Fire Protection  |  Data sheet No. 43104  | Version 02-2016  | 

7

 | 

8

Control unit STG 1.2

Status for the detector:

The status for each detector can be found at the following address:
Address:  

3 x n - 1 

n: Address of the detector = (1 - 99)

Bit 15 - 8 are always 0 and have no effect.

Bit 7

 

-

 

0:

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Service 

mode

Start

99 % 

Contamination

Address error

Failure

Alarm

Status

Status

Bit 7:

 

1: STG is in service mode

 

0: STG is in stored mode (operation)

Bit 6:

 

1: Detector is in start mode 

 

0: Detector is not in start mode

Bit 5:

 

1: Contamination alarm  

 

(detector is 99 % contaminated).

 

0: No contamination alarm

Bit 4:

 

1: Detector has an internal error

 

0: No internal error

Bit 3:

 

1: Malfunction

 

Detector no longer recognized in the bus

 

0: No malfunction

Bit 2:

 

1: Alarm

 

0: No alarm

Bit 1 - 0:

 

0: No detector connected at this address

 

1: DRM connected

 

2: DKM connected

 

3: Address error: multiple detectors are  

 

connected at this address

Measured value for the DRM:

255 = Alarm; < 255 = the chamber of the DRM is no longer in alarm state and the alarm can be deleted.
With one DKM, this register has no effect

The measured value for each DRM can be found at the following address:
Address:  

3 x n 

n: Address of the detector = (1 - 99)

Contamination of the DRM:

The degree of contamination in % for each DRM is located in this registry.
With one DKM, this register has no effect

Contamination for each DRM can be found at the following address:
Address:  

3 x n + 1 

n: Address of the DRM = (1- 99)

Summary of Contents for STG 1.2

Page 1: ...em ring buses Smoke alarms failure and contamination messages are all forwarded from the detectors to the STG and shown on a display This makes it possible for a technician or custodian to supervise a...

Page 2: ...ervice mode Note The service mode is used to integrate a new detector or for system maintenance Operating mode The operating mode is accessed by storing the selected configuration All connected detect...

Page 3: ...rding to electrotechnical regulations Please ensure to connect the current ceiling smoke detector model The older version type DRM 3 3 has been replaced by version DRM 3 3 N Contact depictions are wit...

Page 4: ...ld be installed in a separate conductive and grounded cable trunking It is important to ensure that no potential differences between devices can occur on the Modbus perform equipoten tial bonding The...

Page 5: ...reafter the data register follows The register set is dependent on the query and can vary between 1 and 125 Register description Each register consists of 2 bytes With Modbus RTU it is possible to sen...

Page 6: ...lure LED lights up 0 Failure LED does not light up Bit 12 1 Operation LED lights up 0 Operation LED does not light up Bit 11 1 Alarm relay energized 0 Alarm relay de energized Bit 10 1 Failure relay e...

Page 7: ...ctor has an internal error 0 No internal error Bit 3 1 Malfunction Detector no longer recognized in the bus 0 No malfunction Bit 2 1 Alarm 0 No alarm Bit 1 0 0 No detector connected at this address 1...

Page 8: ...yte 3 Byte 4 Byte 5 STG address Function Error code CRC LSB CRC MSB Byte 0 Address of the STG 1 2 Byte 1 Function byte Here the function byte for the query is sent back However the MSB is set by the f...

Reviews: