INPUT

No. of inputs

1

The range is selectable either by DIP switch or 

by OM Link free SW from PC

DC

Range

±60 mV

> 10 MΩ

Input 1

±75 mV

> 10 MΩ

Input 1

±100 mV

> 10 MΩ

Input 1

±150 mV

> 10 MΩ

Input 1

±300 mV

> 10 MΩ

Input 1

±1000 mV

> 10 MΩ

Input 1

±20 V

1 MΩ

Input 2

±40 V

1 MΩ

Input 2

±100 mA

< 200 mV

Input 3

PM

Range

±5 mA

< 200 mV

Input 3

±20 mA

< 200 mV

Input 3

4…20 mA

< 200 mV

Input 3

±2 V  

1 MΩ

Input 2

±5 V  

1 MΩ

Input 2

±10 V

1 MΩ

Input 2

OHM

Range 

0…100 / 300 Ω 

 

0…1 / 3 / 10 / 30 /100 kΩ

0…300 kΩ  (only 2- and 4-wire)

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

RTD

Range

Pt 100/500/1000, 3851 ppm/°C -50°…450°C

Pt 100, 3 920 ppm/°C

-50°…450°C

Pt 50, 3 910 ppm/°C

-200°…1100°C

Pt 100, 3 910 ppm/°C

-200°…450°C

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

Ni

Range

Ni 1 000/10 000, 5 000 ppm/°C -50°…250°C

Ni 1 000/10 000, 6 180 ppm/°C -200°…250°C

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

Cu

Range

Cu 50/100, 4 260 ppm/°C

-50°…200°C

Cu 50/100,  4 280 ppm/°C

-200°…200°C

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

NTC

Range

NTC 1 2k2, B

2585

 = 3600

-40°…125°C

NTC 2 2k0, B

2585

 = 3528

-40°…125°C

NTC 3 10k, B

2585

 = 3435

-40°…125°C

NTC 4 10k, B

2585

 = 3977

-40°…125°C

NTC 5 12k, B

2585

 = 3740

-40°…125°C

NTC 6 20k, B

2585

 = 4263

-40°…125°C

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

PTC

Range

KTY 81/210

-55°…150°C

Connection

2-, 3- and 4-wire

with broken cable/sensor detection

T/C

Range

J (Fe-CuNi) 

 

-200°…900°C

K (NiCr-Ni) 

 

-200°…1 300°C

T (Cu-CuNi) 

 

-200°…400°C

E (NiCr-CuNi) 

 

-200°…690°C

B (PtRh30-PtRh6)   

300°…1 820°C

S (PtRh10-Pt) 

 

-50°…1 760°C

R (Pt13Rh-Pt) 

 

-50°…1 740°C

N (Omegalloy) 

 

-200°…1 300°C

L (Fe-CuNi)  

 

-200°…900°C

XK (Chromel-Copel)

    -200°...800°C

with broken cable/sensor detection

CJC

adjustable: -20°…99°C or automatic

DU

Power

1.65 VDC/3 mA,

potentiometer resistance > 500 Ω

INSTRUMENT SPECIFICATIONS

TC

50 ppm/°C

Accuracy

±0.1 % of the range (for 20 meas./s)

±0.15 % of the range (OHM - 100k/300k)

Rate

1…100 measurements/s

Overload 

capacity

10x (t < 30 ms), 2x

Compensation of  

conduct

max. 30 Ω (RTD)

Measurement 

accuracy CJC

±1.5°C (T/C)

Functions

Teach-in, Tare, Math functions, Simulation

Digital filters

exponential / floating / arithmetic average, 

rouding

Math functions

polynomial / inverse polynomial / logarithm /

exponential / power / root

Linearization

linear interpolation in 100 points

(only via OM Link)

OM Link

company communication interface for 

operation, setting and update of 

instruments. (microUSB)

Watch-dog

reset after 500 ms

Calibration

at 25°C and 40 % r.h.

