background image

6

Switching Mode Power Supply 

ZEN-PA03024

Safety Precautions

Minor electric shock may occasionally occur. Do not disassemble 
the product or touch internal parts.

Minor fires may occasionally occur. Do not attempt to repair or 
modify the product.

Minor burns may occasionally occur. Do not touch the product 
while power is being supplied or immediately after power is 
turned OFF.

Minor fires may occasionally occur. Tighten terminal screws to a 
torque of 0.5 to 0.6 N·m so that they do not become loose.

Minor electric shock may occasionally occur during operation. Do 
not touch the input and output terminals while power is being 
supplied.

The product may occasionally be damaged. Do not allow any 
clippings or cuttings to enter the product during installation work.

Working voltage can be 350 V max. inside. This voltage can be 
also available 10 s after the switch off.

Precautions for Safe Use

The following precautions must be observed to ensure safety.

Mounting

• Mounting Direction 

(Refer to Installation in Engineering Data on page 4.)

The internal parts may occasionally deteriorate or be broken due to 
adverse heat dissipation depending on the mounting status. Do not 
use the product in any way other than the standard mounting 
direction.

• Mounting Space

Make sure that sufficient heat dissipation is provided when 
installing the Power Supply to increase its long-term reliability. 
Install the product in a location that allows a natural airflow to occur 
around the Power Supply. 
We recommend using End Plates (PFP-M) to secure the Power 
Supply and to ensure that a space of at least 10 mm is maintained 
between Power Supplies.

If the installation space above and below the Power Supply is less 
than 50 mm, reduce the ambient temperature by 5

°

C. A minimum 

space of 20 mm is required.

Note: 1. Convection of air

2. 50 mm min.

3. 10 mm min.

Wiring

• Minor fire may possibly occur. Ensure that input and output 

terminals are wired correctly.

• Use the following material for the wires to be connected to the 

Power Supply to prevent smoking or ignition caused by abnormal 
loads.

Use solid wires. Always attach pin crimp terminals when using 
stranded wire. The stripping distance should be 6.5 mm.

Recommended Wire Type

• Do not apply more than 100 N force to the terminal block when 

tightening the terminals.

• Be sure to remove the sheet covering the product before turning 

ON the Power Supply and confirm that nothing is interfering with 
heat dissipation.

Installation Environment

• Do not use the Power Supply in locations subject to shocks or 

vibrations. In particular, install the Power Supply as far away as 
possible from contactors or other devices that are a vibration 
source.

• Install the Power Supply well away from any sources of strong, 

high-frequency noise.

Operating and Storage Conditions

• When installing the Power Supply, check for any signs that the 

product or packaging has been struck. If internal parts have been 
damaged, overvoltages may be output depending on the location of 
the damage.

• Internal parts may occasionally deteriorate or be damaged. Store 

the Power Supply at a temperature of 

-

25 to 65

°

C and a humidity of 

10% to 90%.

• Internal parts may occasionally deteriorate or be damaged. Do not 

use the Power Supply in areas outside the derating curve (i.e., the 
area shown by shading (1) in the graph on page 4). For UL508 
Listing, the surrounding air temperature should be 40

°

C.

• Use the Power Supply at a humidity of 10% to 90%.

• Do not use the Power Supply in locations where condensation may 

occur due to high humidity or where temperature changes are 
severe.

• Do not use the Power Supply in locations subject to direct sunlight.
• Do not use the Power Supply in locations where liquids, foreign 

matter, or corrosive gases may enter the interior of products.

Overload Protection

• Internal parts may possibly deteriorate or be damaged if a short-

circuited or overcurrent state continues during operation.

• Internal parts may possibly deteriorate or be damaged if the Power 

Supply is used for applications with frequent inrush current or 
overloading at the load end. Do not use the Power Supply for such 
applications.

Charging the Battery

• This product is not intended to function as a battery charger. If a 

battery is to be connected as the load, mount an overcurrent 
limiting circuit and an overvoltage protection circuit.

Standard Mounting

Valid

Horizontal Mounting

Invalid

Other Mounting

Invalid

 

!

CAUTION

(See note 1.)

(See note 1.)

(See note 2.)

(See note 2.)

ZEN-PA03024

(See note 3.)

Solid wire

Cross section 0.5 to 2.5 mm

2

 

(Equivalent to AWG20 to AWG14)

Stranded wire

Cross section 0.5 to 2.5 mm

2

 

(Equivalent to AWG20 to AWG14)

Pin crimp terminals

Dia.: 1.1 to 2.3 mm

Summary of Contents for ZEN-PA03024

Page 1: ...lel operation Output voltage 24 VDC Output current 1 3 A Capacity 30 W Safety standards UL508 60950 1604 CSA C22 2 No 14 60950 213 EN60950 VDE0806 EN50178 VDE0160 Uses lead free soldering Six language instruction manual provided Model Number Structure Model Number Legend 1 Unit PA Power supply unit 2 Power Ratings 030 30 W 3 Output voltage 24 24 V Ordering Information List of Models Accessories Or...

Page 2: ... note 2 105 to 135 of rated load current inverted L drop intermittent automatic reset Parallel operation Yes 2 units max For details refer to the derating curve in Engineering Data For DC input parallel operation is possible only for 110 to 350 VDC Series operation No Others Ambient temperature Operating Refer to the derating curve in Engineering Data with no icing or conden sation Storage 25 to 7...

Page 3: ...ler V V DC OUTPUT Fuse 2A Overcurrent circuit Current detection circuit ZEN PA03024 No Name Function 1 AC input terminal L1 Connect the input line to this termi nal A fuse is included in the cir cuit 2 AC input terminal L2 N Connect the input line to this termi nal Negative pole for DC input 3 DC output terminals V Connect the load lines to these ter minals 4 DC output terminals V Connect the load...

Page 4: ...m possible damage by overcurrent When the output current rises above 105 min of the rated current the protection function is triggered decreasing the out put voltage When the output current falls within the rated range the overload protection function is automatically cleared The values shown in the above diagrams are for reference only Note 1 Internal parts may occasionally deteriorate or be dama...

Page 5: ...ting Holes 4 7 Sliding 13 max ZEN PA03024 4 5 15 25 25 25 25 10 10 7 3 0 15 35 0 3 27 0 15 1 4 5 15 25 25 25 25 15 10 10 1 000 27 24 16 29 2 1 1 5 50 11 5 10 6 2 1 8 1 35 5 35 3 1 8 1 3 4 8 5 16 12 44 3 16 5 10 34 8 35 0 3 Mounting Track PFP 100N PFP 50N PFP 100N2 End Plate PFP M Spacer PFP S 1 000 500 See note Note The values shown in parentheses are for the PFP 50N M4 x 8 pan head screw ...

Page 6: ...re than 100 N force to the terminal block when tightening the terminals Be sure to remove the sheet covering the product before turning ON the Power Supply and confirm that nothing is interfering with heat dissipation Installation Environment Do not use the Power Supply in locations subject to shocks or vibrations In particular install the Power Supply as far away as possible from contactors or ot...

Page 7: ...djust the output voltages of the Power Supplies to the same value In Case there is No Output Voltage The possible cause for no output voltage may be the presence of an overload or overvoltage condition or may be due to the functioning of a latching protective device The latching protection may operate if a large amount of surge voltage such as a lightening surge occurs while turning ON the Power S...

Page 8: ...NTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATI...