53
2x red
1x
orange
When this message is displayed, the unit has made an
emergency stop. This means that the measured input air
temperature is lower than 5°C. In this case, check how the
unit is oriented (left or right) and whether the ducts are
connected correctly.
To change the unit orientation, see section 4.3.
Check that the bypass valve is closed. Check that
the fans are correctly assigned. If necessary,
reassign the fans. See chapter 7.5.