ONEAC Sinergy UPS User Manual
33
Runtime (min.), 2 batteries
half load/full load
NA
140/60
215/92
140/57
Output
Voltage
208, 220, 230, 240 VAC
Voltage tolerance
±3%
Frequency with mains control
see input frequency
Frequency with internal control
50/60 Hz, ± 0.5%
Distortion factor (linear/non-linear load)
max. 4%/max. 7%
Permissible crest factor
3
Overload capability
130% for 1.5 sec., 110% for 10 sec.
output short-circuit proof
Common Data
Electrical safety
CE, EN 50091-1
Radio interference level
EN50091-2 class B
Interference immunity
IEC 801-2, level 4 / IC 801-3, level 3;
IEC 801-4, level 4 / IEC 801-5, level 2
Efficiency
> 83%
Protection class
IP 20
Cooling
Fan
Noise level mains operation
< 41 dBa
< 41 dBa
< 50 dBa
< 50 dBa
Noise level battery operation
< 45 dBa
< 45 dBa
< 50 dBa
< 50 dBa
Operating temperature
+50°F to +105°F (+10°C to +40°C)
recom59°F to +89°F (+15°C to +32°C)
Storage temperature
+5°F to +104°F (+15°C to +40°C)
at 0 to 50,000 feet (0 to 15,000 m)
Relative humidity
20% to 90%, condensation not permissible
Altitude
max. 10,000 ft (3000 m)
above 5,000 ft. (1500 m) max ambient temperature =95°F (35°C)
Table 8. ONEAC Sinergy UPS (S Series) (International)
UPS Model
S700I
S1000XI
S2000XI
S3000XI