background image

2

Frequency inverters

Type designation

200 V class

400 V class

Specifications

IP20 single-phase: CIMR-V7AZ

B0P1

B0P2

B0P4

B0P7

B1P5

B2P2

B4P0

IP65 single-phase: CIMR-V7TZ

---

---

B0P405

B0P705

B1P505

B2P205

---

IP20 three-phase: CIMR-V7AZ

20P1

20P2

20P4

20P7

21P5

22P2

24P0

Maximum permissible motor output kW

1

1.

Based on a standard 4-pole motor for maximum applicable motor output. Select the inverter model within the allowable motor rated current

0.12

0.25

0.55

1.1

1.5

2.2

4.0

O

u

tp

u

t

ch

ar

ac

te

ri

st

ic

s

Inverter capacity  kVA

0.3

0.6

1.1

1.9

3.0

4.2

6.7

Rated output current  A

0.8

1.6

3.0

5.0

8.0

11.0

17.5

Max. output voltage

Proportional to input voltage: 0..240 V

Max. output frequency

400 Hz

P

o

w

er

 

su

p

p

ly

Rated input voltage

and frequency

Single-phase 200..240 V 50/60 Hz

3-phase 200..230 V 50/60 Hz

Allowable voltage 

fluctuation

-15%..+10% 

Allowable frequency 

fluctuation

+5%

IP20 three-phase: CIMR-V7AZ

40P2

40P4

40P7

41P5

42P2

43P0

44P0

45P5

47P5

IP65 three-phase: CIMR-V7TZ

40P405

40P705

41P505

42P205

43P005

44P005

Maximum permissible motor output kW

1

1.

Based on a standard 4-pole motor for maximum applicable motor output. Select the inverter model within the allowable motor rated current

0.37

0.55

1.1

1.5

2.2

3.0

4.0

5.5

7.5

O

u

tp

u

ch

ar

ac

te

ri

st

ic

s

Inverter capacity  kVA

0.9

1.4

2.6

3.7

4.2

5.5

7.0

11.0

14.0

Rated output current  A

1.2

1.8

3.4

4.8

5.5

7.2

9.2

14.8

18.0

Max. output voltage

Proportional to input voltage: 0..400 V

Max. output frequency

400 Hz

P

o

w

er

su

p

p

ly

Rated  input voltage

and frequency

3-phase 380..460 VAC, 50/60 Hz

Allowable voltage

fluctuation

-15%..+10% 

Allowable frequency

fluctuation

+5%

Voltage

B: Single-phase 200 VAC

2: Three-phase 200 VAC

4: Three-phase 400 VAC

Z: European standard specifications

Inverter

V7 series

A: With digital operator (with potentiometer)

T: V7 IP65 type with digital operator 

 

( without potentiometer )

C I M R — V 7 A Z B 0 P 1 0

Max. applicable motor output
 0P1: 0.1 kW

 7P5: 7.5 kW

~

"P" indicates a decimal 

   point

[                               ]

Protective enclosure:
0:   IP20
1:   NEMA1
05: IP65

Varispeed V7

3

Commom specifications

Model number

CIMR-V7AZ-

@

CIMR-V7TZ-

@

Specifications

C

o

n

tr

o

l f

u

n

ct

io

n

s

Control methods

Sine wave PWM (V/f control, sensorless vector control)

Output frequency range

0.1..400 Hz

Frequency tolerance

Digital set value: ±0.01% (-10..+50 ºC)

Analogue set value: ±0.5% (25 ±10 ºC)

Resolution of frequency set value

Digital set value: 0.01 Hz (<100 Hz), 0.1 Hz (>100 Hz)

Analogue set value: 1/1000 of maximum frequency

Resolution of output frequency

0.01 Hz

Overload capability

150%/60 s

Frequency set value

0..10 V (20 k

Ω

), 4..20 mA (250 

Ω

), 0..20 mA (250 

Ω

)

Pulse train input, frequency setting value (selectable)

Braking torque
(short term peak torque)

Up to 200 W 150% or more

550 W to 1.1 kW 100% or more

1.5 kW 50% or more

>1.5 kW 20% or more

Continuous braking torque approx. 20% without, 150% with external braking resistor

