SELECTING THE JUMPERS
B1 and B2 User’s Guide
20
Baud Rate Selection
Jumpers B8, B9, and B11 select the baud rate. Possible configurations are shown below.
Table 2-1: Baud Rate Jumper Settings
Protocol Selection
Jumper B10 selects between 2-pass and 4-pass communications protocol. The 2-pass protocol is
the recommended protocol because it provides faster and more efficient communications. The
4-pass protocol is mainly for use as a troubleshooting aid. When jumper B10 is installed, 2-pass
protocol is selected. The unit can be put into a 4-pass mode by removing the B10 jumper or using
the Optomux software command “E.”
Address Selection
Jumpers B0 through B7 select the Optomux address. Each Optomux unit on the same network must
have a unique address (different from all the others). Addresses are arbitrary and do not need to be
sequential (although they must be unique). The following table lists the possible addresses with
corresponding jumper configurations. To use the table, find the address you wish to use (0 to 255).
To the right of the address is the sequence of jumpers in the following order: B7, B6, B5, B4, B3, B2,
B1, and B0.
Baud
Rate
B8
B9
B11
300
Not Installed
Not Installed
Not Installed
600
Not Installed
Not Installed
Installed
1200
Installed
Not Installed
Not Installed
2400
Installed
Not Installed
Installed
4800
Not Installed
Installed
Installed
9600
Not Installed
Installed
Not Installed
19200
Installed
Installed
Not Installed
38400
Installed
Installed
Installed
Summary of Contents for Optomux B1
Page 1: ...B1 AND B2 USER S GUIDE Form 1574...
Page 9: ...FOR HELP B1 and B2 User s Guide 4...
Page 26: ...CHAPTER 3 INSTALLATION AND WIRING B1 and B2 User s Guide 21 21 Figure 2 7 Jumper Addresses...
Page 29: ...SURGE PROTECTION FOR RS 422 485 COMMUNICATION LINKS B1 and B2 User s Guide 24...
Page 33: ...TROUBLESHOOTING QUESTIONS AND ANSWERS B1 and B2 User s Guide 28...