7-1
7-1 Standard Specification List
7
Specifications
7Specifications
7-1 Standard Specification List
3-phase 200-V Class
3-phase 400-V Class
Item
3-phase 200-V class
Model name (3G3MX-)
A2002
A2004
A2007
A2015
A2022
A2037
A2055
A2075
Applicable motor
capacity
*1
kW
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
HP
1/4
1/2
1
2
3
5
7.5
10
Rated output
capacity (kVA)
200 V
0.6
1.0
1.7
2.8
3.8
6.1
8.3
11.1
220 V
0.6
1.1
1.9
3.0
4.2
6.6
9.1
12.2
Rated input voltage
3-phase (3-wire) 200 to 240 V ±10%, 50/60 Hz ±5%
Rated output voltage
*2
3-phase 200 to 240 V AC (according to the incoming voltage)
Rated output current (A)
1.6
3.0
5.0
8.0
11.0
17.5
24.0
32.0
Weight (kg)
0.7
0.85
0.9
1.8
1.8
1.8
3.5
3.5
Cooling method
Self-cooling
Forced-air-cooling
Braking
torque
At short-time deceleration
*3
At capacitor feedback
Approx. 50%
Approx. 20% to 40%
Approx. 20%
For mounting
discharge resistance
Approx. 150%
Approx. 100%
Approx. 80%
Minimum connection
resistance (
Ω
)
100
100
50
50
35
35
17
17
Item
3-phase 400-V class
Model name (3G3MX-)
A4004
A4007
A4015
A4022
A4037
A4055
A4075
Applicable motor
capacity
*1
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
HP
1/2
1
2
3
5
7.5
10
Rated output
capacity (kVA)
400 V
1.0
1.7
2.6
3.8
6.0
9.0
11.1
440 V
1.1
1.9
2.8
4.1
6.5
9.9
12.1
Rated input voltage
3-phase (3-wire) 380 to 480 V ±10%, 50/60 Hz ±5%
Rated output voltage
*2
3-phase 380 to 480 V AC (according to the incoming voltage)
Rated output current (A)
1.5
2.5
3.8
5.5
8.6
13.0
16.0
Weight (kg)
1.3
1.7
1.8
1.8
1.8
3.5
Cooling method
Self-cooling
Forced-air-cooling
Braking
torque
At short-time deceleration
*3
At capacitor feedback
Approx. 50%
Approx. 20% to 40%
Approx. 20%
For mounting
discharge resistance
Approx.
150%
Approx. 100%
Approx. 80%
Minimum connection
resistance (
Ω
)
180
180
180
100
100
70
70
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...
Page 252: ......