Wiring to Orcomm Smart Touch Screen (V1 pre 6/2018 models)
The below can be followed when installing with monitors Version 1.
Touch Screen Monitor will need to be set in
“
NO
”
mode
Voltage will measure 4 to 5V DC in standby mode
When Zones 1
–
8 are pulled below 1V DC the alarm will trigger
Wiring to Orcomm Smart Touch Screen (V2 8/2018 onwards)
The below can be followed when installing with monitors Version 2.
Touch Screen Monitor will need to be set in
“
3C
”
mode
Voltage will measure between 2 to 3V DC in standby mode
When Zones 1
–
8 are pulled higher than 4V DC the alarm will trigger