F

u

n

ct

io

n

al

it

y

Binary inputs

7 freely programmable inputs

Binary outputs

1 relay output, 2 freely programmable open collector outputs

Analogue output

1 programmable analogue output (0..10 V)/pulse output

Analogue inputs

2 analogue inputs, 0..10 V, 4..20 mA, 0..20 mA

Braking/acceleration times

0.01..6000 s

Display

Optionally frequency, current or set value

Error and status LED

P

ro

te

ct

io

n

 f

u

n

ct

io

n

Motor overload protection

Electronic thermal overload relay

Instantaneous overcurrent

Motor coasts to a stop at approx. 250% of inverter rated current

Overload

Motor coasts to a stop after 1 minute at 150% of inverter rated output current

Overvoltage

Motor coasts to a stop if DC bus voltage exceed 410 V  (double for 400 V class)

Undervoltage

Stops when DC bus voltage is approx. 200 V or less (double for 400 V class)

(approx. 160 V or less for single-phase series)

Momentary power loss

Following items are selectable: not provided (stop if power loss is 15 ms or longer), continuous operation  

if power loss is approx. 0.5 s or shorter, continuous operation

Cooling fin overheat

Protected by electronic circuit

Stall prevention level

Individual levels during accel/constant speed.  Decel ON/OFF available. During decel enable/disable selectable.

Cooling fan fault

Detected by electronic circuit (fan lock detection)

Ground fault

Protected by electronic circuit (operation level is approx. 250% of rated output current)

Power charge indication

RUN lamp stays ON or digital operator LED stays ON until the DC bus voltage becomes 50 V or less. 

(Charge LED is provided for 400 V)

A

m

b

ie

n

co

n

d

it

io

n

s

Degree of protection

IP20, NEMA1, IP65

Cooling

Self cooling for 200 V 0.1..0.4 kW (3 or single phase) and for 400 V 0.2..0.75 kW

Cooling fan for 200 V 0.75 to 7.5 kW and for 400 V 1.5 to 7.5 kW

Ambient temperature

Open air mounting: -10 ºC..50 ºC

Wall mounting: -10 ºC..40 ºC

Ambient humidity

95% (without condensation)

Storage temperature

-20 ºC..+60 ºC (short-term temperature during transportation)

Installation

Indoor (no corrosive gas, dust, etc.)

Installation height

Max. 1000 m

Vibration

10 to 20 Hz, 9.8 m/s

2

 max; 20 to 50 Hz, 2 m/s

2

 max

Varispeed V7

6

Summary of Contents for V7

Page 1: ...Advanced Industrial Automation Decentralised control Intelligence on board Expanded functionality NEW V7 INVERTERS Improvin g o n pe rfe ctio n ...

Page 2: ... operate in the most severe environments Hence it goes far beyond normal expectations standard published specifications For example it delivers 40 more current than any inverter on the market And it does this under severe conditions such as high carrier frequency high temperature large voltage fluctuations etc The result is that you get what s in the box and much more Now that s quality beyond a d...

Page 3: ...with perfect control of your machines Packaging feed Positioning Product feed Product out Speed S Travel distance blue area S Time Nominal speed S S Standard stop at nominal speed Stopping without position control Stopping with position control Preferred stop position Unexpected stop position New features Sensor less vector controller ensures 100 at 0 5Hz Compact size available in IP20 or IP65 Sil...

Page 4: ...ion board based on Omron s market leading PLC technology offers you all the cost saving benefits of PLC functionality It not only equips the V7 with extra functionality for a broad range of digital control tasks it also leads to significant savings by eliminating the need for a separate PLC The board s inverter based architecture provides for wireless installation and seamless access to all V7 par...

Page 5: ... can be customized to meet specific application Examples Traverse sofware S 9381 For detailed information please refer to case software section Ratings 200 V Class single phase 0 1 to 4 kW 200 V Class three phase 0 1 to 7 5 kW 400 V Class three phase 0 2 to 7 5 kW System configuration See note See note Option frames are needed for V7 IP65 type Communication unit 3G3IV PCN329 E Inverter to PC cable...

Page 6: ...P4 40P7 41P5 42P2 43P0 44P0 45P5 47P5 IP65 three phase CIMR V7TZ 40P405 40P705 41P505 42P205 43P005 44P005 Maximum permissible motor output kW1 1 Based on a standard 4 pole motor for maximum applicable motor output Select the inverter model within the allowable motor rated current 0 37 0 55 1 1 1 5 2 2 3 0 4 0 5 5 7 5 Output characteristics Inverter capacity kVA 0 9 1 4 2 6 3 7 4 2 5 5 7 0 11 0 14...

Page 7: ...d Motor coasts to a stop after 1 minute at 150 of inverter rated output current Overvoltage Motor coasts to a stop if DC bus voltage exceed 410 V double for 400 V class Undervoltage Stops when DC bus voltage is approx 200 V or less double for 400 V class approx 160 V or less for single phase series Momentary power loss Following items are selectable not provided stop if power loss is 15 ms or long...

Page 8: ... can be set or monitored while this indicator is lit 3 Mode key Switches the simplified LED setting and monitor item indicators in sequence Parameter being set will be canceled if this key is pressed before entering the setting Increment key Increases multi function monitor numbers parameter numbers and parameter set values Decrement key Decreases multi function monitor numbers parameter numbers a...

Page 9: ... 42 1 0 1 1 B0P7 2 108 140 96 118 5 64 1 5 Fan cooled 1 5 B1P5 156 96 1 5 2 2 B2P2 140 163 128 71 2 2 4 0 B4P0 170 180 158 2 9 Three phase 400 V 0 37 40P2 2 108 128 92 96 118 5 16 1 0 Self cooled 0 55 40P4 110 34 1 1 1 1 40P7 140 64 1 5 1 5 41P5 156 1 5 Fan cooled 2 2 42P2 1 5 3 0 43P0 140 143 128 71 2 1 4 0 44P0 2 1 Voltage class Max applicable motor output kW Inverter model CIMR V7AZ Figure Dime...

Page 10: ... H2 H3 D1 Single phase 200 V 0 55 B0P405 4 280 240 142 260 228 165 38 275 44 3 4 Self cooled 1 1 B0P705 4 3 Fan cooled 1 5 B1P505 3 7 2 2 B2P205 4 2 Three phase 400 V 0 55 40P405 280 240 142 260 228 165 38 275 44 4 2 Self cooled 1 1 40P705 4 3 Fan cooled 1 5 41P505 3 7 2 2 42P205 3 7 3 0 43P005 4 1 4 0 44P005 4 1 W 1 D D1 W H 2 H 1 H Figure 4 W 2 H 1 6 4 3x PG25 Varispeed V7 10 ...

Page 11: ...1 H2 H3 D1 D2 Single phase 200 V 0 55 B0P405 5 280 240 180 260 228 165 38 275 44 38 3 6 Self cooled 1 1 B0P705 4 5 Fan cooled 1 5 B1P505 3 9 2 2 B2P205 4 4 Three phase 400 V 0 55 40P405 280 240 180 260 228 165 38 275 44 38 4 4 Self cooled 1 1 40P705 4 5 Fan cooled 1 5 41P505 3 9 2 2 42P205 3 9 3 0 43P005 4 3 4 0 44P005 4 3 Figure 5 W 2 D D1 H 1 H D2 W W 1 6 4 H 2 H 1 3x PG25 2x PG12 Frequency inve...

Page 12: ... S1 S2 S3 S4 S5 S6 S7 RP FS FR FC SC PNP NPN Shield connection terminal Speed reference pulse train 33 kHz max Frequency setting power supply 12 V 20 mA Speed frequency reference 0 to 10 V 20 kΩ OR 4 to 20 mA 250 Ω 0 V P2 P1 MA MB MC PC Multi function photocoupler output 48 VDC 50 mA or less Running Speed agree Grounding Fault Multi function output 250 VAC 1 A or less 30 VDC 1 A or less IM twisted...

Page 13: ...ion 7 Factory setting JOG command SC Multi function input selection Common Common for control signal Analog input signals RP Speed reference pulse train input 33 kHz max FS Power supply terminal for frequency setting 12V allowable current 20 mA max FR Speed frequency reference 0 to 10 VDC 20 kΩ or 4 to 20 mA 250 Ω 0 to 20 mA 250 Ω resolution 1 1000 FC Frequency reference common 0 V 1 CN2 Multi fun...