ANALOGUE OUTPUT

No. of outputs

1

Type

isolated, configurable with a resolution of 

10 000 parts, type and range are selectable 

in the menu

Non-linearity

0.1 % of FS

TC

15 ppm/°C

Rate

response to change of value < 3,5 ms

Ranges

0…10 V, 10…0 V

resistive load < 2,6 kΩ

0…20 mA/20…0

4…20/20…4 mA (active/passive)

compensation of leads' resist. < 600 Ω/12 V

EXCITATION

Fixed voltage

24 VDC/35 mA, isolated

POWER SUPPLY

Power

10…30 VDC/24 VAC, ±10 %, 2.5 VA, PF ≥ 0.4, 

I

STP

< 40 A/1 ms, isolated

- fuse inside (T500mA)

MECHANIC PROPERTIES

Material

PA66, incombustible UL 94 V-0, blue

Dimensions

114.5 x 99.0 x 17.5 mm

Installation

to DIN rail 35 mm wide

OPERATING CONDITIONS

Connection

connector terminal blocks, 

section < 2.5 mm

2

Stabilization 

period

within 5 minutes after switch-on

Working temp.

-20°…60°C 

Working 

humidity

< 95 % r.h., non condensing

Storage temp.

-20°…85°C

Protection

IP20

Construction

safety class I

El. safety

EN 61010-1, A2

Dielectric 

strength

2.5 kVAC for 1 min. between power supply 

and signal input

2.5 kVAC for 1 min. between signal input 

and outputs

Insulation 

resist.*

for pollution degree II, measurement cat. III

power supply > 300 V (PI), 255 V (DI)

Input/outputs > 300 V (PI)

EMC

EN 61326-1 (Industrial area)

Seismic

qualification

IEC/IEEE 60980-344 Edition 1.0, 2020, par. 6, 9

Mechanical 

resistance

EN 60068-2-6 ed. 2:2008

* PI - Primary insulation, DI - Double insulation

6   

Technical data

5   

Instrument dimensions and installation

ORBIT MERRET, spol. s r.o.

Vodňanská 675/30

198 00  Praha 9

Czech Republic

+420 - 281 040 200   

[email protected]

Measuring instruments of the OMX 311UNI series conform to the European regulation 2014/30/EU and 2014/35/EU

This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.

As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication.

Side view

mm

inch

Front view

17,5

0.69

Top view

Installation to DIN rail of 35 mm width

4.49

114,5

4.47

114,5

1 2 3 4 5 6 7 8 9 10 11 12

ON

1

2

4

5

3
6

SET

SET
PWR

7

8

10

11

9

12

3.90

99

MINI-TECHDOK - OMX 311UNI - 2022.1 - en

4 / 4

www.orbitmerret.eu

Summary of Contents for OMX 311UNI

Page 1: ... Digital DIN rail mounted signal convertor MULTIFUNTION INPUT DC PM RTD T C DU z Multifunction input DC PM RTD T C DU z Configurable type and measuring range z Analogue output passive active z Quick configuration by DIP switch z PC configurable via USB port z Excitation 24 VDC z Galvanic isolation 2 5 kVAC z Simple instalation to DIN rail de cs ru en fr Note There is galvanic connection between USB c...

Page 2: ... SET green 3 by a short press of the SET button return to the standard working mode with active Tare LED PWR green LED SET white i A short press at any time during the calibra tion will end the calibration without saving After one minute of inactivity the calibration is terminated without saving and both LEDs return to the basic state 7 9 8 10 12 11 7 9 8 10 12 11 7 9 8 10 12 11 Current mA i Setti...

Page 3: ... 4 02 mA MAN HI Setting the HI input signal value 19 97 for MAX example 19 97 mA 99999 4 999999 99999 20 999999 MAN LO MAN HI T IN LO T IN HI For the minimum of the selected input range For the maximum of the selected input range YES YES YES YES YES Short circuit leads on the sensor side and select YES Output Password to connect the device to PC If it is set to 0 access is not blocked Setting the ...

Page 4: ...ponential power root Linearization linear interpolation in 100 points only via OM Link OM Link company communication interface for operation setting and update of instruments microUSB Watch dog reset after 500 ms Calibration at 25 C and 40 r h ANALOGUE OUTPUT No of outputs 1 Type isolated configurable with a resolution of 10 000 parts type and range are selectable in the menu Non linearity 0 1 of ...

Reviews: