background image

■ 

Overview and Features

By connecting the power monitor/sensor KM series (sold separately), the ZN-KMX21-

 

allows you to record the measured data of the power monitor/sensor (KM series) and set 

various operations.

● 

Display and judgment output

The display of the measured data can be switched with the 

 and 

 keys. Also, 

you can select the measurement target of the monitoring target and set the 

threshold value to output an alarm from the output terminal.

● 

Data output and viewing

Measurement values can be recorded to the unit's memory and the recorded 

measurement values can be stored into the SD card.

SD card : Data is in CSV format.

Measured values collected on multiple sensors can be displayed as a graph and 

combined as a single file by using the PC software that can be downloaded from 

the product page.

■ 

Names and Functions

Display

MODE key

Item select key

(    key)

Item select key

(    key)

SET/REC/STOP  key

Alarm output terminal

SD card slot

Sensor head
connector

AC adapter terminal

Mounting
screw hole

Reset switch

Screw hook hole

Function

Switches operating modes

Releases error and alarm (holding)

Cancels during settings

Moves setting items (upper direction)
Switches display screens (reverse direction)
Changes the setting value (increasing)
Moves the setting items (lower direction)
Switches the display screens (forward direction)
Changes the setting value (decreasing)

Confirms the setting value

Starts/stops record (holding)

Saves recorded data to the SD memory card.

Used to secure screws (M3x4 mm female hole)

For screw head hook

Restarts the unit.*

Name

 

MODE key

Item select key

(     key)

Item select key

(     key)

SET/REC/STOP key

Mounting screw hole

Screw hook hole

Reset switch

* Used when an SD card is not available when recording stops, or when error 
recovery cannot be made.

LAN port

■ 

Alarm Output Specifications

GND

External 
power 
supply

OUT

0V

Load

GND OUT

● 

Terminals

● 

Output Specifications

Terminal names are inscribed on the unit.
For wire used for a terminal block,consider the following.
Wire length

30m and less

(1) OUT

Judgment result allocated in THR mode is output.

(2) GND

Common terminal.

Do not directly connect the external power supply between OUT and GND.

Be sure to connect the load.

External power 
supply voltage

Load current

ON residual voltage

OFF leakage current

Internal circuit 
diagram

12 to 24 VDC

12 to 24 VDC  ±10%

45 mA max.

1.2 V max.

0.1 mA max.

■ 

Display Unit

Display

Meaning and operation when turned on

Communication with LAN cable.

Integral power consumption reset interval is set.
The setting is OFF when it is not displayed.

LAN cable is connected and network communication is possible.
Recording data into the internal memory. 
Recording start wait using timer when blinking.

Power is supplied.

Indicates the upper limit threshold value.
Indicates the maximum total momentary power value.
Indicates the minimum total momentary power value.
Indicates the average total momentary power value.
The unit is currently operating in RUN mode.
The unit is currently operating in FUN mode.
The unit is currently operating in THR mode.

SD card has been inserted.
SD card is being accessed while light blinking.

A total integrated power consumption has exceeded the specified 
upper threshold value.

■ 

7-segment Display List

■ 

Ratings

Item

Connectable Power Sensor/Monitor

Model

KM20-B40-FLK, KM50-C, KM50-E, KM100, KM-N1-FLK, KM-N2-FLK and KM-N3-FLK

ZN-KMX21-

Accessories

10 to 150 Hz, 0.7 mm double amplitude, acceleration: 50 m/s2 for each in X, Y and Z directions for 80 min

*

7

150 m/s2 in 6 directions (+/-X, +/-Y, and +/-Z directions), 3 times each

*

7

Instruction Sheet (This sheet), Startup Guide, 

Alarm Output Connector

*

7, AC Adapter

*

8, 

*

9, DC Cable

*

9, and Dedicated Connection Cable

ABS

IP30

Magnet mounting, screw mounting, hook, free standing

Approx. 500 g

Shock Resistance

Material

Degree of Protection

Mounting

Weight (in Package)

Max. Number of Connectable 
Power Sensor/Monitor Units

Display

Recording Interval

Recorded data

Operation Function

Recording Mode

External Output

Communication Interface

Memory Capacity (Internal)
Memory Capacity (External)

Power Supply

Current Consumption

Operating Temperature

Operating Humidity

Storage Humidity/Temperature

Insulation Resistance

Withstand Voltage

Vibration Resistance

7-seg. 5-digit 2-step LCD display, auxiliary information indicator displays

1 s, 2 s, 5 s, 10 s, 20 s, 30 s, 1 min.

Momentary power, Integrated power, Power factor, Sum of pulse input counts 1 and 2 

*

1

Integrated power total sum, integrated momentary power, electricity rate total sum

Continue mode

*

2, Ring mode 

*

3

Alarm output (Photocoupler output) 

*

4

Ethernet (10BASE-T, 100BASE-TX)

Internal memory: approx. 200 data items (at maximum load); approx. 6800 data items*5  (at minimum load)

SD card with SDHC compatibility (measured value and converted value saving/set value saving and reading): 

Recommended SD card: HMC-SD291(2GB)/HMC-SD491(4GB)(manufactured by OMRON) *6

DC input: 24 VDC±10%, AC adapter: 100 to 240 VAC/50 to 60 Hz

80 mA max. (at 24 VDC); 70 mA max. (AC adapter used)

Without Ethernet: -10°C to 40°C (no condensation or icing) With Ethernet: 0°C to 40°C (no condensation or icing)

20 to 85%RH (no condensation or icing)

-15°C to +60°C, 20 to 85%RH (no condensation or icing)

20 M

Ω

 (500 VDC)

1000 VAC, 50/60 Hz, 1 min.

31 units

*

1: Only supported for KM50-C and KM50-E.

*

2: Automatically writes the data to the SD memory card when the internal memory reaches its capacity and continues recording until the SD card memory capacity reaches its limit. The 

unit stops operation if there is no SD memory card inserted when the internal memory reaches its capacity. (Recording can be resumed after inserting an SD memory card and 

outputting the data to it at a press of button.)

*

3: Continues the recording of the latest measured values until the internal memory reaches its capacity. (If the internal memory capacity exceeds the capacity, data is overwritten from 

the oldest one in the memory.)

*

4: Output when the integrated power upper limit specified in THR mode is exceeded.

*

5: The maximum load is applied when 10 KM50-� units are connected; and the minimum load, when a single KM20-B40-FLK is connected.

*

6: When using third party SD card, please use industrial SD card (flash memory is SLC type) with high reliability and durability. Available SD card is SD standard or SDHC standard, 

Class 4 or higher, (SDXC standard can not be used) You must confirm the operation of third party SD card yourself.

*

7: The vibration resistance when mounted using the ZN9-EM01-S magnets (separately sold): 10 to 55 Hz, 0.3mm double amplitude, acceleration: 20m/s2 for each in X, Y and Z 

directions for 50 min. The installation place must be free from physical shock.

*

8: OMRON's XW4B-02B1-H1 connector.

*

9: This provided AC adapter must be used.

*

10: An AC adapter is provided in the ZN-KMX21 package; and a DC cable and ferrite core are included in the ZN-KMX21-A package.

Reviews: