Manual test of the UPS 

Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well 
and are functional even when the UPS is not charging the battery. 

Manual Battery test:  Scroll the parameters until Manual Bat test displays on the LCD. 

Press the “Enter” button twice. 

**) Note: In order for the UPS and power management software to operate normally, 
Manual Bypass should always be set to OFF as the load will not be protected by the unit 
when Manual Bypass is ON. This is aimed for operating an external maintenance bypass 
switch. 

***) Note: You should turn UPS off and keep the AC power before you use “Generator” 
function. (even you want to select “\Generator\OFF” to back to normal mode). 

7.4 Interpreting UPS messages 

Troubleshooting procedures described here give simple instructions in determining UPS 
malfunctions. 

Start the troubleshooting procedure if you witness any alarm indication on the control panel. 

Alarm indicators 

The UPS gives the following audible alarms: 

z

 

If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds. 

z

 

If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will beep 
twice every 5 seconds. 

z

 

If UPS is on bypass and the BYPASSED LED is on, UPS will no beep. 

z

 

If UPS has an internal fault and the FAULT LED is on, the UPS will give a constant 
audible alarm displaying the cause on the LCD display. 

Silencing an alarm 

By pressing any of the three buttons on the front panel, the alarm can be turned off, except 
when the battery is low, which will cause the alarm to resound. 

On the LCD display, you can also choose silent alarm mode which will not warn you of any 
malfunction audibly. 

 

24

7.5 Trouble shooting 

Displayed on LCD 

Audible Alarm Alarm Description 

What You Should Do 

Output Overload 

Two Beeps per 
second 

The UPS is overloaded (in 
Line Mode). Your 
equipment needs more 
power than the UPS can 
provide. The UPS operates 
on bypass. 

Shut off the least important 
equipment connected to the 
UPS. If this solves the 
overload problem, the UPS 
will switch from bypass back 
to normal operation. 

Battery Test 

No Beeps 

The UPS is doing a battery 

test. 

No action needed. The UPS 

will return to normal operation 

when it successfully completes 

the battery test. 

Over-Charge 

Constant beep 

Batteries are 
overcharged. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Low Battery 

2 beeps every 
5seconds 

The unit is operating on 
battery power and will shut 
down soon due to very low 
battery voltage 

The unit will restart 
automatically when acceptable 
power returns. 

On-Battery 

Once every 5 
seconds 

The unit is operating on 
battery power. 

Save your data and perform a 
controlled shutdown. 

Charger Failure 

Constant beep 

Charger has failed. 

Phone the local dealer 

Over-Temperature 

Constant beep 

High ambient Temperature. Make sure the unit’s fans and 

vent holes are not blocked, and 
make sure the ambient 
surrounding temperature is not 
above 40 degree C. If these 
conditions did not solve the 
problem, call your service 
representative.  

Output Short 

Constant beep 

Output short circuit 

Call the Local dealer 

High output Voltage 

Constant beep 

High output voltage 

Call the Local dealer 

Low Output Voltage 

Constant beep 

Low output voltage 

Call the Local dealer 

  Bus Fault 

2 Beeps per 
second 

High internal DC bus 
Voltage. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Site wiring Fault 

1 Beep per 
second 

Voltage detected between 
Neutral and Ground 

UPS mains connector polarity 
is wrong. Rotate the connector 
(Schuko). UPS installed to 
mains supply without ground. 
See page 15 on how to disable 
the site wiring alarm 

Line abnormal 

1 Beep per 
second 

Wrong AC Line backed up 
during auto restart 

 

Summary of Contents for DS1000B

Page 1: ...User s Guide Durable Series Models DS1000B 1500B 2000B 3000B DS1000B RM 1500B RM 2000B RM 3000B RM ...

Page 2: ... local branch offices or your dealers Who the warranty protects This warranty is valid only for the first consumer purchaser What the warranty does not cover 1 Any product on which the serial number has been defaced modified or removed 2 Damage deterioration or malfunction resulting from a Accident misuse neglect fire water or other acts of nature unauthorized product modification or failure to fo...

Page 3: ...lusion of incidental or consequential damages so the above limitations and exclusions may not apply to you Limitations of Warranty for Australian States and Territories The Trade Practices Act 1974 and corresponding State and Territory Fair Trading Acts or legalization of another Government the relevant acts in certain circumstances imply mandatory conditions and warranties which cannot be exclude...

Page 4: ... classe B respecte toutes les ٛ aterielٛ s du Reglement sur le ٛ ateriel brouilleur du Canada Declaration of Conformity Request Units labeled with a CE mark comply with the following standards and directives z Harmonic Standards EN 50091 1 1 and EN 50091 2 z EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC ...

Page 5: ...el away from batteries 2 The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow up maintenance of the UPS and batteries CAUTION The unit has a dangerous amount of voltage If the UPS indicator is on the unit s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because...

Page 6: ...hat a power failure lasts longer than a UPS backup time it will shut down avoiding battery discharge and as soon as voltage comes back the UPS will automatically charge up and start recharging the batteries As shown in fig 1 block diagram z An input filter reduces transients on the mains z For maintaining full battery charge AC power is rectified and regulated in the rectifier feeding power to the...

Page 7: ... 3000VA 5 min 4 hours Additional External Battery Cabinets are available if more back up time is needed 6 3 Safety Information Information presented here is vital to all personnel and please also read the UPS safety manual Storage and Transportation Please handle with extreme caution since a high amount of energy is contained with the batteries Always keep the unit in position as marked on the pac...

Page 8: ...mber the following when locating the UPS system and battery options z Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C z Provide protection for the equipment from moisture z Space and ventilation requirements must be met Ensure there is 100mm behind and 50mm on the sides of the UPS for ventilation z Ensure that the...

Page 9: ...hased Installation with bottom bracket Part No RMB 06 2 PCS Screw M5 11 4 PCS Installation with rear bracket Part No RMB 01 2PCS Screw M5 11 4 PCS 10 5 2 Rear panel views 1KVA 1 5KVA Rear Panel SMART SLOT OPTIONAL DATA LINE PROTECTION BATTERY BACKUP OUTLETS EXTENDED BATTERY CONNECTOR USB SMART SLOT OPTIONAL DATA LINE PROTECTION BATTERY BACKUP OUTLETS EXTENDED BATTERY CONNECTOR USB 100 110 120V EPO...

Page 10: ...CUIT BREAKER 12 RM 1U 1KVA Rear Panel RM 2U 1KVA 1 5KVA Rear Panel INPUT CIRCUIT BREAKER EPO RS232 SMART SLOT OPTIONAL BATTERY BACKUP OUTLETS 100 110 120V BATTERY BACKUP OUTLETS SMART SLOT 220 230 240V CIRCUIT BREAKER EPO RS232 INPUT USB INPUT USB RS232 CIRCUIT BREAKER EPO INPUT USB BATTERY BACKUP OUTLETS DATA LINE PROTECTION DATA LINE PROTECTION BATTERY BACKUP OUTLETS SMART SLOT SMART SLOT 100 11...

Page 11: ...PS Connect a second battery cabinet to the first one with the cable provided if more than one is to be installed z Be aware of UPS parameters and changing the Battery pack quantity when using the external battery cabinets see chapter 7 2 z Connect the Input cable to the UPS and connect the other end to a grounded outlet The batteries will automatically charge when connected to the mains Please rea...

Page 12: ...that allows you to install different communications cards It can be used parallel with either the RS232 or USB ports Currently there are two cards available for the optional interface slot An SNMP WEB card allows management and monitoring over a network or internet and the AS 400 card allows voltage free relay contacts Your local dealer will have more information about these option cards Connectin...

Page 13: ...to chapter 5 2 regarding the two load segments that come with each model 18 7 User s guide to operations Necessary information for operation of the unit is covered in this chapter Normally the UPS runs automatically but on those few occasions such as just after installation all the starting and shutting down procedures are described herein 7 1 Starting and shutting down the UPS Starting the UPS z ...

Page 14: ...YPASS While operating in bypass mode this LED will light up in yellow FAULT If any internal error occurs in the UPS this LED will light up in red and give off an audible alarm Press any of the buttons on the front panel to turn off the alarm 20 Status of the UPS measurements and alarms are all indicated on the LCD screen Figure 6 Control panel Normal display The UPS status is shown in normal displ...

Page 15: ... goes into free run mode 2 5 7 5 Input Bypass Voltage I P Bypass Set Select Input Voltage range when bypass is available 10 10 15 15 20 10 15 Free Run Mode Free Run Set Select if UPS can run in Free run mode unsynchronized ON OFF ON Bypass Enable Disable at Free run mode Bypass disable If Enable is chosen the UPS can go to bypass when unsynchronized Disable Enable Disable HE mode Setting HE Mode S...

Page 16: ... What You Should Do Output Overload Two Beeps per second The UPS is overloaded in Line Mode Your equipment needs more power than the UPS can provide The UPS operates on bypass Shut off the least important equipment connected to the UPS If this solves the overload problem the UPS will switch from bypass back to normal operation Battery Test No Beeps The UPS is doing a battery test No action needed ...

Page 17: ... burn from high short circuit currents Please observe the following precautions 1 Remove jewelry and metal objects such as watches and rings 2 Use tools that have insulated handles 3 Keep tools and other metal objects from contacting and away from the batteries ELECTRIC ENERGY HAZARD Do not attempt to rewire alter or change any battery wiring or connectors Attempting to make such alterations can c...

Page 18: ...ss Voltage 184 265 VAC user selectable 28 Input Voltage range 120 140 160 VAC 276 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 1000 VA 4A 1500 VA 6A 2000 VA 7 7A 3000 VA 12A Input Power factor 0 97 OUTPUT Output Voltage 208 220 230 240 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion 5 THD at full non linea...

Page 19: ...oling Forced air cooling Humidity 0 95 non condensing Audible noise 40 db normal and battery mode 30 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 class B Immunity EN50091 2 100 110 120V Model OUTPUT POWER 1000VA 700W 1500VA 1050W 2000VA 1400W 3000VA 2100W Connection Input Attached power cord Connection Output 6 x 5 15R US 6 x 5 15R US 12 x 5 15R US 12 x 5 15R US Battery type Lead acid 7 2Ah 12...

Page 20: ...to 90 4 hours to 90 4 hours to 90 Dimensions W x L x H mm 428 x 425 x 84 428 x 425 x 84 428 x 635 x 84 428 x 635 x 84 Weight kg 17 1 18 1 31 6 32 5 19 Rack mount Model 1U OUTPUT POWER 1000VA 700W Connection Input IEC 320 10A Connection Output 4 x IEC 320 10A Battery type Lead acid 7 Ah 6V Number of batteries 4 Backup time full load 6 min Recharge time 4 hours to 90 Dimensions W x L x H mm 428 x 52...

Reviews: