Fire Protection  |  Data sheet No. 43104  | Version 02-2016  | 

5

 | 

8

Control unit STG 1.2

Response from the STG 1.2

The response from the STG 1.2 appears as follows:

Byte 0 Byte 1

Byte 2

Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 

Byte  Byte n Byte 

n + 1

Byte 

n + 2

Byte 

n + 3

MSB

LSB

MSB

LSB

MSB

LSB

MSB

LSB

MSB

LSB

LSB

MSB

STG 

address

Func-

tion

Number 

of 

databytes

Register x

Register x+1

Re2

……..

Register y

CRC

At the outset the address of the STG 1.2 and the query function are always returned. Then the designation follows regarding the 
number of databytes (2 bytes of data are incurred per register). Thereafter the data (register) follows. The register set is dependent 
on the query, and can vary between 1 and 125. 

Register description:

Each register consists of 2 bytes. With Modbus RTU, it is possible to send 250 bytes of data (MSB is sent first). In this way a total of 125 
registers can be read at once with one query.

Register address

Description

0

STG general status

1

Number of connected detectors

2

Status of the detector at Address 1

3

Measured value of the detector at Address 1

4

Contamination in the detector at Address 1

5

Status of the detector at Address 2 

6

Measured value of the detector at Address 2

7

Contamination in the detector at Address 2

8

9

...

296

Status of the detector at Address 99

297

Measured value of the detector at Address 99

298

Contamination in the detector at Address 99

Summary of Contents for STG 1.2

Page 1: ...em ring buses Smoke alarms failure and contamination messages are all forwarded from the detectors to the STG and shown on a display This makes it possible for a technician or custodian to supervise a...

Page 2: ...ervice mode Note The service mode is used to integrate a new detector or for system maintenance Operating mode The operating mode is accessed by storing the selected configuration All connected detect...

Page 3: ...rding to electrotechnical regulations Please ensure to connect the current ceiling smoke detector model The older version type DRM 3 3 has been replaced by version DRM 3 3 N Contact depictions are wit...

Page 4: ...ld be installed in a separate conductive and grounded cable trunking It is important to ensure that no potential differences between devices can occur on the Modbus perform equipoten tial bonding The...

Page 5: ...reafter the data register follows The register set is dependent on the query and can vary between 1 and 125 Register description Each register consists of 2 bytes With Modbus RTU it is possible to sen...

Page 6: ...lure LED lights up 0 Failure LED does not light up Bit 12 1 Operation LED lights up 0 Operation LED does not light up Bit 11 1 Alarm relay energized 0 Alarm relay de energized Bit 10 1 Failure relay e...

Page 7: ...ctor has an internal error 0 No internal error Bit 3 1 Malfunction Detector no longer recognized in the bus 0 No malfunction Bit 2 1 Alarm 0 No alarm Bit 1 0 0 No detector connected at this address 1...

Page 8: ...yte 3 Byte 4 Byte 5 STG address Function Error code CRC LSB CRC MSB Byte 0 Address of the STG 1 2 Byte 1 Function byte Here the function byte for the query is sent back However the MSB is set by the f...

Reviews: