10

Intelligent Flag I/II 

V600-HA

Power Supply Voltage

Do not impose any voltage exceeding the rated voltage range. Doing
so, or applying alternating current (100 VAC) may cause the product
to explode or burn.

Load Short-circuiting

Do not short-circuit the load connected to the product or connect to
the power supply. Doing so may cause the product to explode or
burn.

Wiring

Avoid wiring mistakes such as incorrect polarity in the power supply.
Wiring mistakes may cause the product to explode or burn.

Correct Use

Grounding

The FG line is provided for grounding to the earth. When using the
Amplifier in an environment where it is exposed to large amounts of
noise or if the V600-HA

@

91/-HA

@

81/-HA

@

92 Amplifier malfunctions,

provide a Class-3 ground (ground resistance of 100 

 or less). Note

that sharing the grounding wire with other equipment or grounding to
the beam of a building will adversely affect the grounding effect.

Mounting

Amplifier Spacing
When installing V600-HA

@

91/V600-HA

@

81/V600-HA

@

92 Amplifi-

ers in a row, provide a minimum space of 10 mm between Amplifiers
in order to prevent them from being affected by the heat produced by
each Amplifier.

When housing the Amplifiers in a box, provide a fan or ventilation
opening for radiating the heat.

When wiring power cables, which carry large current such as motor
drive cables, near the V600-HA

@

91/81/92 Amplifiers, conduct neces-

sary tests to make sure that the installation conditions are fully satis-
fied.

I/O Interface Requirements

1.

The TRG input must be 10 ms min.

2.

The INHIBIT input must be 20 ms min.

3.

Minimum of 5 ms is required as the transfer time of the Read/
Write Selection Input (W/R).

4.

The read data output must be read after the Normal End Output is
set to ON.

Connecting the Sensor

Hold the black part of the connector, line up the notch and push it in
until it clicks.

Compatibility with the SRAM Memory 
Type Data Carrier

1.

If the Data Carrier is stationary in the transmission area for a long
time when using the V600-HA

@

91/81 in the AUTO mode, or when

using the V600-HAR92, it will drastically reduce the battery life.
Therefore, stop the oscillation in the sensor either by turning off
the power of the V600-HA

@

91/81/92 Amplifier or by setting the

Inhibit input to ON.

2.

Use a Data Carrier that has the oscillation frequency of 530 kHz.
Note that the following models manufactured before February
1991 cannot be used. 

V600-D2KR01

V600-D2KR02

Precautions When Using the AUTO 
Mode

If transmitting to the Data Carrier while it is traveling under the AUTO
mode, conduct tests to make sure that the travel speed and installa-
tion conditions are fully satisfied.

V600-HA

†

91/81/92

Other equipment

FG

Less than 100 

V600-HA

†

91/81/92

Other equipment

FG

Less than 100 

OK

NG

10 mm min.

V600-HA

†

91/81/92

Summary of Contents for V600-HA

Page 1: ... consumption 130 mA max Input Transistor output or contact output Short circuit current 3 mA typical IN terminal and 0 V short circuit OFF voltage 15 to 30 VDC ON voltage 0 to 5 VDC Input impedance 8 2 kΩ Applied voltage 30 VDC max Transistor output OFF voltage 15 to 30 VDC Input impedance 8 2 kΩ Short circuit current 3 mA typical for 0 V short circuit of INHIBIT TRG ON voltage 0 to 5 VDC Applied ...

Page 2: ...ta output lines Interface Cable Note The interface cable connector is not waterproof If there is a possibility that the connector may be exposed to water keep it inside the control box The maximum cable length is 10 m Vibration resistance Destruction 10 to 150 Hz 0 3 mm double amplitude with 4 sweeps of 8 min each in 3 directions Destruction 10 to 150 Hz 1 5 mm double amplitude with 4 sweeps of 8 ...

Page 3: ...erature 10 to 60 C 10 to 70 C Storage temperature 25 to 75 C Ambient humidity 35 to 95 Insulation resistance 50 MΩ at 500 VDC between cable terminal and case Dielectric strength 1 000 VAC 50 60 Hz for 1 min between cable terminal and case leakage current 1 mA max Degree of protection IEC60529 IP67 Vibration resistance Destruction 10 to 2 000 Hz 3 mm double amplitude with 2 sweeps of 15 min each in...

Page 4: ...600 HS61 V600 HS63 V600 HS67 V600 D23P53 V600 D23P54 V600 D23P55 V600 D23P61 V600 D23P66N V600 D23P66SP V600 D23P72 V600 D23P71 V600 D8KR12 V600 D8KR04 V600 D2KR16 Wireless transmission Wireless transmission Terminal block wiring Connector connection Connector connection Connector connection Host Sensor Cable length fixed to 2 m Amplifier Cable length fixed to 0 5 m with connector interface Connec...

Page 5: ... Y 0 10 20 30 10 20 30 Y X 10 20 30 X Y V600 HS51 V600 D23P53 V600 HS51 V600 D23P54 V600 HS51 V600 D23P55 V600 HS51 V600 D23P61 V600 HS51 V600 D23P66N V600 HS51 V600 D8KR12 0 4 8 4 8 Y X 4 8 Y X Y X 0 4 8 12 4 8 12 Y X 4 12 8 0 5 10 15 5 10 15 5 10 15 Y X X Y 0 5 10 15 20 25 5 10 15 20 25 Y X 5 10 15 20 X Y 0 10 20 30 10 20 30 Y X 10 20 30 X Y 0 10 20 30 10 20 30 Y X 10 20 30 X Y V600 HS61 V600 D2...

