Be sure to conduct a walk test at the following three points:
A. In front of the transmitter
B. In front of the receiver
C. At the mid point between the transmitter and receiver
The detector is installed properly when Alarm/Level indicator LED turns
ON in the tests at all the three points.
5-2 OPERATION CHECK
After installation is complete, be sure to check the operation.
Make sure that the Alarm/Level indicator LED is OFF.
If it is illuminated even when the beams are not blocked, make optical
alignment again.
Check that the Power/Low battery indicator LEDs on both transmitter and
receiver are ON.
If the Power/Low battery indicator LED is blinking, the battery power is low.
Replace with new batteries.
Conduct a walk test to check that Alarm/Level indicator LED on the
receiver turns ON as the walker interrupts the beams.
Specifications and design are subject to change without prior notice.
* The value is based on the condition that it is used within the ambient temperature range of 20 to 25°C.
** Using batteries other than those recommended may shorten the battery life.
TROUBLESHOOTING
6
SPECIFICATIONS
8
OPTIONS
9
These units are designed to detect an intruder and activate an alarm control panel. Being
only a part of a complete system, we cannot accept responsibility for any damages or
other consequences resulting from an intrusion.
These products conform to the EMC Directive 2004/108/EC.
NOTE
Model
SL-100TNR
SL-200TNR
Maximum detection range
30 m/100 ft.
Maximum arrival distance
265 m/800 ft.
Total: Approx.
500
μ
A
Transmitter: Approx. 200
μ
A
Receiver: Approx.
300
μ
A
Total: Approx.
600
μ
A
Transmitter: Approx. 300
μ
A
Receiver: Approx.
300
μ
A
Total: Approx.
600
μ
A
Transmitter: Approx. 200
μ
A
Receiver: Approx.
400
μ
A
Total: Approx.
700
μ
A
Transmitter: Approx. 300
μ
A
Receiver: Approx.
400
μ
A
60 m/200 ft.
530 m/1740 ft.
Detection method
Twin infrared beam interruption detection
SB-D02HP
by VITZROCELL
3.9 VDC
3.0 VDC
Transmitter
Receiver
Approx. 6 years
Approx. 5 years
Approx. 5 years
Approx. 5 years
Transmitter
Receiver
Approx. 1.5 years
Approx. 1 year
Approx. 1 year
Approx. 1 year
CRH-5 (CR123A
by Panasonic)
Interruption time
Variable between 50/100/250/500 ms (4 steps)
Power source
3.9 VDC D size lithium batteries
Each Transmitter and Receiver: 2 units
(SB-D02HP manufactured by VITZROCELL)
3.0 VDC CR123A lithium batteries Each Transmitter and Receiver: 8 units
(OPTION CRH-5: 2unit)
Current draw
(stand by /at 25°C)
Battery
life
Alarm output
Form C-Solid State Switch: 3.9 VDC, 0.01 A
Alarm period
2 s (±1)
Low battery output
N.C. (Solid State Switch): 3.9 VDC, 0.01 A
Cover tamper output
(Receiver)
N.C. (Solid State Switch): 3.9 VDC, 0.01 A
Opens when the battery cover removed.
Alarm/ Level indicator
ON:
Beam not received
(Receiver)
Blinking: Beam not received sufficiently
OFF: Beam
received
Power/ Low battery indicator
(Transmitter and Receiver)
ON: Power
ON
Blinking: Voltage reduction
OFF: Power
OFF
Operating temperature
-20°C to +60°C (-4°F to 140°F)
Operating humidity
95 % (max.)
Alignment angle
±90° Horizontal, ±5° Vertical
Dimension
H × W × D mm (inch): 295 (11.6) × 69 (2.7) × 117 (4.6)
Weight
1200 g (Total weight of Trans Receiver, excluding accessories)
International protection
IP65
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Power/Low battery indicator LEDs are
not illuminated. (transmitter/receiver)
Reversed battery polarity.
Check the battery polarity.
Alarm is not output.
Re
fl
ection from the
fl
oor or wall.
Beam has not been blocked.
Block all two beams.
Batteries are running out too quickly.
Set the cover properly.
Optical alignment not optimized.
Improper output
Problem with wiring.
Install the correct wiring.
Batteries are inactive condition.
Align beams away from the floor or wall.
Problem with tamper output.
DIMENSIONS
7
Output
Indicator
LED
*
**
BCU-5 Battery Common use Unit (2 units/set)
Unit: mm (inch)
Share power source and low battery signals between the main unit and the wireless
transmitter.
CRH-5 CR123A Battery Holder (2 units/set)
Battery holder when using CR123A as a power source
PCU-5 Power Convertor Unit (1 unit/set, battery is sold separately.)
Voltage convertor unit used to enable wired operation of the detector
55 (2.2)
26 (1.0)
16 (0.6)
See “4-2 OPTICAL ALIGNMENT”
on page 3 and make realignment.
Open and close the battery cover
20 times with two seconds intervals.
After this, open the battery plate
and then close it.
When the beam is blocked, the
“ALARM” indicator LED is illuminated
but the alarm is not activated.
Alarm is activated even if the
light is not blocked.
Even if new batteries are used, Low
battery indicator LED is ON.
Signal line short-circuited
Check the wiring.
Interruption time is too short.
See “4-1 BEAM INTERRUPTION
ADJUSTMENT” on page 3, set an
appropriate interruption time.
Surface of
Transmitter/Receiver cover
soiled.
Clean the cover (wipe the cover with
a soft cloth dampened with water or
diluted neutral detergent).
Optical alignment was not
performed properly.
See “4-2 OPTICAL ALIGNMENT” on
page 3 and make realignment.
Frost, snow or heavy rain
causes false alarm.
A
B
Transmitter
Receiver
C
Unit: mm (inch)
295 (11.6)
117 (4.6)
69 (2.7)
83.5 (3.3)
(WALL)
Unit: mm (inch)
34 (1.3)
34 (1.3)
56 (2.2)
Unit: mm (inch)
71 (2.8)
20 (0.8)
53 (2.1)
OPTEX CO., LTD. (JAPAN)
URL: http://www.optex.net/
OPTEX INC. (U.S.)
www.optexamerica.com
OPTEX DO BRASIL LTDA. (Brazil)
www.optex.net/br/es/sec
OPTEX (EUROPE) LTD. / EMEA HQ (U.K.)
www.optex-europe.com
OPTEX SECURITY SAS (France)
www.optex-security.com
OPTEX SECURITY Sp.z o.o. (Poland)
www.optex.com.pl
OPTEX (DONGGUAN) CO.,LTD.
SHANGHAI OFFICE (China)
www.optexchina.com
OPTEX KOREA CO.,LTD. (Korea)
www.optexkorea.com
OPTEX PINNACLE INDIA, PVT., LTD. (India)
www.optex.net/in/en/sec
OPTEX TECHNOLOGIES B.V.
(The Netherlands)
www.optex.eu