IF-722ETH version 5.0.001
6
IP Audio interface
2 inputs / 2 outputs
IF-722ETH
R+D Department
3.1.
IP Connection, communication and control module
Ground connection
1)
FUSE.
2.5 A Secondary power supply fuse.
2)
POWER SUPPLY 2
3)
24 VDC Secondary power input.
GND Contact
4)
FAIL
Contacts
5)
Output relay used to indicate a system failure.
If the COM contact is linked to the NO contact, it
indicates that there are no faults or alarms in the
system. If on the other hand, COM is linked to NC, it
indicates that the equipment is switched off or that
alarms were detected (figure 4).
Maximum
DC charge current: 150 mA
Maximum DC or AC peak charge voltage: 350 V
BUS
CAN Contacts
6)
Data communication bus between the IF-722ETH and
the system peripherals (MD-30C, ME-200C, NS-CAN).
OUTPUT CT Contacts
7)
Incorporates three output contacts configured as dry
contacts. Each contact has two terminals (A and B).
The functionality and stand-by state (NC/NO) are
configured through the
Call Point
software. They may be
configured as general purpose contacts or in the
evacuation system as fault notification contacts,
Emergency Mode
indicator activated...
INPUT Contacts CT 1, 2 and 3
8)
Incorporates three input contacts.
The functionality and stand-by state (NC/NO) are
configured through the
Call Point
software. They may be
configured as general purpose contacts or in the
evacuation system as emergency mode activation
contacts, evacuation
message activated...
The detection time of the activation pulse of the input
contacts is configurable through the
Call Point
software
(0-50-100-200-300-400-500-1000-1500-2000
milliseconds).
If you wish, the system may monitor these contacts
(short-circuit or open line detection).
ETH B Connector
9)
Is used in a redundant network as a secondary
connection to the IP network.
ETH A Connector
10)
Is used to connect the unit to the IP network.
LINK/ACTIVITY indicator
(green LED):
11)
When illuminated it indicates a network connection.
When flashing it indicates that data is being sent or
received.
SPEED indicator
(yellow LED):
12)
Speed of the network. If the LED is lit, indicates a speed
of 100 Mbps. If unlit, indicates a network speed of 10
Mbps (it is highly recommended to use a transmission
speed of 100 Mbps).
No alarms
COMPACT is turned off
or alarms detected
Figure 4
FAIL RELAY STATUS
Figure 3