Page 14: ... 51 4 82 8 113 6 176 4 Model CIMR V7AZ 40P2 40P4 40P7 41P5 42P2 44P0 45P5 47P5 Inverter capacity kVA 1 4 2 6 3 7 4 2 5 5 7 0 11 14 Rated current A 1 8 3 4 4 8 5 5 7 2 8 6 14 8 18 Heat loss W Fin 15 1 30 3 45 8 50 5 58 2 73 4 168 8 209 6 Inside unit 15 0 24 6 29 9 32 5 37 6 44 5 87 7 99 3 Total heat loss 30 1 54 9 75 7 83 0 95 8 117 9 256 5 308 9 W Inverter Inverter Inverter 50 mm min 5 5 and 7 5 K...

Page 15: ...A CIMR V7AZB0P10 0 25 Kw 1 6 A CIMR V7AZB0P20 0 55 Kw 3 0 A CIMR V7AZB0P40 1 1 Kw 5 0 A CIMR V7AZB0P70 1 5 Kw 8 0 A CIMR V7AZB1P50 2 2 Kw 11 0 A CIMR V7AZB2P20 4 0 Kw 17 5 A CIMR V7AZB4P00 3x200 V 0 12 Kw 0 8 A CIMR V7AZ20P10 0 25 Kw 1 6 A CIMR V7AZ20P20 0 55 Kw 3 0 A CIMR V7AZ20P40 1 1 Kw 5 0 A CIMR V7AZ20P70 1 5 Kw 8 0 A CIMR V7AZ21P50 2 2 Kw 11 0 A CIMR V7AZ22P20 4 0 Kw 17 5 A CIMR V7AZ24P00 5 ...

Page 16: ...MR V7AZ Schaffner Rasmi Rated current A Weight kg 3 Phase 200 VAC 20P1 20P2 20P4 20P7 3G3MV PFI2010 SE 3G3MV PFI2010 E 10 0 8 21P5 22P2 3G3MV PFI2020 SE 3G3MV PFI2020 E 20 1 0 24P0 3G3MV PFI2030 SE 3G3MV PFI2030 E 30 1 1 25P5 27P5 3G3MV PFI2050 E 50 2 3 Single Phase 200 VAC B0P1 B0P2 B0P4 3G3MV PFI1010 SE 3G3MV PFI1010 E 10 0 6 B0P7 B1P5 3G3MV PFI1020 SE 3G3MV PFI1020 E 20 1 0 B2P2 3G3MV PFI1030 S...

Page 17: ...way Used for running or stopping the inverter setting or referencing parameters and monitoring output frequency output current or similar items through CANopen communication with the host controller SI T1 V7 MECHATROLINK II option card Used for running or stopping the inverter setting or referencing parameters and monitoring output frequency output current or similar items through MECHATROLINK II ...

Page 18: ... and monitoring software tool CX One Computer software Configuration and monitoring software tool DATA 15 5 STOP 78 3 07 18 2 0 72 88 3 46 5 0 2 80 3 15 4 4 4 DIA MTG HOLES 58 2 28 11 0 43 70 2 76 15 5 0 61 23 1 0 91 50 1 97 10 5 0 41 30 4 1 20 1 7 0 07 12 2 0 48 68 2 68 56 2 20 4 M4 SPOT FACING DEEP 3 5 0 14 4 4 4 dia MTG holes 4 M4 spot facing deep 3 5 0 14 DSPL STOP RESET DATA ENTER 78 3 07 18 ...

Page 19: ... 101 100 1 125 21P5 260 100 1 125 60 2 2 22P2 B2P2 700 70 1 120 22P2 260 70 1 120 60 4 0 24P0 B4P0 620 62 1 100 23P7 390 40 1 125 32 5 5 25P5 25P5 520 30 1 115 9 6 7 5 27P5 27P5 780 20 1 125 9 6 400 V three phase 0 37 40P2 751 750 1 230 750 0 55 40P4 751 750 1 230 40P7 70 750 1 230 750 1 1 40P7 751 750 1 130 40P7 70 750 1 130 510 1 5 41P5 401 400 1 125 41P5 260 400 1 125 240 2 2 42P2 301 300 1 115...

Page 20: ... 11 00 www omron industrial com More Omron representatives www omron industrial com Control Systems Programmable logic controllers Human machine interfaces Remote I O Motion Drives Motion controllers Servo systems Inverters Control Components Temperature controllers Power supplies Timers Counters Programmable relays Digital panel indicators Electromechanical relays Monitoring products Solid state ...

Reviews: