19
(b) If no button is pressed within 10 seconds, it will return to original status.
3. “FUNC” is a Function button. Each function can be enabled by pressing this button.
(a). Push the “FUNC” button (at least 2 seconds) to choose which function that you
want.
Each content can be displayed by pressing at once, and it has
fourteen
kinds of function to be checked.
(b). After choosing the function, push the “ENTER” button to enter the function that you
want.
(c). Push the “FUNC” button to choose other function again.
(d). Push the “ENTER” button to enable your function.
(e). Push the “ENTER” button to confirm and enable your function.
(f). If no pressing within 10 seconds, it will return to original status.
7.3 Control Panel functions
Operation of the UPS is indicated on the monitor panel with five LED indicators and an
LCD screen. This display is also capable of alerting the user with audible alarms.
ON
This green LED is lit when UPS has been turned on.
ON-LINE
When the UPS is in normal or static bypass modes, there is voltage at the
output terminals and this LED will light up in green.
ON-BAT While operating in battery mode.
BYPASS While operating in bypass mode, this LED will light up in yellow.
FAULT If any internal error occurs in the UPS, this LED will light up in red and
give off an audible alarm. Press any of the buttons on the front panel to
turn off the alarm.
20
Status of the UPS, measurements and alarms are all indicated on the LCD screen.
Figure 6.
Control panel
Normal display
The UPS status is shown in normal display mode. From here you have a choice to go to UPS
meters display and the Setting display by pushing the button.
UPS meters display
Various measurements are available through the UPS meters display; pressing
the button will scroll through the following meters:
LCD message
Description
O/P VOLT= xxx, xV
Shows Output AC voltage
O/P FREQ= xx, x Hz
Shows Output Frequency
I/P VOL T= xxx, xV
Shows Input AC voltage
I/P FREQ= xx, x Hz
Shows Input Frequency
BAT VOLT= xx,xV
Shows Battery Voltage
O/P LOAD%= xx%
Shows Load % of max load
O/P W= xW
Shows Output Watts
O/P VA= xVA
Shows Output VA
O/P CURR= xA
Shows Output Current
BACKUP TIME= xx min
Shows Estimated Backup time in minutes
BAT CHARG= xx%
Shows approximate percentage of Battery capacity
TEMPERATURE= xxC
Shows approximate ambient temperature
BAT PACK NUM= x
Shows External Battery Pack Number
RATING = xxxxVA
Shows UPS Rating
CPU VERSION xx.x
Shows CPU Version