ONEAC Sinergy UPS User Manual
41
Load connection
hardwired
min
8
AWG/6 mm
2
max 6 AWG/16 mm
2
hardwired
min 6 AWG/10 mm
2
max 4 AWG/20 mm
2
hardwired
4 AWG/20 mm
2
Connections (continued)
Interfaces COM A
9-pin SUB-D, pin contacts
Interfaces COM B (optional)
9-pin SUB-D, outlet
External battery cabinet
keyed plug, 3-pole
hardwired
Min 8 AWG/6 mm
2
Max 4 AWG/20 mm
2
hardwired
4 AWG/20 mm
2
EPO
N/A
N/A
hardwired
removable terminal
block
Table 15. ONEAC Sinergy UPS (SE Series) (International)
UPS Model
SE61XI
SE101XI
Electrical Data
Rating
6 kVA
10 kVA
Input
Voltage 230
VAC
single-phase
Voltage range
170 V to 276 V
176 to 276 V
Frequency
50/60Hz ± 5%
Power factor (lambda)
≥
0.97
Battery
Integrated battery type
Lead-calcium, maintenance-free
Battery voltage (V)
240
Runtimes (min.)
(half load/full load)
25/8
30/12
Runtimes (min.),1 batteries
(half load/full load)
94/38
100/40
Output Voltage
Voltage
230 VAC, single-phase
Voltage tolerance
± 3%
Table 14. ONEAC Sinergy UPS (SE Series) North America
UPS Model
SE61XA
(SE41XA*)
SE101XA
(SE81*)
SE203XA
(SE153XA*)