3   

Device setting

Input wiring diagram for type DC and DU

+

-

7

9

8

10

12

11

+

+

-

7

9

8

10

12

11

+

Input wiring diagram for type PM

+

-

7

9

8

10

12

11

+

RANGE 

DC

0…60 /75/100/150 / 300 mV
0…1000
±60 / ±75 mV
±100/150 / 300 mV
±1000

Input 1

8

0…20 /±40 V 
±20 / ±40 V

Input 2

9

0…100 mA
±100 mA

Input 3

12

RANGE 

PM

Passive

0…5/20 mA
±5 / ±20 mA
4…20 mA

Input 3

12

Active

4…20 mA

Input 3

10

0…2/5/10 V
±2 / ±5 / ±10 V

Input 2

9

Voltage [mV]

Voltage [V]

Voltage [V]

Current [mA]

passive

4-20 [mA]

active

Input wiring diagram for type OHM, Pt, Ni, Cu, PTC, NTC and TC

i

In case 2-wire connection is used either for RTD or 

for OHM measurement, it is absolutely essential to 

interconnect the unconnected terminals

(7+8 / 9+11)

7

9

8

10

12

11

ES-

ES+

7

9

8

10

12

11

S+

E+

ES-

7

9

8

10

12

11

S-

S+

E+

E-

2-wire

4-wire

3-wire

7

9

8

10

12

11

+

RANGE

T/C

J / K / T / E / B / S / R / N / L/XK

Input 1

8

7

9

8

10

12

11

Linear potentiometer

Analogue input range setting, TEACH-IN

1.  by a long press (>2s) of the 

SET

 button enter the configuration mode - LED 

PWR

  

yellow and LED 

SET

 turquoise 

2.  connect the signal of the desired value for the minimum of the range 

RNG.MIN.

 to the input of the converter (for example 5 mA)

3.  by a long press (>2s) of the 

SET

 button this value is set - LED 

PWR

  

yellow, LED 

SET

  

purple

4.  connect the signal of the desired value for the maximum of the range 

RNG.MAX.

 to the input of the converter (for example 19,5 mA)

5.  by a long press (>2s) of the 

SET

 button this value is set - LED 

PWR

  

yellow, LED 

SET

  

  

green

6.  by a short press of the 

SET 

button return to the standard working mode - LED 

PWR

  

green

For a quick and simple set-up you can use the DIP switch

Tare settings

1.  by a short press of the 

SET 

button enter configuration of Tare - LED 

PWR

  

white and LED 

SET

turquoise

2.  by a long press (>2s) of the 

SET

 button set the current value of Tare - LED 

PWR 

  

white, LED 

SET

     green

3. by a short press of the 

SET 

button return to the standard working mode with active Tare - LED 

PWR

  

green, LED 

SET

 white

i

A short press at any time during the calibra-

tion will end the calibration without saving.

After one minute of inactivity, the calibration 

is terminated without saving and both LEDs 

return to the basic state

7

9

8

10

12

11

+−

7

9

8

10

12

11

+

7

9

8

10

12

11

+−

Current [mA]

i

Setting of 

Analogue input TEACH-IN

 is 

active only when DIP switches No. 1-5 are in 

the “0” position, i.o.

 Setting via OM Link

Thermocouple

i

Minimum range of 

Analogue output

 for U/I 

inputs signals is pre-set as unipolar,

 i.e. "0 V/mA" or "4 mA".

If required, it is also possible to enter a nega-

tive value of the maximum in the minimum, 

i.e. zero will be in the middle of the selected 

range.

