SGE/SCC

16

Application Examples 

(A Safety Relay Unit or Safety Controller other than the G9SB can be used.)

Note:

The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming 
the usage conditions.

Application Overview

• The power supply to the motor M is turned OFF when pressure is applied to the edge.

• The power supply to the motor M is turned OFF when the S2 detects that the guard is opened.

• The power supply to the motor M is kept OFF until pressure is not applied to the edge (, the reset switch S1 is pressed for manual reset) and the guard is closed.

PL/safety category

Model

Stop category

Reset

PLe/3 equivalent

Safety Edge/Edge Controller SGE+SCC
Safety Door Switch D4GS-N/D4NS/D4BS
Safety Relay Unit G9SB

0

Manual/Auto

24 VDC

+

SGE
Safety Edge

N

o short-circ

u

it

8.2 kW

SCC-1224
SCC-1224

N

D

(Man

u

al reset/DC po

w

er s

u

pply)

AC po

w

er s

u

pply

SCC a

u

to reset

S1

0V

A1

S11 S12

S11 S12

X1 X2

Z1 Z2

Z1 Z2

23

14

32

A2

B1

B2

A1

A2

B1

B2

KM2

KM1

M

31

24

13

G9SB-2002-A

K2

K1

Feed

b

ack loop

KM1

KM2

KM1

KM2

A1

A2

T11

T12

T31 T32

13

23

14

24

T21

T22

OPE

N

S2

Note 1: 

This fig

u

re sho

w

s the SGE Safety Edge 

w

ith no press

u

re on it and the S1 reset s

w

itch 

b

efore it is pressed.

         2: 

There is no polarity for X1 and X2.

31-32

2 to 3s

KM1 and KM2 (NO)

Safety door switch S2

KM1 and KM2 (NC)

G9SB 

13-14, 23-24

Pressured

Not pressured

SGE 
safety edge 

SCC edge controller

13-14, 23-24

SCC-1224 
Edge Controller

31-32

SCC-1224ND
Edge Controller

2 to 3s

KM1 and KM2 (

N

O) 

KM1 and KM2 (

N

C) 

G9SB  

13-14, 23-24 

SCC-1224

N

Edge Controller 

SCC-1224  
Edge Controller 

Safety door s

w

itch S2 

31-32 

Reset s

w

itch S1 

SGE  
safety edge  

SCC edge controller 

13-14, 23-24 

31-32 

2 to 3s 

2 to 3s 

Press

u

red 

N

ot press

u

red 

S1: Reset switch 

S2: Safety door switch 

KM1 and KM2: Magnet contactor 

M1: 3-phase motor 

Timing Chart (SCC Auto Reset) 

Timing Chart (SCC Manual Reset) 

Summary of Contents for SCC Series

Page 1: ...Safety Edge Edge Controller SGE SCC Introducing the New Safety Edge Friendly to Human and Machines ...

Page 2: ...s or objects Its elastic material and shock absorption properties soften the impact on such persons or objects The SCC Edge Controller conforms to PLe Safety Category 3 Occurrance of any short circuits and or breaks are continually monitored and the status shown with LED indicators Edge mounted to moving parts such as doors and fences of SGE Safety Edge SCC Edge Controller SCC Edge Controller Prot...

Page 3: ...in your application or equipment Select any length from 150 mm to 6 100 mm with increments of 50 mm An L shaped mounting base is also provided depending on the mounting location except the SGE 125 series Select wiring from four types 2 wire connector male female cable terminating resistor and cable length 100 mm or any length from 500 mm to 10 000 mm with increments of 500 mm for both ends of the ...

Page 4: ...ompression force at the actuation distance Five series with different cross sectional shapes are provided 1 Values of actuation distance and actuation force are characteristic values tested according to EN 1760 2 using a test object of ϕ80 mm and actuating point C3 under a test temperature of 20 C and test speed v 10 mm s Refer to Characteristics on page 11 for details 2 The SGE 225 can be used fo...

Page 5: ...ination 0 2 wire cable on both sides 2 2 wire cable on one side terminating resistor on the other side 8 2kΩ 0 25W 3 Connector cable on one side male connector cable on the other side female 4 Connector cable on one side male terminating resistor on the other side 8 2kΩ 0 25W 5 2 wire cable on one side connector cable on the other side female 2 wire cable 2 wire cable Safety edge 2 wire cable Term...

Page 6: ...ble termination method for both ends of a safety edge and add a code at the end of the cable length Note When using a terminating resistor cable termination method is not required to be selected Step 6 Direction of Cable Connection Determine the direction of the cable that is connected to the Safety Edge Note Refer to Model Number Legend for 5 and 6 in the above table Orders can be customized by s...

Page 7: ...ble on one side connector cable on the other side female Code Specification 4 digit number 0150 to 6 100 mm in increments of 50 mm Code Specification None Standard Mounting Base L L shaped Mounting Base Config No of 2 5 6 Cable Length 5 digits Terminal code Cable Length 5 digits Terminal code 0 00100 to 10000 C 00100 to 10000 C 2 00100 to 10000 C Terminating resistor None 3 00100 to 10000 M 00100 ...

Page 8: ...ty output Auxiliary output Ratings Terminal Model DPST NO SPST NO One shot timer that turns ON between two and three seconds after the application of pressure to the safetyedge 24 VDC Screw terminals SCC 1224 SPST NO Kept ON during the application of pressure to the safety edge SCC 1224ND Appearance Cross sectional dimensions including a standard mounting base 1 Actuation distance 2 Material Model...

Page 9: ... ON during the application of pressure to the safety edge Rated resistive load 250 VAC 2 5 A 30 VDC 2 5 A Terminating resistor 8 2 kΩ Ambient operating temperature 20 to 50 C With no icing or condensation Degree of protection IP20 Terminal type Screw terminals Terminal tightening torque 0 5 to 0 6 N m Mounting method DIN rail mounted Weight factory set 210 g Model Item SGE 125 SGE 225 4 SGE 245 SG...

Page 10: ...city at 20 C 2 2 Resistance Against Permanent Deformation 3 4 2 Abrasion 3 3 Elongation at Tear 4 5 3 Cold Flexibility 2 2 Material TPE EPDM Model SGE 125 SGE 225 SGE 245 SGE 365 Features Tolerance 1 2 3 4 5 6 1 2 3 4 5 6 Heat Stability 4 2 Oxidation Stability 1 1 UV Stability 1 1 Weather Ozone Resistance 1 1 Flame Resistance 6 6 Gas Permeability 3 4 Material TPE EPDM Model SGE 125 SGE 225 SGE 245...

Page 11: ...teristic Values for Test Speed v 10 mm s SB A SV 250N SV 400N B1 B2 Safety output Closed Safety output Open Test Temperature 20 C Actuating Force FA N 42 Actuating Distance SB mm 2 6 Overtravel Distance Sv at 250N in mm 8 1 Overtravel Distance Sv at 400N in mm 9 5 Test Temperature 20 C Actuating Force FA N 43 Actuating Distance SB mm 6 4 Overtravel Distance Sv at 250N in mm 7 7 Overtravel Distance...

Page 12: ...e an 8 mm hole has to be drilled in the appropriate place Carefully remove the burr from both sides 5 The connecting wire and the cable end with the terminal resistor have to be placed in the mounting base 6 In order to make fitting the safety edge easier the mounting base and the safety edge should be sprayed with soapy water Once the soap suds have evaporated the safety edge is firmly fitted in ...

Page 13: ...efault settings Remove the jumper if safety output 1 and 2 are not connected in series Safety output 2 23 24 Name Description Power supply LED indicator Green Lights when the power supply is ON Active LED indicator Yellow Lights when pressure is applied to the SGE safety edge blinks during interlock state When pressure is released the interlock is reset and turned OFF Error LED indicator Red Light...

Page 14: ... 23 31 S12 S11 Z2 Z1 X2 X1 B2 B1 Z2 S11 S12 Z1 B2 X1 X2 B1 A2 31 32 A1 14 23 24 13 SCC 1224 Power Actuate Fault Aux Output 114 22 5 99 Edge Controller SCC 1224 SCC 1224ND Terminal Arrangement SGE 125 2 5 2 8 1 3 15 7 25 SGE 225 25 20 17 9 5 5 25 2 5 25 20 17 9 5 5 46 2 5 SGE 245 SGE 245L 25 20 17 9 5 5 46 2 5 60 ...

Page 15: ... 125 For SGE 225 245 14 13 25 2 25 14 13 2 16 For SGE 225 245 L shaped 14 35 15 2 For SGE 365 14 35 15 17 6 2 For SGE 365 L shaped 35 4 M8 1 12 4 Black 1 Brown 3 Blue Connector male Terminal code M Pin arrangement Connector female Terminal code F Pin arrangement 33 9 12 4 Black 3 Blue 1 Brown ...

Page 16: ...rcuit 8 2 kW SCC 1224 SCC 1224ND Manual reset DC power supply AC power supply SCC auto reset S1 0V A1 S11 S12 S11 S12 X1 X2 Z1 Z2 Z1 Z2 23 14 32 A2 B1 B2 A1 A2 B1 B2 KM2 KM1 M 31 24 13 G9SB 2002 A K2 K1 Feedback loop KM1 KM2 KM1 KM2 A1 A2 T11 T12 T31 T32 13 23 14 24 T21 T22 OPEN S2 Note 1 This figure shows the SGE Safety Edge with no pressure on it and the S1 reset switch before it is pressed 2 Th...

Page 17: ...er supply of the specified voltage Do not use power supplies with large ripples or power supplies that intermittently generate incorrect voltages 5 Do not under any circumstances use the product for loads that exceed the product s contact ratings such as the switching capacity switching voltage and switching current During so may not only result in faulty insulation contact deposition contact fail...

Page 18: ...e product or expose it to excessive vibration or mechanical shock The product may be damaged and may not function properly 2 Do not apply loads on a certain location of the Safety Edge for a long period of time It may damage the Safety Edge 3 Do not use the Safety Edge submerged in water or in locations continuously subject to splashes of water 3 Adhesion of solvent Do not allow organic solvents s...

Page 19: ...ions or uses not described in this document Nuclear energy control systems combustion systems railroad systems aviation systems medical equipment amusement machines vehicles safety equipment and installations subject to separate industry or government regulations Systems machines and equipment that could present a risk to life or property Please know and observe all prohibitions of use applicable ...

Page 20: ... JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tower 200 Yin Cheng Zhong Road PuDong New Area Shanghai 200120 China Tel 86 21 5037 2222 Fax 86 21 5037 2200 OMRON SCIENTIFIC TECHNOLOGIES INC 6550 Dumbarton Circle Fremont CA 94555 U S A Tel 1 510 608 3400 Fax ...

Reviews: