An unfavorable output from these commands indicates a hardware fault with that
particular component. A voltage or temperature deviating more than 10% from the
provided specification means a problem with the respective component.
For example, on the CLI of the switch, enter the following command to check its
status:
# env_test
This command performs a set of checks and displays the overall status of switch, as in
the following example:
Environment test started:
Starting Voltage test:
Voltage ECB OK
Measured 3.3V Main = 3.28 V
Measured 3.3V Standby = 3.37 V
Measured 12V = 12.06 V
Measured 5V = 5.03 V
Measured VBAT = 3.25 V
Measured 1.0V = 1.01 V
Measured I4 1.2V = 1.22 V
Measured 2.5V = 2.52 V
Measured V1P2 DIG = 1.17 V
Measured V1P2 AND = 1.16 V
Measured 1.2V BridgeX = 1.21 V
Measured 1.8V = 1.80 V
Measured 1.2V Standby = 1.20 V
Voltage test returned OK
Starting PSU test:
PSU 0 present
PSU 1 present
PSU test returned OK
Starting Temperature test:
Back temperature 23.00
Front temperature 32.62
SP temperature 26.12
Switch temperature 45, maxtemperature 45
Bridge-0 temperature 41, maxtemperature 42
Bridge-1 temperature 43, maxtemperature 44
Temperature test returned OK
Starting FAN test:
Fan 0 not present
Fan 1 running at rpm 11212
Fan 2 running at rpm 11313
Fan 3 running at rpm 11521
Fan 4 not present
FAN test returned OK
Starting Connector test:
Connector test returned OK
Starting onboard ibdevice test:
Switch OK
Bridge-0 OK
Bridge-1 OK
All Internal ibdevices OK
Onboard ibdevice test returned OK
Environment test PASSED
When the switch status is operational, you can start the Subnet Manager (SM).
Verify the Switch Status
Use the Sun Datacenter InfiniBand Switch 36 in Multirack Configurations 14-3
Summary of Contents for Exalogic Elastic Cloud
Page 12: ...xii ...
Page 70: ...Default Port Assignments 4 16 Machine Owner s Guide ...
Page 82: ...Initial Network Configuration of Exalogic Machine 5 12 Machine Owner s Guide ...
Page 102: ...Network Configuration Worksheets 6 20 Machine Owner s Guide ...
Page 112: ...What Next 7 10 Machine Owner s Guide ...
Page 134: ...Use the Phone Home Service to Manage the Storage Appliance 8 22 Machine Owner s Guide ...
Page 162: ...Oracle Solaris Creating VNICs and Associating Them with VLANs 11 6 Machine Owner s Guide ...
Page 250: ...Using Oracle Services in Oracle Enterprise Manager Ops Center 17 36 Machine Owner s Guide ...
Page 324: ...Power Distribution Unit Cabling Tables E 32 Machine Owner s Guide ...
Page 338: ...Migrate a Zone to a New Host F 14 Machine Owner s Guide ...
Page 342: ...Install Update and Remove RPMs Using Yum G 4 Machine Owner s Guide ...