MINI-TECHDOK - OMX 311UNI - 2022.1 - en

www.orbitmerret.eu

2 / 4

1 2 3 4 5 Input - Type

1 2 3 4 5 Input - Type

1 2 3 4 5 Input - Type

Setting via OM Link

• • •

Pt100/3920 ppm, 2/4 w [US]

• • •

NTC 10k/3435, 2/4 w

Voltage [V]

• •

Pt100/3920 ppm, 3 w [US]

• • •

NTC 10k/3435, 3 w

• •

Current [mA]

• • •

Pt100/3910 ppm, 2/4 w [RU]

• • • •

NTC 20k/4263, 2/4 w

• • •

Pt100/3910 ppm, 3 w [RU]

• •

NTC 20k/4263, 3 w

• •

Voltage [mV]

• • • •

Pt1000/3850 ppm, 2/4 w [EU]

• •

Thermocouple - B

• •

Resistance 2/4 w

Pt1000/3850 ppm, 3 w [EU]

• • •

Thermocouple - E

• • •

Resistance 3 w

Ni1000/5000, 2/4 w

• • • •

Thermocouple - J

Linear potentiometer

• • •

Ni1000/5000, 3 w

• • •

Thermocouple - K

Pt100/3850 ppm, 2/4 w [EU]

• • • •

Ni1000/6180, 2/4 w

• • • •

Thermocouple - R

• •

Pt100/3850 ppm, 3 w [EU]

• •

Ni1000/6180, 3 w

• • • •

Thermocouple - S

• • • • •

Thermocouple - T

6 7 8

Input - Range

Voltage [V]

Voltage [mV]

Current

Resistance

Pt / Ni

T/C

NTC / PTC

0…5 V

0…60 mV

0…5 mA

100 Ω

0°…100°C

0°…100°C

0°…50°C

0…10 V

0…150 mV

0…20 mA

300 Ω

0°…200°C

0°…200°C

0°…100°C

0…20 V

0…1000 mV

4…20 mA

1 kΩ

0°…300°C

0°…500°C

0°…200°C

• •

0…40 V

±60 mV

5…0 mA

3 kΩ

0°…400°C

0°…800°C

-50°…50°C

5…0 V

±150 mV

20…0 mA

10 kΩ

0°…500°C

0°…1000°C

-50°…100°C

• •

10…0 V

±1000 mV

20…4 mA

30 kΩ

0°…800°C

-100°…100°C

• •

±5 V

±5 mA

100 kΩ

0°…1000°C

-100°…200°C

• • •

±10 V

±20 mA

300 kΩ

-50°…100°C

-100°…300°C

9 10 Output - Range

0…10 V

0…20 mA [Act.]

4…20 mA [Act.]

• •

4…20 mA [Pas.]

Summary of Contents for OMX 311UNI

Page 1: ... Digital DIN rail mounted signal convertor MULTIFUNTION INPUT DC PM RTD T C DU z Multifunction input DC PM RTD T C DU z Configurable type and measuring range z Analogue output passive active z Quick configuration by DIP switch z PC configurable via USB port z Excitation 24 VDC z Galvanic isolation 2 5 kVAC z Simple instalation to DIN rail de cs ru en fr Note There is galvanic connection between USB c...

Page 2: ... SET green 3 by a short press of the SET button return to the standard working mode with active Tare LED PWR green LED SET white i A short press at any time during the calibra tion will end the calibration without saving After one minute of inactivity the calibration is terminated without saving and both LEDs return to the basic state 7 9 8 10 12 11 7 9 8 10 12 11 7 9 8 10 12 11 Current mA i Setti...

Page 3: ... 4 02 mA MAN HI Setting the HI input signal value 19 97 for MAX example 19 97 mA 99999 4 999999 99999 20 999999 MAN LO MAN HI T IN LO T IN HI For the minimum of the selected input range For the maximum of the selected input range YES YES YES YES YES Short circuit leads on the sensor side and select YES Output Password to connect the device to PC If it is set to 0 access is not blocked Setting the ...

Page 4: ...ponential power root Linearization linear interpolation in 100 points only via OM Link OM Link company communication interface for operation setting and update of instruments microUSB Watch dog reset after 500 ms Calibration at 25 C and 40 r h ANALOGUE OUTPUT No of outputs 1 Type isolated configurable with a resolution of 10 000 parts type and range are selectable in the menu Non linearity 0 1 of ...

Reviews: