101
Sure Sort™ Operator Manual
OPEX Corporation
3.6. Electrical Requirements - North American
North American Sure Sort units require an AC line voltage of 120/208 VAC,
single phase, 60Hz (2 Lines + N Ground to Earth).
•
Line to Line voltage = 6%/-10%
•
Line to Neutral voltage = 6%/-10%
The machine is supplied with a 15 ft. (4.57 m) length of 10/4 SO cord, and
NEMA locking plug L14-30P, connected to the AC distribution enclosure of the
Induct conveyor module.
The customer must provide a 30 Amp maximum circuit breaker-protected
circuit using a NEMA rated L14-30R locking receptacle (Hubbell HBL2713 or
equivalent). See North American plug and receptacle diagram in Figure 3-13.
Figure 3-13: North American plug and receptacle requirements
FEMALE RECEPTACLE (SITE SIDE-CUSTOMER SUPPLIED)
30
A
25
0V
12
5/
X
W
Y
G
30
A
2
5
0
V
12
5/
FRONT VIEW
Y
W
X
G
(G) GRN
PROTECTIVE EARTH
(X) RED
LINE
(W) WHT
NEUTRAL
(Y) BLK
LINE
NEMA L14-30 RECEPTACLE
(HUBBELL # HBL2713 OR EQUIVALENT)
MALE PLUG (MACHINE SIDE)
NEMA L14-30 PLUG
(HUBBELL # HBL2711)
(G) GRN
PROTECTIVE EARTH
BACK (WIRING SIDE) VIEW
(W) WHT
NEUTRAL
(X) RED
LINE
(Y) BLK
LINE
FRONT VIEW
(W) WHT
NEUTRAL
BACK (WIRING SIDE) VIEW
(W) WHT
NEUTRAL
(G) GRN
PROTECTIVE EARTH
(G) GRN
PROTECTIVE EARTH
(X) RED
LINE
(X) RED
LINE
(Y) BLK
LINE
(Y) BLK
LINE
Summary of Contents for Sure Sort
Page 167: ...84 Sécurité Sure Sort Manuel de l opérateur OPEX Corporation Page laissée volontairement vide ...
Page 168: ...84 Safety Sure Sort Operator Manual OPEX Corporation Page intentionally blank ...
Page 316: ...158 Statistics Sure Sort Operator Manual OPEX Corporation Page intentionally blank ...
Page 318: ...Sure Sort Operator Manual G Glossary G 1 List of Acronyms 160 G 2 List of Terms 160 ...
Page 331: ...166 Sure Sort Manuel de l opérateur OPEX Corporation ...
Page 332: ...166 Sure Sort Operator Manual OPEX Corporation ...