Mass for PINs 2 and 6 – 9 

 

Standby mode 

Output 

Battery empty 

Output 

Normal operating mode 

Output 

Battery mode 

Output 

Table 2: PIN description 

 

Internal circuit, opener / closer 

The card has 3 relays which are controlled by the UPS system. Each relay has an additional jumper 
which defines the functionality of the respective relay: if PINs 1 and 2 are bypassed, the relay is oper-
ated as a closer (AC = active close). If PINs 2 & 3 are bypassed, it is operated as an opener (AO = ac-
tive open). 

 

Jumper 

Function 

Closer (AC) 

Opener (AO) 

JP 1 

Bypass mode 

PIN 5 & 2 closed 

PIN 5 & 2 open 

JP 2 

Normal operating mode 

PIN 5 & 8 closed 

PIN 5 & 8 open 

JP 3 

Standby mode 

PIN 5 & 6 closed 

PIN 5 & 6 open 

JP 4 

Battery empty 

PIN 5 & 7 closed 

PIN 5 & 7 open 

JP 5 

Battery mode 

PIN 5 & 9 closed 

PIN 5 & 9 open 

Table 3: Configuration of openers / closers 

 
If necessary, reposition the pre-installed jumpers as set out in Table 3. 
 

 

 

Figure 3: Jumper position for opener (AO) 

 

 

Figure 4: Jumper position for closer (AC) 

 

 
Example application: 

 

Compatibility list 

The AS400 / relay card is compatible with the following UPS models from ONLINE UPS systems AG: 
 
ZINTO series, model 2017 
Serial no. Z800, Z1000, Z1500, Z2000, Z3000 
 
XANTO series, model 2017 
Serial number X700/R, X1000/R, X1500/R, X2000/R, X3000/R, X6000, X10000, X1000031, X2000031 

Summary of Contents for AS400

Page 1: ...ände von der USV Anlage empfangen oder ein Shutdown Kommando an die USV Anlage senden Installation 1 Entfernen Sie die Schrauben an der Abdeckung des Slots an der USV Anlage 2 Schieben Sie die AS400 Relaiskarte in den Slot Die USV sollte während der Installation ausge schaltet sein Die Karte ist jedoch HOT PLUG fähig kann also auch während des USV Betriebes installiert werden 3 Befestigen Sie die ...

Page 2: ...is als Schließer AC active close betrieben Bei Überbrückung der PINs 2 3 erfolgt ein Betrieb als Öffner AO active open Jumper Funktion Schließer AC Öffner AO JP1 Bypassbetrieb PIN 5 2 geschlossen PIN 5 2 geöffnet JP 2 Normalbetrieb PIN 5 8 geschlossen PIN 5 8 geöffnet JP 3 Standbybetrieb PIN 5 6 geschlossen PIN 5 6 geöffnet JP 4 Batterie leer PIN 5 7 geschlossen PIN 5 7 geöffnet JP 5 Batteriebetri...

Page 3: ...ceive signals operating statuses from the UPS system or send a shut down command to the UPS system Installation 1 Remove the screws on the cover of the slot on the UPS system 2 Push the AS400 relay card into the slot The UPS should be switched off during installation How ever the card is HOT PLUG compatible meaning it can also be installed while the UPS is running 3 Secure the AS400 relay card usi...

Page 4: ... relay is oper ated as a closer AC active close If PINs 2 3 are bypassed it is operated as an opener AO ac tive open Jumper Function Closer AC Opener AO JP 1 Bypass mode PIN 5 2 closed PIN 5 2 open JP 2 Normal operating mode PIN 5 8 closed PIN 5 8 open JP 3 Standby mode PIN 5 6 closed PIN 5 6 open JP 4 Battery empty PIN 5 7 closed PIN 5 7 open JP 5 Battery mode PIN 5 9 closed PIN 5 9 open Table 3 ...

Page 5: ...e un comando di shutdown al sistema UPS Installazione 1 Rimuovere le viti sul coperchio dello slot sul sistema UPS 2 Inserire la scheda AS400 relè nello slot Si raccomanda di spegnere il sistema UPS durante l in stallazione La scheda tuttavia è di tipo HOT PLUG e può quindi essere inserita anche durante il funzionamento del gruppo di continuità 3 Fissare la scheda AS400 relè al sistema UPS con le ...

Page 6: ... ponti cello si trova tra i PIN 2 e 3 il suo funzionamento avviene come normalmente chiuso AO active open Ponticello Funzione Normalmente aperto AC Normalmente chiuso AO JP 1 Modalità Bypass Pin 5 e 2 chiusi Pin 5 e 2 aperti JP 2 Funzionamento normale Pin 5 e 8 chiusi Pin 5 e 8 aperti JP 3 Modalità Standby Pin 5 e 6 chiusi Pin 5 e 6 aperti JP 4 Batteria scarica Pin 5 e 7 chiusi Pin 5 e 7 aperti JP...

Reviews: