DEVICENET INFORMATION
3-8
BD-DEVNET Users Guide
Connection Object Class Code: 05H
The Connection Objects manages the characteristics of each communication
connection. As a Group II Only Slave device the unit supports one explicit and one POLL
message connection.
Table 3-17: Class Attributes
Attr
Access
Name
Ty p e
Value
1
Get
Revision
UINT
1
** Connection IDs:
Connection 1 Produced Connection ID: 10xxxxxx011
Connection 1 Consumed Connection ID: 10xxxxxx100
Connection 2 Produced Connection ID: 01111xxxxxx
Connection 2 Consumed Connection ID: 10xxxxxx101
* Connection States:
0 = non-existent
1 = configuring
2 = established
3 = timed out
Table 3-18:Connection Object, Instance 1 Attributes (Explicit Message)
Attr
Access
Name
Ty p e
Value
1
Get
State
USINT
*
2
Get
Instance Type
USINT
0=Exp Msg
3
Get
Transport Class Trig.
USINT
83H
4
Get
Prod. Connection ID
UINT
**
5
Get
Cons. Connection ID
UINT
**
6
Get
Initial Comm Char.
USINT
21H
7
Get
Prod. Conn. Size
UINT
7
8
Get
Cons. Conn. Size
UINT
7
9
Get
Expected Packet Rate
UINT
2,500 msec
12
Get
Watchdog Timeout Act
USINT
1=autodel
13
Get
Prod. Conn. Path. Lngth
USINT
0
14
Get
Prod. Conn. Path
USINT
(null)
15
Get
Cons. Conn. Path. Lngth
USINT
0
16
Get
Cons. Conn. Path
USINT
(null)
xxxxxx = Node Address