Remove the Rear I/O Module
174
SPARC T5-8 Server Service Manual • November 2015
Are you sure you want to start the faultmgmt shell (y/n)?
y
faultmgmtsp>
3.
Use the
fmadm
faulty
command to determine if the main module is operating
normally.
■
“Diagnostics Process” on page 25
.
■
If no fault was detected, the main module is operating normally.
Related Information
■
“Remove the Rear I/O Module” on page 174
■
“Install the Rear I/O Module” on page 176
■
“Verify the Rear I/O Module” on page 178
Remove the Rear I/O Module
The rear I/O module is a cold-service component that can be replaced only after you have
powered off the server. For the location of the rear I/O module, see
.
Caution -
This procedure requires that you handle components that are sensitive to electrostatic
discharge. This discharge can cause server components to fail.
1.
Take the necessary ESD precautions.
See
“Prevent ESD Damage” on page 57
2.
Remove all of the power from the server.
See
“Removing Power From the Server” on page 53
.
3.
Locate the rear I/O module.
See
“Rear Panel Components (Service)” on page 15
for the location of the rear I/O module in
the server.
4.
Label the cables connected to the ports on the rear I/O module, and then
disconnect the cables from the ports.
You will reconnect the cables to the same ports on the replacement rear I/O module.
Summary of Contents for SPARC T5-8
Page 1: ...Part No E35082 14 November 2015 SPARC T5 8 Server Service Manual ...
Page 2: ......
Page 10: ...10 SPARC T5 8 Server Service Manual November 2015 ...
Page 12: ...12 SPARC T5 8 Server Service Manual November 2015 ...
Page 48: ...48 SPARC T5 8 Server Service Manual November 2015 ...
Page 58: ...58 SPARC T5 8 Server Service Manual November 2015 ...
Page 108: ...108 SPARC T5 8 Server Service Manual November 2015 ...
Page 122: ...122 SPARC T5 8 Server Service Manual November 2015 ...
Page 140: ...140 SPARC T5 8 Server Service Manual November 2015 ...
Page 148: ...148 SPARC T5 8 Server Service Manual November 2015 ...
Page 180: ...180 SPARC T5 8 Server Service Manual November 2015 ...
Page 190: ...190 SPARC T5 8 Server Service Manual November 2015 ...
Page 194: ...194 SPARC T5 8 Server Service Manual November 2015 ...
Page 200: ...200 SPARC T5 8 Server Service Manual November 2015 ...
Page 206: ...206 SPARC T5 8 Server Service Manual November 2015 ...