background image

UNIT

No. of connected Power 
Sensor Station/Monitor 

1 to 31

Sets the number of connected Power Sensor Stations/Monitors.

1

REC

-

-

-

-

-

-

-

-

-

-

UTOFS

Unit No. offset setting

1 to 99

1

 FUN mode

 Major Error Displays and Countermeasures

E1100

E2001

E2002

E2003

E3000

E3002

E3003

E5000

E5001

E5002

HARD

Display

Description

Failed to write recorded data to the SD memory card. Insert a write-enabled SD card. Hold the MODE key for 3 seconds or more to cancel the error display.

A sensor different from the one auto-registered at startup is mounted. Restart the unit.

Communication with the sensor failed. Check the wiring between the sensor and the main unit. To cancel the error display, press and hold the MODE key for 3 seconds or more.

Failed to register the sensor in the initial processing on startup. Check the wiring between the sensor and the main unit, and restart the main unit.

If you turn on the power of the main unit before the sensor starts up, the sensor cannot be properly registered.

An SD memory card is not inserted. Insert a write-enabled SD card. Hold the MODE key for 3 seconds or more to cancel the error display.

The SD memory card is write-protected. Replace it with a write-enabled one. Hold the MODE key for 3 seconds or more to cancel the error display.

Failed to recognize the SD card. Insert a normal SD memory card. Hold the MODE key for 3 seconds or more to cancel the error display.

The setting data in the SD memory card is invalid e.g. an invalid model type or setting values. Hold the MODE key for 3 seconds or more to cancel the error display.

Failed to write setting files to the SD memory card. Insert a write-enabled SD card. Hold the MODE key for 3 seconds or more to cancel the error display.

There is no setting files contained in the SD memory card. Replace it with an SD memory card with setting files. 

Hold the MODE key for 3 seconds or more to cancel the error display.

There may be a failure on the hardware. Please contact the distributor or OMRON representative office. 

Overview

Recorded data writing failure

Sensor error

Sensor communications error

Sensor registration failed

No SD memory card inserted

Write-protected SD memory card

SD card recognition error

Invalid setting file data

Setting file writing failure

Setting file reading failure

Hardware error

■ 

List of Major Setting Items

RUN

FUN

THR

Mode

Description

Performs measurement/recording.

Sets various parameters.

Performs condition settings regarding alarm outputs.

Item

Measurement execution mode

Function setting mode

Threshold setting mode

● 

Operation mode

Item

Overview

Setting range

Description

Default

Specifies the starting (offset) unit number set for the Power Sensor/Monitor units to 

be connected. To use the unit numbers from No.10 to No.15, for example, "10" is set 

for the offset number (this setting item), while "6" is set for the number of Power 

Sensor/Monitor units to be connected (UNIT).

CYCLE

Recording interval setting

1s/2s/5s/10s

20s/30s/1min

Sets an recording interval of the measured value.

10s

Recording operation mode setting

CONT/RING

Sets operation for a case in which the internal memory capacity reaches the limit during recording.

CONT

CONT

Continue mode

Outputs a recorded value to the SD card and continues recording when the 
internal memory capacity reaches the limit during recording.

RING

Ring mode

Overwrites a recorded value to the SD card and continues recording when the 
internal memory capacity reaches the limit during recording.

INTEG

Setting of reset interval of 
integrated power consumption

OFF/30 m

1 h/24 h

Specifies the integrated power reset interval. The integrated power value is reset at the 
specified time interval, displaying the data belonging to that interval.

OFF

INIT

Setting initialization

Initializes the unit setting to the factory default value. Holding the SET/REC/STOP key  
starts initialization. Changing measurement  operation mode with the MODE key after 
DONE is displayed initializes the settings and the unit restarts.

ETC

Display setting for other items

OFF/DISP

Sets whether displaying other setting items.

OFF

RESTR

Read setting data

Recovers the setting from the SD card in which the setting data 

of the sensor unit is stored. Insert the SD card and hold the 

SET/REC/STOP key. Writing completes when DONE is displayed.

BCKUP

Write setting data

Writes the setting data of the sensor unit to the SD card as a backup. Insert the SD card 
and hold the SET/REC/STOP key. Writing completes when DONE is displayed.

CLOCK

Time setting

OFF/DISP

Sets whether displaying the time setting item.

OFF

RATE

Rate conversion setting

0.000 to 99.999

Sets the conversion coefficient to convert the integrated power consumption to rate.

0

CONV

Conversion unit setting

JPY/USD/EUR

CNY/KRW/CO2

Sets the conversion unit.

JPY

REREC

Power failure REC restoration

OFF/ON

Sets whether writing data and starting recording at next startup 
after power shutdown during recording.

OFF

INT H (Unit: kWh)

Displayed item

Setting range

0 to 99999

Overview

Upper threshold setting of the integrated power consumption (kWh or more)

Default

0

 THR mode

 Connected Units and Recording Interval

1 second

2 seconds

5 seconds

10 seconds

20 seconds

30 seconds

1 minute

Minimum recording interval

1 unit

Up to 2 units

Up to 6 units

Up to 12units

Up to 24 units

Number of units

Up to 31 units

The possible minimum recording interval varies depending on the number of power 
sensors/monitors. Check the following table of the number of units that can be 
connected to set the recording interval.

 Recording Interval and Internal Memory

Recording Interval

Approx. 1 hr. 50 min.

Approx. 3 hr. 40 min.

Approx. 9 hr. 30 min.

Approx. 19 hr.

Approx. 1 day 14 hr.

Approx. 2 days

Approx. 4 days

Min. load

(KM20 x 1 unit)

-

-

-

-

-

Approx. 1 hr. 40 min.

Approx. 3 hr. 20 min.

Max. load

(KM50 x 31 units)

Example of possible recording time in the internal memory

An example of the possible recording time in the internal memory that varies 
depending on the recording interval setting is shown below.

1 second

2 seconds

5 seconds

10 seconds

20 seconds

30 seconds

1 minute

IP

IP address display setting 

OFF/DISP

Sets whether performing IP address setting.

OFF

 Notice for Korea Radio Law

A급 기기(업무용 방송통신기자재)
이 기기는 업무용(A급) 전자파적합기기로서 판매자
또는 사용자는 이 점을 주의하시기 바라며,가정외의
지역에서 사용하는 것을 목적으로 합니다.

Suitability for Use

s

Omron Companies shall not be responsible for conformity with any standards, 
codes or regulations which apply to the combination of the Product in the 

Buyer’s application or use of the Product. At Buyer’s request, Omron will 

provide applicable third party certification documents identifying ratings and 
limitations of use which apply to the Product. This information by itself is not 
sufficient for a complete determination of the suitability of the Product in 
combination with the end product, machine, system, or other application or 
use. Buyer shall be solely responsible for determining appropriateness of the 

particular Product with respect to Buyer’s application, product or system. 

Buyer shall take application responsibility in all cases. 

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING 
SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE 
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, 

AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND 

INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL 
EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.

O c t ,   2 0 1 4

D

OMRON Corporation

      Industrial Automation Company

 Contact:  www.ia.omron.com

Tokyo, JAPAN

OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.

Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road # 05-05/08 (Lobby 2), 

Alexandra Technopark, 
Singapore 119967

Tel: (65) 6835-3011/Fax: (65) 6835-2711

OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower, 
200 Yin Cheng Zhong Road, 
PuDong New Area, Shanghai, 200120, China

Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200

OMRON EUROPE B.V.
Sensor Business Unit
Carl-Benz-Str. 4, D-71154 Nufringen, Germany

Tel: (49) 7032-811-0/Fax: (49) 7032-811-199

Regional Headquarters

Reviews: