background image

18

Cleaning the boiler every year

Cleaning the Induced draft blower:

200013_EN 1.2

Summary of Contents for Easypel

Page 1: ...Operating Manual Easypell 16 32kW ENGLISH...

Page 2: ...N 1 2 Version valid from 09 2015 Approved Wohlinger Christian Author Eco Engineering 2050 GmbH A 4132 Lembach M hlgasse 9 Tel 43 0 72 86 74 50 Fax 43 0 72 86 74 50 10 E Mail office easypell com by Eco...

Page 3: ...e el ll l 1 11 1 7 7 M Ma ai in nt te en na an nc ce e a an nd d s se er rv vi ic ci in ng g 1 13 3 7 1 Maintenance 13 7 2 Emptying the ash pan 13 7 3 Cleaning the boiler every year 15 8 8 O Op pe er...

Page 4: ...read this manual right through and take note of the safety warnings Keep all documentation supplied with this unit in a safe place for future reference Please pass on the documentation to the new user...

Page 5: ...ld lead to death or life threatening injury Warning indicates a situation that could lead life threatening or serious injury Caution indicates a situation that could lead to injury Note indicates a si...

Page 6: ...ed with suffi cient combustion air The openings in the combustion air inlet must never be partially or completely closed Ventilation systems central vacuum cleaning systems extractor fans air conditio...

Page 7: ...op pe er rt ty y Heat the pellet heating system using pellets that comply with EN 14961 2 class A1 and A2 only D Da am ma ag ge e t to o p pr ro op pe er rt ty y Do not use the heating system if it or...

Page 8: ...ntaining chlorine nitrobenzene or halogen in the room where the heating system is installed if combustion air is drawn directly from the room Do not hang out washing in the central heating room Preven...

Page 9: ...e of the boiler Safety temperature sensor The pellet boiler is equipped with a safety temperature sensor This is located on the pel let boiler If the boiler temperature exceeds 95 C then the heating s...

Page 10: ...et ts s o of f n na at tu ur ra al l w wo oo od d t th ha at t c co om mp pl ly y w wi it th h s st ta an nd da ar rd d E EN N 1 14 49 96 61 1 2 2 c cl la as ss s A A1 1 w wi it th h a a d di ia am me...

Page 11: ...d 32kW Note Refer to the data plate for the power rating of your Easypell The data plate is located on the rear side of the boiler Here you find the type designation manufacturer s serial number and y...

Page 12: ...late 7 Suction fan 2 Flame tube 8 Anti blowback system 3 Heat exchanger 9 Burner auger 4 Boiler water 10 Electronic ignition 5 Boiler insulation 11 Combustion chamber sensor 6 Combustion chamber cover...

Page 13: ...elting point 1300 C and pellets with higher bulk density 650kg leads to additional cleaning of the burner plate at regular intervals 7 2 Emptying the ash pan R Ri is sk k o of f b bu ur rn ns s Use gl...

Page 14: ...14 Emptying the ash pan 200013_EN 1 2...

Page 15: ...s Do not clean the boiler until it has been allowed to cool down Switch off the heating system at least 6 hours before opening the boiler Switch off the main switch before starting any mainte nance wo...

Page 16: ...16 Cleaning the boiler every year Procedure for cleaning the boiler 200013_EN 1 2...

Page 17: ...p pe er rf fo or rm ma an nc ce e a an nd d d da am ma ag ge e t to o p pe el l l le et t b bo oi il le er r d du ue e t to o b bl lo oc ck ka ag ge es s i in n t th he e a ai ir r i in nl le et t Cle...

Page 18: ...18 Cleaning the boiler every year Cleaning the Induced draft blower 200013_EN 1 2...

Page 19: ...dren away from the central heating room and storage room F Fi ir re e r ri is sk k Keep the ash removal door closed while the boiler is in operation 8 1 Description of the control panel The control pa...

Page 20: ...played the set value can be changed When this function is selected the value can be changed by pressing the arrow keys When this function is selected you leave the menu without saving the changed valu...

Page 21: ...ile the fire protection device is being opened approx 2 minutes After the fire protection device has been opened the ignition process starts and the symbol for ignition is displayed On completion of t...

Page 22: ...emperature Note This function is only available if a DHW sensor is connected to the boiler controller Please also refer to the installation manual chapter 13 Controller for heating and hot water The c...

Page 23: ...he value can be raised or lowered by pressing the keys button save value The stored value is displayed button 9 9 1 1 1 1 S Se et tt ti in ng g t th he e t ti im me e p pr ro og gr ra am m f fo or r D...

Page 24: ...tton Cursor at the hour button The value can be set by pressing the keys button save value Cursor jumps to the minute Other values minutes and hours are set as described above Note The set heating per...

Page 25: ...time program for DHW heating 25 button Cursor at the symbol button button Activate the set heating periods The symbol shows that the heating periods have been activated and saved Operating Manual Easy...

Page 26: ...26 Setting the time button 9 9 1 1 2 2 S Se et tt ti in ng g t th he e t ti im me e The current time is displayed Note The time is set in the same way as the heating periods button 200013_EN 1 2...

Page 27: ...ion only Pressing the button repeatedly returns you to the start screen Status display symbols Display Description DHW priority active heating circuit demand is subordinate Pump output active Minimum...

Page 28: ...l chapter 13 Controller for heating and hot water If heating periods are programmed the boiler runs at the set times During these periods burner requests from the external controller terminal 7 8 are...

Page 29: ...The value can be set by pressing the keys button save value Cursor jumps to the minute Other values minutes and hours are set as described above Note The set heating period still needs to be activate...

Page 30: ...30 Setting the boiler heating period button Cursor at the symbol button button Activate the set heating periods The symbol shows that the heating periods have been activated and saved 200013_EN 1 2...

Page 31: ...the time 31 button 9 9 2 2 1 1 S Se et tt ti in ng g t th he e t ti im me e The current time is displayed Note The time is set in the same way as the heating periods button Operating Manual Easypell...

Page 32: ...be entered This display is for information only Pressing the button repeatedly returns you to the start screen Status display symbols Display Description Pump output active Minimum boiler temperature...

Page 33: ...e The system restarts automatically when the cause has been eliminated Overview of malfunction alarm texts Display Error code 0 Description Boiler sensor fracture measuring circuit from boiler sensor...

Page 34: ...ure too low sensor temperature below measuring range 10 C sensor polarity incorrect exchange and connections Display Error code 4 Description Negative draft input open measuring circuit from negative...

Page 35: ...to cool and reset alarm Display Error code 8 9 Description Flue gas minimum temperature not reached during ignition phase Cause and Remedy no pellets available fill up with pellets ignition electrode...

Page 36: ...connectors Display Error code 14 Description Container cover open Cause and Remedy Cover open close cover End switch defect replace end switch Display Error code 15 Description DHW sensor fracture me...

Page 37: ...e original Eco Engineering spare parts only Not using original Eco Engineering spare parts will cause the warranty to become void 10 5 Checking the central heating room and storage room Checking the p...

Page 38: ......

Page 39: ......

Page 40: ......

Reviews: