Replacing Flash Modules
11.
If you replaced faulty DIMMs, clear the server DIMM faults.
a.
To see server faults, log in to the ILOM SP as
root
and type the following
ILOM CLI command list all known fault on the system:
->
show /SP/faultmgmt
The server lists all known faults, for example:
->
show /SP/faultmgmt
Targets:
0 (/SYS/MB/P0/D2)
Properties:
Commands:
cd
show
b.
To clear the fault, type the following command:
->
set /SYS/MB/P
n
clear_fault_action=true
Where P
n
is the DIMM number. For example, to clear a fault on the DIMM in location D2
on CPU0:
->
set /SYS/MB/P0/D2 clear_fault_action=true
Are you sure you want to clear /SYS/MB/P0 (y/n)?
y
Set ???clear_fault_action” to ???true???
Related Information
■
“DIMM and CPU Physical Layout” on page 133
■
“DIMM Population Rules” on page 134
■
“DIMM Considerations and Limitations” on page 135
■
“DIMM Rank Classification Labels” on page 136
■
“Error Correction and Parity” on page 136
■
“Identify and Remove Faulty DIMMs” on page 137
Replacing Flash Modules
The server contains two slots for flash modules. These topics describe how to remove and
install these flash modules.
Replacing Motherboard Assembly Components
143
Summary of Contents for Sun Netra X4270
Page 1: ...Sun Netra X4270 Server Service Manual Part No E23171 03 September 2015 ...
Page 2: ......
Page 10: ...10 Sun Netra X4270 Server September 2015 ...
Page 12: ...12 Sun Netra X4270 Server September 2015 ...
Page 36: ...36 Sun Netra X4270 Server September 2015 ...
Page 72: ...72 Sun Netra X4270 Server September 2015 ...
Page 100: ...100 Sun Netra X4270 Server September 2015 ...
Page 224: ...224 Sun Netra X4270 Server September 2015 ...
Page 230: ...WDT W WDT watchdog timers 230 Sun Netra X4270 Server September 2015 ...