problems relating
to industrial property rights arising from use of any information, circuit,
equipment or device provided or referenced in this manual.
•
•
Characteristics, specifications and dimensions are subject to change without
notice.
•
•
is a registered trademark or trademark of Oriental Motor
Co.,Ltd., in Japan and other countries.
© Copyright ORIENTAL MOTOR CO., LTD. 2014
Technical Support Tel:(800)468-3982
8:30
A.M.
to 5:00
P.M.
, P.S.T. (M-F)
7:30
A.M.
to 5:00
P.M.
, C.S.T. (M-F)
www.orientalmotor.com
Schiessstraße 74, 40549 Düsseldorf, Germany
Technical Support Tel:00 800/22 55 66 22
www.orientalmotor.de
Tel:01256-347090
www.oriental-motor.co.uk
Tel:01 47 86 97 50
www.orientalmotor.fr
Tel:02-93906346
www.orientalmotor.it
Tel:+55-11-3266-6018
www.orientalmotor.com.br
• Please contact your nearest Oriental Motor office for further information.
4-8-1Higashiueno,Taito-ku,Tokyo 110-8536
Japan
Tel:03-6744-0361
www.orientalmotor.co.jp
Tel:0800-060708
www.orientalmotor.com.tw
Singapore
Tel:1800-8420280
www.orientalmotor.com.sg
Tel:1800-806161
www.orientalmotor.com.my
Korea
Tel:080-777-2042
www.inaom.co.kr
Tel:1800-888-881
www.orientalmotor.co.th
Tel:400-820-6516
www.orientalmotor.com.cn
Tel:+91-80-41125586
www.orientalmotor.co.in
Hong Kong Branch
Tel:+852-2427-9800
Burnout protection for overload/locked-rotor state
Note
In order to prevent the motor from burning out for when the
output shaft is locked or in the case of an overload state, use an
electromagnetic switch.
When connecting to an inverter, use the electronic thermal relay
function of the inverter.
When connecting to the power supply
•
•
Always connect an electromagnetic switch.
Connect the electromagnetic switch according to the operating manual of the
electromagnetic switch.
•
•
Set the motor rated current for the thermal relay.
The motor rated current is described on the motor nameplate.
•
•
For electromagnetic switches, use the products as shown in the chart, or an
equivalent.
[ Fuji Electric FA Components & Systems Co., Ltd. ]
•
•
For motor output power 60 W Model: SC11AAN-
10TF
•
•
For motor output power 100 W Model: SC11AAN-
10TH
(
: Coil code)
Coil code
50 Hz
60 Hz
2
200 V
200-220 V
M
200-220 V
220-240 V
P
220-240 V
240-260 V
Use the product which satisfies the motor rated voltage by selecting the coil
code.
[ Mitsubishi Electric Corporation ]
•
•
For motor output power 60 W
Model: MSO-T10 0.35A 200V AC200V
•
•
For motor output power 100 W Model: MSO-T10 0.5A 200V AC200V
When connecting to the inverter
Be sure to set the electronic thermal relay according to the operating manual of
the inverter. Unless the electronic thermal relay is set, a burnout may result.
When using the motor with an inverter
When the motor is used with connecting an inverter, perform the following
settings to the inverter.
When driving the inverter, use it at the setting frequency 120 Hz or lower.
Setting for motor
Electronic thermal relay function
Set the rated current listed on the motor
nameplate based on the base frequency
and the voltage applied to the motor.
Applicable motor setting
Constant-torque motor or inverter motor
Motor capacity
Motor rated output power
If the setting value in the inverter does not
exist, set the closest value.
Number of motor poles
4 poles
Notes about when using the motor with an inverter
The inverter which input voltage exceeds 240 VAC cannot be used.
The insulation of the motor winding may deteriorate, causing damage to the
motor.
Time rating
Continuous operation is possible (continuous rating).
Troubleshooting
When the motor cannot be operated correctly, refer to the contents provided in
this section and take appropriate action. If the problem persists, contact your
nearest office.
Phenomena
Check items
Motor does not rotate.
Motor sometimes
rotates and stops.
•
•
Check the power supply voltage.
•
•
Connect the power supply and the motor correctly.
•
•
If terminal blocks or crimp terminals are used, check
them for poor connection.
•
•
Keep the load at or below the allowable value.
The motor rotates in
the direction opposite
to the specified
direction.
•
•
The connection varies depending on the gear ratio of
the gearhead.
•
•
The rotation direction is as viewed from the output
shaft end. Check the reference direction.
Motor temperature
abnormally high.
[Motor case
temperature exceeds
90 °C (194 °F)]
•
•
Check the power supply voltage.
•
•
Review the ventilation condition.
Noisy operation.
Check whether the combination of the motor and
gearhead is correct. (Refer to p.1 for the combinations)
Standard and CE Marking
•
•
This product is recognized by UL under the UL and CSA standards.
Also, it conforms to the China Compulsory Certification System (CCC System).
The motor model name is the recognized product name.
•
•
The motor is affixed the CE Marking under the Low Voltage Directive.
UL Standards
*
, CSA Standards
*
, CCC System
*
Applications standards
Certification Body / File No.
UL 1004-1
UL /
UL File No.E62327
CSA C22.2 No.100
GB 12350
CQC
•
•
Thermal Class: 130 (B)
CE Marking
*
•
•
Applications standards
EN 60034-1, EN 60034-5, EN 60664-1
•
•
Installation conditions
(For EN standard)
Terminal box type: Overvoltage category
ІІ
, Pollution degree 3, Class
І
equipment
Lead wire type: Overvoltage category
ІІ
, Pollution degree 2, Class
І
equipment
When the machinery to which the motor is mounted requires overvoltage
category
ІІІ
specifications, install the motor in a cabinet that connect to power
supply via an isolation transformer.
*
Temperature rise tests required by the above standards are performed in a
state that has been attached a heat radiation plate instead of a gearhead.
The size and material for the heat radiation plates are as follows.
Size: 200×200 mm (7.87×7.87 in.)
Thickness: 5 mm (0.20 in.) Material: Aluminum alloy