The Local Bus is a high speed parallel interface communicating over 1.4 megabi•ts per second and can be up to
200 ft. in length. It connects the G4LC32 controller to local digital and analog I/O units.
The following table lists some of the Local Bus specifications.
Local I/O Bus Specifications
No. of Active Lines
12
No. of Ground Lines
17
No. of Conductors in Cable
34
Cable Type
Flat Ribbon
Bus Drivers
Open collector
Impedance
100 ohm
Propagation Delay
1.7 ns/ft.
Max Bus Length
200 ft.
Bus Times
Adjusts between 200 and 700 ns, and
are distance proportional
Reset Line
None
Interrupts
Available
Digital Response Time
1 ms + Local Bus transmission time
Analog Response Time
3 to 7 ms + Local Bus transmission time
Bus Speed
1.4 MHz
Cables and Connectors
This table lists parts for making custom local bus cables.
Manufacturer
Ribbon Cable
3M P/N
Alpha P/N
Regular
3365/34
3580/34 or
3583/34
Ground Planed
3469/34 or
3476/34
3584/34
Jacketed
3603/34
3598/34
Jacketed and Ground
Planed
3517/34
3590/34
3M
Circuit
Assembly
Connectors
3414-7000
CA-34IDS-B
COMMUNICATIONS AND CABLES
5-9
Summary of Contents for G4LC32
Page 6: ...G4LC32 User s Guide WELCOME vi...
Page 8: ...G4LC32 User s Guide G4LC32 REVISED FEATURES 1 2...
Page 14: ...G4LC32 User s Guide INTRODUCTION 2 6...
Page 26: ...G4LC32 User s Guide G4LC32 Inside Panel CONFIGURATION 3 12...
Page 46: ...G4LC32 User s Guide COMMUNICATIONS AND CABLES 5 12...
Page 48: ...G4LC32 User s Guide SOFTWARE AND FIRMWARE 6 2...
Page 50: ...G4LC32 User s Guide...