320
Frequency inverters
Control circuit
Note:
1.The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1
for S6 and multi-step speed setting 2 for S7.
2.Do not use this power supply for supplying any external equipment.
3.When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode.
Type
No.
Signal name
Function
Signal level
Digit
al inp
u
t
sign
als
S1
Forward run/stop command
Forward run when ON; stopped when OFF.
24 VDC, 8 mA
photocoupler isolation
S2
Reverse run/stop command
Reverse run when ON; stopped when OFF.
S3
External fault input
*1
Fault when ON.
Functions are selected by
setting H1-01 to H1-05.
S4
Fault reset
*1
Reset when ON
S5
Multi-step speed reference 1
*1
(Master/auxiliary switch)
Auxiliary frequency reference when
ON.
S6
Multi-step speed reference 2
*1
Multi-step setting 2 when ON.
S7
Jog frequency reference
*1
Jog frequency when ON.
SC
Digital input common
–
–
SN
Digital input neutral
–
–
SP
Digital input power supply
+24 VDC power supply for digital inputs
24 VDC, 250 mA max.
*2
Ana
log inpu
t signal
s
+V
15 V power output
15 V power supply for analog references
15 V (max. current: 20 mA)
A1
Frequency reference
0 to +10 V/100%
0 to +10 V (20 k
Ω
)
A2
Multi-function analog input
4 to 20 mA/100%
0 V to +10 V/100%
0 to 20 mA/100%
Function is selected by
setting H3-09.
4 to 20 mA (250
Ω
)
0 V to +10 V (20 k
Ω
)
0 to 20 mA (250
Ω
)
AC
Analog reference common
–
–
E(G)
Shield wire, optional ground line
connection point
–
–
Dig
ita
l o
utp
ut
sign
als
M1
Running signal
(1NO contact)
Operating when ON.
Multi-function
contact outputs
Relay contacts
contact capacity:
1 A max. at 250 VAC
1 A max. at 30 VDC
*3
M2
M3
Zero speed
Zero level (b2-01) or below when ON
M4
MA
Fault output signal
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
MB
MC
A
nalog
o
utp
ut
signa
ls
FM
Multi-function analog output
(frequency output)
0 to 10 V, 10 V=100%
output frequency
Multi-function analog
output 1
0 to +10 V max. ±5%
2 mA max.
AC
Analog common
–
AM
Multi-function analog output
(current monitor)
0 to 10 V, 10V = 200% of the inverter
rated current
Multi-function analog
output 2
RS-
485/
422
R+
MEMOBUS communications input
For 2-wire RS-485, short R+ and S+ as well as R- and S-.
Differential input,
photocoupler isolation
R-
S+
MEMOBUS communications output
Differential input,
photocoupler isolation
S-
IG
Signal common
–
–
Internal heatsink
55 ˚C
45 ˚C
Upper cover
Upper part air
temperature
-10 to 55 ˚C
Open chassis
type inverter
Inverter inlet
temperature
-10 to 45 ˚C
Peripheral
temperature 40 ˚C
Lower cover
Heatsink
Remove the upper and lower covers
for the models of 15 kW or less in
200 V and 400 V classes.
When using open chassis type inverters of 200 V/400 V
22 kW or more, secure spaces for eyebolts and wiring
of the main circuit.
Upper cover
50 mm or more
50 mm or more
120 mm or more
120 mm or more
30 mm or more
30 mm
or more
Heatsink
Lower cover
Side spaces
Top and bottom spaces
Cover MTG screw
Air
Air