TEMPERATURE CONVERSIONS ROUTINES
C-2
Pamux User’s Guide
ALGORITHMS
These algorithms should be used for all Pamux-compatible analog input modules that produce data
to be converted to temperatures. The algorithms are listed by input module.
AD4
ICTD
TEMP = (0.08262 * VALUE%) - 188.4
AD5, AD5T
TYPE J THERMOCOUPLE
TEMP = (VALUE% - A0) * A1 + A2
where A0, A1, and A2 depend on VALUE% and can be derived from the following table:
VVAALLUUEE%
%
AA00
AA11
AA22
TTeem
mp
p RRaange
nge ((°°CC))
< 1
104
0.1923067
20.15
-20 to -1
1 to 161
0
0.1863354
0.10
0 to 30
162 to 354
161
0.1813472
30.19
31 to 65
355 to 551
354
0.1776649
65.10
66 to 100
552 to 867
551
0.1740506
100.15
101 to 155
868 to 1766
867
0.1724137
155.10
156 to 310
1767 to 2546
1766
0.1730769
310.00
311 to 445
2547 to 2895
2546
0.1719197
445.05
446 to 505
2896 to 3191
2895
0.1689189
505.10
506 to 555
3192 to 3464
3191
0.1654411
555.10
556 to 600
3465 to 3743
3464
0.1612903
600.20
601 to 645
3744 to 3901
3743
0.1572327
645.17
646 to 670
> 3901
3901
0.1546391
670.10
> 670
Accurate to ±0.2°C from -20°C to 700°C.
Summary of Contents for PAMUX
Page 10: ...TABLE OF CONTENTS x Pamux User s Guide...
Page 14: ...TABLE OF CONTENTS xiv Pamux User s Guide...
Page 103: ...PROGRAMING WITH THE PAMUX DRIVER 3 42 Pamux User s Guide...
Page 121: ...PROGRAMING WITHOUT THE PAMUX DRIVER 4 18 Pamux User s Guide...
Page 125: ...TROUBLESHOOTING AND TIPS A 4 A 4 A 4 A 4 A 4 Pamux User s Guide...
Page 135: ...SPECIFICATIONS B 10 Pamux User s Guide...
Page 141: ...TEMPERATURE CONVERSIONS ROUTINES C 6 Pamux User s Guide...
Page 143: ...PRODUCT SUPPORT D 2 Pamux User s Guide...
Page 149: ...GLOSSARY E 6 Pamux User s Guide...