Page 6: ...30 50 40 Y X 10 20 30 40 50 Y X 0 20 40 60 20 40 60 Y X 20 40 60 X Y 0 20 40 60 20 40 60 Y X 20 40 60 X Y 0 20 40 60 20 40 60 Y X 20 40 60 Y X 0 20 40 60 80 20 40 60 80 Y X 20 40 60 80 Y X 0 20 40 60 80 20 40 60 80 Y X 20 40 60 X Y V600 HS63 V600 D23P55 V600 HS63 V600 D23P61 V600 HS63 V600 D23P66N V600 HS63 V600 D23P66SP V600 HS63 V600 D23P71 V600 HS63 V600 D23P72 V600 HS63 V600 D8KR12 V600 HS63 V...

Page 7: ...80 20 40 60 80 60 20 40 Y 80 0 20 40 60 80 20 40 60 80 80 60 20 40 X Y Y X X 0 20 40 60 80 100 20 40 60 80 100 100 80 60 20 40 X Y Y X 0 20 40 60 80 100 20 40 60 80 100 100 80 60 20 40 X Y Y X 0 20 40 60 80 20 40 60 80 80 60 20 40 X Y Y X 0 20 40 60 80 20 40 60 80 80 60 20 40 X Y Y X 0 40 80 120 40 80 120 120 40 80 X Y Y X V600 HS67 V600 D23P66N V600 HS67 V600 D23P66SP V600 HS67 V600 D23P71 V600 H...

Page 8: ...0 HAM91 HAM81 otherwise an external input error may result 1 Maximum switching current 1 A min 2 Minimum switching current 10 mA min 3 Response time ON to OFF 3 ms min The following OMRON products cannot be connected to this product CVM1 OD219 C20H C28H C40H or C60H Programmable Controllers Sensor Controllers other than from the S3D2 Series When using a contact output pay careful attention to chat...

Page 9: ...ich carry large current such as motor drive cables near the V600 HA 91 81 92 Amplifiers conduct neces sary tests to make sure that the installation conditions are fully satis fied I O Interface Requirements 1 The TRG input must be 10 ms min 2 The INHIBIT input must be 20 ms min 3 Minimum of 5 ms is required as the transfer time of the Read Write Selection Input W R 4 The read data output must be r...

Page 10: ... Amplifier V600 HAR91 HAR81 Enlarged Section of Mounting Hole Two mounting holes Vinyl insulated round cord 5 8 mm dia 13 conductor cable standard length 0 5 m XG4E 2031 30û 4 4 5 5 30 21 17 5 28 3 36 3 61 8 89 8 2 98 68 5 55 30 80 35 2 500 mm 28 1 44 7 25 6 25 2 M4 89 0 2 21 0 2 Mounting Hole Dimensions ...

Page 11: ... Mounting Hole Two mounting holes Vinyl insulated round cord 5 8 mm dia 23 conductor cable standard length 0 5 m XG4E 2631 30 4 4 5 5 30 21 17 5 28 3 36 3 61 8 52 3 44 3 89 8 2 98 68 5 75 55 30 80 35 2 500 mm 28 1 52 3 25 6 25 2 M4 89 0 2 21 0 2 Mounting Hole Dimensions ...

Page 12: ...ound cord 5 8 mm dia 23 conductor cable standard length 0 5 m Mounting Hole Dimensions 35 49 5 33 7 M12X1 9 6 dia 13 7 dia Vinyl insulated round cord 4 mm dia Connector 2 lock washers 2 lock nuts Case Brass Transmission window ABS resin Filter Epoxy resin Cable PVC oil resistant 49 5 30 5 18 18 10 4 5 8 5 6 5 13 7 dia Vinyl insulated round cord 4 mm dia Connector Detection surface 12 0 2 2 3 5X5 m...

Page 13: ...2 R5 Bushing Power indicator green Case ABS resin Filter Epoxy resin Cable PVC oil resistant Connector Bushing Vinyl insulated round cord 6 mm dia 51 5 25 13 8 dia 10 10 11 30 20 Power indicator green 100 90 0 2 50 5 5 50 100 90 0 2 Four 4 5 dia mounting holes 14 Case ABS resin Filter Epoxy resin Cable PVC oil resistant Vinyl insulated round cord 9 mm dia 7 0 2 mm dia 13 conductor cable standard l...

Page 14: ...r V600 HAM91 HAM81 HAR92 Model L m V600 A60R 60M 2 V600 A61R 61M 5 V600 A62R 62M 10 Vinyl insulated round cord 9 mm dia 7 0 2 mm dia 23 conductor cable standard length 2 m XG5M 2632 N Connector 7 6 10 6 37 6 30 30 5 20 5 20 5 20 5 L 100 0 330 5 0 ...

Page 15: ...stems railroad sys tems aviation systems medical equipment amusement machines vehicles safety equipment and installations subject to separate industry or government regulations Systems machines and equipment that could present a risk to life or property Please know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE...

Reviews: